HomeMy WebLinkAboutWQ0044259_Final Permit_20240301ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
RICH DEMING — CHIEF EXECUTIVE OFFICER
CAROLINA POULTRY POWER RG2, LLC
3730 NORTH MAIN STREET
FARMVILLE, NORTH CAROLINA 27828
Dear Mr. Deming,
NORTH CAROLINA
Environmental Quality
March 1, 2024
Subject: Permit No. WQ0044259
Carolina Poultry Power —
Wilson CUS
Reclaimed Water Conjunctive
Utilization System
Wilson County
In response to your permit application request received on March 27, 2023, and subsequent
additional information received on August 7, 2023 and December 11, 2023, we are forwarding herewith
Permit No. WQ0044259 dated March 1, 2024, to Carolina Poultry Power RG2, LLC for the construction
and operation of the subject reclaimed water conjunctive utilization facilities.
This permit is effective from the date of issuance through July 31, 2030, and is subject to the
conditions and limitations therein. The Permittee shall submit a renewal application no later than
February 1, 2030.
Please pay attention to the monitoring requirements listed in Attachments A and B. Failure to
establish an adequate system for collecting and maintaining the required operational information may result
in future non-compliance.
This permit can be contested as provided in Chapter 150B of the North Carolina General Statutes
by filing a Petition for a Contested Case Hearing (Petition) with the North Carolina Office of Administrative
Hearings (OAH) within 30 calendar days. Requirements for filing a Petition are set forth in Chapter 150B
of the North Carolina General Statutes and Title 26 of the North Carolina Administrative Code. Those
interested in filing may access additional information regarding the requirements for filing a Petition and
Petition forms at the OAH website or by calling the OAH Clerk's Office at (919) 431-3000. A party filing
a Petition shall serve a copy of the Petition on the Department of Environmental Quality's Office of General
Counsel at 1601 Mail Service Center, Raleigh, NC 27699-1601. If the party filing the Petition is not the
Permittee, then the party shall also serve the Permittee pursuant to G.S. 15013-23(a).
� North Carolina Department of Environmental Quality I Division of Water Resources
512 North Salisbury Street 11617 Mail Service Center I Raleigh, North Carolina 27699-1617
NORTH CAROLINA +
D^wr"^^00 ro^m^^v n^a� /'� 919.707.9000
Mr. Rich Deming
March 1, 2024
Page 2 of 2
Included with this permit are Division -approved plans and specifications. If you need additional
information concerning this permit, please contact Erick Saunders at (919) 707-3659 or
erickson.saunders&deq.nc. og_v.
Sincerely,
DocuSigned by
A:
��PiG / h021L
D1043082680C483...
Richard E. Rogers, Jr., Director
Division of Water Resources
cc: Wilson County Health Department (Electronic Copy)
Raleigh Regional Office, Water Quality Regional Operations Section (Electronic Copy)
Kim Melvin, PE — Project Integration, Inc. (Electronic Copy)
City of Wilson — Water Reclamation Facility (Electronic Copy)
Laserfiche File (Electronic Copy)
Digital Permit Archive (Electronic Copy)
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENTAL QUALITY
RALEIGH
RECLAIMED WATER CONJUNCTIVE UTILIZATION SYSTEM PERMIT
Pursuant to the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended,
and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Carolina Poultry Power RG2, LLC
Wilson County
FOR THE
operation of a reclaimed water conjunctive utilization facility consisting of the:
construction and operation of. a 1,777,604 gallon heat exchange storage lagoon (3,006,662 gallons total);
dual 1,218 gallon per minute (GPM) heat exchange loop pumps; 2,888 linear feet (LF) of ambient
temperature reclaimed water distribution line; eighteen 69.4 GPM heat exchange spray irrigation nozzles;
4,507 LF of 8-inch carbon steel hot reclaimed water return line; and all associated piping, valves, controls,
and appurtenances; and the
construction and operation of. 495 LF of 6-inch carbon steel supply lines capped for future use at the boiler
building and buildings at the Hominy Creek WRF; 435 LF of 2-inch carbon steel hot pipe capped for future
use as a hot water supply at the Hominy Creek WRF primary clarifiers; and associated piping, valves,
controls, and appurtenances
to serve the Carolina Poultry Power — Wilson CUS, with no discharge of wastes to surface waters, pursuant
to the application received on March 27, 2023, subsequent additional information received on August 7,
2023, and December 11, 2023, and in conformity with the Division -approved plans and specifications
considered a part of this permit.
