SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
February 15, 2024
Scott Carpenter, Manager
Linville Land Harbor Prop Owners Assoc
Email: scott.carpenter@linvillelandharbor.com
SUBJECT: Compliance Inspection Report
Linville Land Harbor WWTP
NPDES WW Permit No. NC0022756
Avery County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Linville Land Harbor
WWTP on 1/24/2024. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0022756. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Mara Chamlee with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
mara.chamlee@deq.nc.gov.
Sincerely,
Daniel Boss, Assistant Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Laserfiche, C.L. Lewis (ORC)
DocuSign Envelope ID: A6199FCA-935C-42EF-8B4A-3A7656D49A24
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0022756 24/01/24 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Linville Land Harbor WWTP
20 Land Harbor Plz
Newland NC 28657
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
09:30AM 24/01/24 20/06/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Cecil L Lewis/ORC/828-733-8300/
Other Facility Data
11:00AM 24/01/24 25/01/31
Name, Address of Responsible Official/Title/Phone and Fax Number
William D Twiggs,PO Box 160 Linville NC 286460160//828-733-8300/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Mara G Chamlee DWR/ARO WQ/828-296-4500/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: A6199FCA-935C-42EF-8B4A-3A7656D49A24
2/15/2024
2/15/2024
NPDES yr/mo/day
24/01/24
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Mara Chamlee, with the Asheville Regional Office, conducted a Compliance Evaluation Inspection of
the Linville Land Harbor WWTP on January 29, 2024. This inspection was conducted to determine
whether the facility is being operated and maintained in compliance with NPDES Permit No.
NC0022756. Mr. C.L. Lewis (ORC) was present and assisted with the inspection.
The facility appears to be well maintained and operated. There were no compliance issues found.
The following items were noted during the inspection:
1) Operations & Maintenance- Mr. Lewis noted that there is one restauraunt on site that has a grease
trap and at present it does not cause grease problems for the facility. He also noted that they do
receive some grease from the houses within the development, but it has not caused major issues up
to this point.
2) Equalization Basins- Mr. Lewis indicated that the collection system has issues with I&I and the EQ
basin helps stabilize the plant during times of heavy flow.
3) Effluent sampling- The thermometer was not in the unit at the time of the inspection, but in the
facility office. The thermometer should be replaced to the sampler when sampling events occur.
NC0022756 17 (Cont.)
Page#2
DocuSign Envelope ID: A6199FCA-935C-42EF-8B4A-3A7656D49A24
Permit:NC0022756
Inspection Date:01/24/2024
Owner - Facility:
Inspection Type:
Linville Land Harbor WWTP
Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Process controls analyzed include DO, temperature, settleability. Mr. Lewis noted that
there is one restauraunt on site that has a grease trap and at present, it does not
cause grease problems for the facility. He also noted that they do receive some grease
from the houses within the development, but it has not caused major issues up to this
point.
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Page#3
DocuSign Envelope ID: A6199FCA-935C-42EF-8B4A-3A7656D49A24
Permit:NC0022756
Inspection Date:01/24/2024
Owner - Facility:
Inspection Type:
Linville Land Harbor WWTP
Compliance Evaluation
Record Keeping Yes No NA NE
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
The facility utilizes Water Tech Labs for processing of their samples.Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Mr. Lewis indicated that there is a backup manual bar screen if needed. Screenings
are hauled to the Town of Boone landfill.
Comment:
Equalization Basins Yes No NA NE
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Mr. Lewis indicated that the collection system has issues with I&I and the EQ basin
helps stabilize the plant during times of heavy flow.
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Page#4
DocuSign Envelope ID: A6199FCA-935C-42EF-8B4A-3A7656D49A24
Permit:NC0022756
Inspection Date:01/24/2024
Owner - Facility:
Inspection Type:
Linville Land Harbor WWTP
Compliance Evaluation
Aeration Basins Yes No NA NE
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Mr. Lewis indicated that the digester is pumped as needed by Appalachian Pumping
and Triple T Pumping companies. The blowers are on timers and the decant goes back
to the headworks.
Comment:
Disinfection-Gas Yes No NA NE
Are cylinders secured adequately?
Page#5
DocuSign Envelope ID: A6199FCA-935C-42EF-8B4A-3A7656D49A24
Permit:NC0022756
Inspection Date:01/24/2024
Owner - Facility:
Inspection Type:
Linville Land Harbor WWTP
Compliance Evaluation
Disinfection-Gas Yes No NA NE
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No.
7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-____-____)
If yes, then when was the RMP last updated?
There are three 150-lb. cylinders on site. Mr. Lewis indicated that the chlorine contact
chamber is pumped out as needed along with the digester.
Comment:
De-chlorination Yes No NA NE
Type of system ?Gas
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
The flow meter was last calibrated by Water Tech Labs on August 16, 2023.Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Page#6
DocuSign Envelope ID: A6199FCA-935C-42EF-8B4A-3A7656D49A24
Permit:NC0022756
Inspection Date:01/24/2024
Owner - Facility:
Inspection Type:
Linville Land Harbor WWTP
Compliance Evaluation
Effluent Sampling Yes No NA NE
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
The thermometer was not in the unit at the time of the inspection, but in the facility
office. The thermometer should be replaced to the sampler when sampling events
occur.
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
There is a gas pump on site at the Linville Land Harbor in the event of an extended
power outage. The generator is monitored and serviced by Linville Land Harbor
personel.
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Page#7