This permit is effective from the date of issuance through July 31, 2030, and is subject to the following
conditions and limitations:
WQ0044259 Version 1.0 Shell Version 230811 Page 1 of 10
I. SCHEDULES
1. Prior to construction and operation of the reclaimed water heat exchange spray system, the Permittee
shall provide verification that the Permittee has removed any residual material in the existing heat
exchange storage lagoon and has tested the heat exchange storage lagoon liner. The Permittee shall
submit this documentation via the Non -Discharge online portal_ [15A NCAC 02T .0108(b)(1)(A)]
2. Upon completion of construction and prior to operation of this permitted facility, the Permittee shall
submit an engineering certification from a North Carolina licensed Professional Engineer certifying
that the permitted facility has been constructed pursuant to G.S. 143-215.1, Administrative Code Title
15A Subchapter 02U, this permit, and the Division -approved plans and specifications. For phased and
partially certified facilities, the Permittee shall retain the responsibility to track further construction
approved under this permit and shall provide a final engineering certification upon project completion.
The Permittee shall submit the Engineering Certification via the Non -Discharge online portal_ [15A
NCAC 02T .0116(a), 02U .01161
3. The Permittee shall notify the Raleigh Regional Office, telephone number (919) 791-4200, at least two
business days in advance of the initial operation of the constructed facilities so that the Division can
conduct a startup inspection. [15A NCAC 02T .0108(b)(1)(A), 02U .0108]
4. Prior to the operation of the reclaimed water utilization system, the Permittee shall install a gauge to
monitor freeboard levels in the 1,777,604 gallon heat exchange storage lagoon. [15A NCAC 02T
.0108(b)(1)(B), 02U .0108, 02U .0401(h)]
Prior to the operation of the reclaimed water conjunctive utilization system, the Permittee shall submit
a final Operation and Maintenance Plan. The Permittee shall submit the final Operation and
Maintenance Plan via the Non -Discharge online portal_ [15A NCAC 02T .0108(b)(1)(B), 02U .0108,
02U .0801(a)]
6. If the permitted facilities change ownership or the Permittee changes its name, the Permittee shall
submit a permit modification request on Division -approved forms within 90 days of the change of
ownership. The Permittee shall comply with all terms and conditions of this permit until the Division
transfers the permit to the successor -owner. [G.S. 143-215.1(d3)]
7. The Permittee shall request renewal of this permit on Division -approved forms no later than February
1, 2030. [ 15A NCAC 02T .0105(b), 02T .0109, 02U .0105, 02U .0109]
II. PERFORMANCE STANDARDS
The Permittee shall operate and maintain the subject reclaimed water conjunctive utilization facilities
so there is no discharge to surface waters, nor any contravention of groundwater or surface water
standards. In the event the facilities do not perform as designed, including the creation of nuisance
conditions due to improper operation and maintenance, the Permittee shall take immediate corrective
actions, including Division -required actions, such as the construction of additional or replacement
reclaimed water conjunctive utilization facilities, or cessation of reclaimed water conjunctive
utilization. [15A NCAC 02T .0108(b)(1)(A), 02U .0108]
2. This permit shall not relieve the Permittee of its responsibility for contravention of groundwater or
surface water standards resulting from the operation of this facility. [ 15A NCAC 02T .0108(b)(1)(A),
02U .01081
3. The Permittee shall only utilize generated reclaimed water at the sites and for the activities specified in
Attachment B. [ 15A NCAC 02U .0401(a)]
WQ0044259 Version 1.0 Shell Version 230811 Page 2 of 10
4. The Permittee shall connect the reclaimed water utilization system to an anemometer designed to
prevent irrigation during high wind events (i.e., sustained wind speeds more than 25 miles per hour
(mph)). For wind speeds more than 25 mph, the Permittee shall inspect the pond to verify spray is not
drifting beyond the pond perimeter. [15A NCAC 02T .0108(b)(1)(A)]
5. The conjunctive utilization of generated reclaimed water does not negate, preclude, or invalidate Permit
Nos. NCO023906 and WQ0018709. [15A NCAC 02T .0108(b)(1)(A), 02U .0108]
6. The Permittee shall tag or label all reclaimed water valves, storage facilities, and outlets to warn the
public or employees that the reclaimed water is not for drinking. [ 15A NCAC 02U .0403(b)]
7. The Permittee shall color -code, tape, or otherwise mark all reclaimed water piping, valves, outlets, and
other appurtenances to identify the source of the water as reclaimed water as follows:
a. All reclaimed water piping and appurtenances shall be either colored purple (Pantone 522 or
equivalent) and embossed or integrally stamped or marked "CAUTION: RECLAIMED WATER -
DO NOT DRINK" or installed with a purple (Pantone 522 or equivalent) identification tape or
polyethylene vinyl wrap. The warning shall be on opposite sides of the pipe and repeated every
three feet or less.
b. Identification tape shall be at least three inches wide and have white or black lettering on a purple
(Pantone 522 or equivalent) field stating "CAUTION: RECLAIMED WATER - DO NOT
DRINK." The Permittee shall install identification tape on top of reclaimed water pipelines
fastened at least every 10 feet to each pipe length and run continuously the entire length of the pipe.
c. The Permittee shall tape or otherwise identify existing underground distribution systems retrofitted
for conveying reclaimed water as described in Paragraphs a. and b. above. The Permittee shall
perform this identification within 10 feet of any potable water supply line or sanitary sewer line
crossing a reclaimed water line. The Permittee does not need to perform this identification for the
entire length of the distribution system.
[ 15A NCAC 02U .0403(c)1
8. The Permittee shall secure all reclaimed water valves and outlets such that only Permittee-authorized
personnel can operate them. [15A NCAC 02U .0403(d)]
9. The Permittee shall place hose bibs in locked, below -grade vaults and label them non -potable. The
Permittee may place hose bibs above ground and label them non -potable if the hose bibs require a tool
to operate. [15A NCAC 02U .0403(e)]
10. There shall be no direct cross -connections between the reclaimed water and potable water systems
unless such connection is Department -approved pursuant to 15A NCAC 18C .0406. [15A NCAC 02U
.0403
11. For reclaimed water irrigation sites permitted on or after September 1, 2006, the Division has
established the compliance and review boundaries at the irrigation area boundary. Any exceedance of
groundwater standards at or beyond the compliance boundary shall require the Permittee to take
corrective action. The Division shall note any Division -approved relocation of the compliance
boundary in Attachment B. The Division shall consider multiple contiguous properties under common
ownership and permitted for use as a disposal system as a single property regarding the determination
of a compliance boundary. [15A NCAC 02L .0106(e), 02L .0107(c), 02L .0107(f), 02T .0105(h), 02U
.0501(a)(6)]
12. The Permittee shall notify the Division of any sale or transfer of property affecting a compliance
boundary (i.e., parcel subdivision). [15A NCAC 02L .0107(1)]
13. The Permittee or any landowner who owns land within the compliance boundary shall not construct
any water supply wells within the compliance boundary. [ 15A NCAC 02L .0107(i)]
WQ0044259 Version 1.0 Shell Version 230811 Page 3 of 10
14. Permittee shall ensure that any landowner who owns land within the compliance boundary and who is
not the Permittee executes and files with the Wilson County Register of Deeds an easement running
with the land. This easement shall contain either a notice of this permit, including the permit number,
a description of the type of permit, and the name, address, and telephone number of the permitting
agency; or a reference to a notice of this permit with book and page number of its recordation. The
landowner may request that the Director file a document terminating the easement with the Wilson
County Register of Deeds upon completion of the following:
a. The Permittee has completed all required groundwater remediation.
b. The Division determines that groundwater monitoring is no longer required pursuant to 15A NCAC
02L .0110(fl.
c. The Permittee has abandoned monitoring wells pursuant to 15A NCAC 02C .0113.
The City of Wilson has executed and recorded an easement in the Wilson County Register of Deeds
(Deed Book 2983 / Page No. 512) for the compliance boundary that extends onto Parcel No. 3720-86-
1702.000.
[ 15A NCAC 02L .0107(k)]
15. Reclaimed water distribution lines shall be at least five feet horizontally from and 18 inches below any
water line if practicable. If these separation distances cannot be met, the piping and integrity testing
procedures shall meet water main standards pursuant to 15A NCAC 18C. [ 15A NCAC 02U .0403W,
02U .0403(h)1
16. Reclaimed water distribution lines shall not be less than 50 feet from a well unless the piping and
integrity testing procedures meet water main standards pursuant to 15A NCAC 18C, but in no case
shall they be less than 25 feet from a private well. [ 15A NCAC 02U .0403(g), 02U .0403(i)]
17. Reclaimed water distribution lines shall meet the separation distances to sewer lines pursuant to 15A
NCAC 02T .0305. [15A NCAC 02U .0403(g), 02U .0403(i)]
18. The Permittee shall operate and maintain the permitted facilities pursuant to the following setbacks:
a. The Division originally permitted the reclaimed water irrigation sites on March 1, 2024, with an
application received on March 27, 2023. The setbacks for spray reclaimed water irrigation sites
originally permitted or modified with an application received on or after September 1, 2018, are as
follows (all distances in feet):
i. Surface waters classified SA: 100
ii. Surface waters not classified SA: 25
In. Each well with exception of monitoring wells: 100
[ 15A NCAC 02U .0701(c), 02U .0701(d)]
WQ0044259 Version 1.0 Shell Version 230811 Page 4 of 10
III. OPERATION AND MAINTENANCE
1. The Permittee shall operate and maintain the subject facilities as anon -discharge system. [15A NCAC
02U .0101]
2. The Permittee shall maintain an Operation and Maintenance Plan, which shall include:
a. A description of the operation of the system in sufficient detail to show what operations are
necessary for the system to function and who shall conduct the operations.
b. A description of the anticipated maintenance of the system.
c. Provisions for safety measures, including restriction of access to the site and equipment.
d. Spill control provisions that include response to upsets and bypasses, including control,
containment, and remediation; and contact information for personnel, emergency responders, and
regulatory agencies.
f 15A NCAC 02U .0801(a)]
3. Upon the Water Pollution Control System Operators Certification Commission's (WPCSOCC)
classification of the subject non -discharge facilities, the Permittee shall designate and employ a certified
Operator in Responsible Charge (ORC), and one or more certified operators as Back-up ORCs. The
ORC or its Back-up shall operate and visit the facilities as required pursuant to 15A NCAC 08G .0204
and 08G .0205.
At the time of this permit issuance, the WPCSOCC does not require an ORC and Back-up ORC for
Reclaimed Water Conjunctive Utilization Systems. [ 15A NCAC 02T .0117, 02U .0117]
4. The Permittee shall test and calibrate the spray nozzle equipment once per permit cycle. [15A NCAC
02U .0801(d)]
5. The Permittee shall only utilize reclaimed water generated from the Hominy Creek WRF (Permit No.
NC0023906) at the sites and for the activities listed in Attachment B. [ 15A NCAC 02U .01011
6. The Permittee shall control public access to reclaimed water utilization sites during active site use.
[ 15A NCAC 02U .0501(a)(2)]
7. The Permittee shall maintain a freeboard of not less than two feet in the 1,777,604 gallon heat exchange
storage lagoon. [ 15A NCAC 02U .0401(h)]
8. The Permittee shall provide a gauge to monitor freeboard levels in the 1,777,604 gallon heat exchange
storage lagoon. This gauge shall have readily visible permanent markings, at inch or tenth of foot
increments, indicating the following elevations: the maximum liquid level at the top of the temporary
liquid storage volume, the minimum liquid level at the bottom of the temporary liquid storage volume,
and the lowest point on top of the dam. [ 15A NCAC 02U .0801(fl]
9. The Permittee shall establish and maintain a protective vegetative cover on all berms, pipe runs, erosion
control areas, surface water diversions, and earthen embankments (i.e., the outside toe of the
embankment to the maximum allowable temporary storage elevation on the inside of the embankment).
The Permittee shall remove all trees, shrubs, and other woody vegetation from earthen dikes and
embankments. The Permittee shall keep all earthen embankments mowed or otherwise controlled and
accessible. [15A NCAC 02U .0801(a)]
10. The Permittee shall test and calibrate metering equipment annually. [ 15A NCAC 02U .0801(d)]
11. The Permittee shall provide notification to the public and its employees about the use of reclaimed
water and that reclaimed water is not for drinking. The Permittee shall provide notification to
employees in a language they understand. [15A NCAC 02U .0501(a)(2)]
WQ0044259 Version 1.0 Shell Version 230811 Page 5 of 10
12. The Permittee shall develop and implement an education program to inform users and its employees
about the proper use of reclaimed water. The Permittee shall provide educational material to all
residents and/or other facilities provided with reclaimed water. The Permittee shall make all
educational materials available to the Division upon request. [15A NCAC 02U .0501(a)(4)]
13. Reclaimed water used for activities other than land application shall not cause exposure to aerosols.
[ 15A NCAC 02U .0501(b)(6)1
14. The Permittee or Permittee-authorized users shall not use reclaimed water for swimming pools, hot
tubs, spas, or similar uses. [ 15A NCAC 02U .0501(c)]
IV. MONITORING AND REPORTING
1. The Permittee shall conduct and report any Division -required monitoring, including the monitoring of
groundwater, surface water or wetlands, waste, reclaimed water, residuals, soil, treatment processes,
lagoon or storage ponds, and plant tissue, if necessary to evaluate this facility's impact on groundwater
and surface water. [ 15A NCAC 02T .0108(c), 02U .01081
2. The Permittee shall maintain records tracking the amount of reclaimed water utilized and shall include
the following information:
a. Date reclaimed water utilized;
b. Volume of reclaimed water utilized to each site specified in Attachment B; and
c. Wind speed.
The Permittee shall sum the monthly water utilized and report on Form NDMR (see Attachment A)
under parameter WQO1 (Flow, Reclaimed Water Distributed). This value shall represent the total
volume of reclaimed water utilized for that month. [ 15A NCAC 02T .0108(c), 02U .0108]
3. The Permittee shall measure and record weekly to the nearest inch or tenth of a foot of freeboard (Le.,
the waste level to the lowest embankment elevation) in the 1,777,604 gallon heat exchange storage
lagoon. The Permittee shall maintain the weekly freeboard records for eight years and shall make them
available to the Division upon request. [15A NCAC 02T .0108(c), 02U .01081
4. On or before the last day of the month following the previous month's sampling, the Permittee shall
submit monitoring data (as specified in Conditions IV.2 and IV.3) on Form NDMR for each PPI. If no
activities occurred during the monitoring month, the Permittee shall still submit monitoring reports
documenting the absence of the activity. The Permittee shall submit the reports via the Non -Discharge
monitoring report portal_ [15A NCAC 02T .0105(1), 02U .0105]
The Permittee shall keep a log of all maintenance done at this facility. The Permittee shall maintain
this log for eight years and shall make it available to the Division upon request. This log shall include:
a. Date of spray nozzle equipment calibration.
b. Record of preventative maintenance (e.g., changing of equipment, adjustments, testing,
inspections, cleanings, etc.).
c. Record of all discharges of reclaimed water to surface waters or the land surface, including the date
of occurrence, estimated volume, and corrective action taken.
[ 15A NCAC 02U .080I (h)]
WQ0044259 Version 1.0 Shell Version 230811 Page 6 of 10
6. Noncompliance Notification:
The Permittee shall report to the Raleigh Regional Office, telephone number (919) 791-4200, within
24 hours of first knowledge of the following:
a. Any time self -monitoring indicates the facility has gone out of compliance with its permit
limitations.
b. Any failure resulting in a discharge of reclaimed water directly to surface waters or any release of
reclaimed water to land surface greater than or equal to 5,000 gallons. The Permittee shall
document releases less than 5,000 gallons to land surface pursuant to Condition IV.5.c. but does
not require Regional Office notification.
Emergencies requiring reporting outside normal business hours shall call the Division's Emergency
Response personnel at the telephone number (800) 858-0368. All noncompliance notifications shall
file a written report to the Raleigh Regional Office within five days of first knowledge of the
occurrence, and this report shall outline the actions proposed or taken to ensure the problem does not
recur. [15A NCAC 02T .0108(b)(1)(A), 02U .0108]
V. INSPECTIONS
1. The Permittee shall perform inspections and maintenance to ensure proper operation of the reclaimed
water conjunctive utilization facilities. [15A NCAC 02U .0801(i)]
2. The Permittee shall inspect the reclaimed water conjunctive utilization facilities to prevent
malfunctions, facility deterioration, and operator errors that may result in discharges of wastes to the
environment, threats to human health, or public nuisances. The Permittee shall maintain an inspection
log that includes the date and time of inspection, observations made, and maintenance, repairs, or
corrective actions taken. The Permittee shall maintain this inspection log for eight years from the date
of the inspection and shall make this log available to the Division upon request. [15A NCAC 02U
.0801 h , 02U .0801(i)]
Division -authorized representatives may, upon presentation of credentials, enter and inspect any
property, premises, or place related to the permitted reclaimed water conjunctive utilization facilities at
any reasonable time for determining compliance with this permit. Division -authorized representatives
may inspect or copy records maintained under the terms and conditions of this permit and may collect
influent, treatment process water, generated reclaimed water, residual, soil, plant tissue, groundwater,
or surface water samples. [G.S. 143-215.3(a)(2)]
WQ0044259 Version 1.0 Shell Version 230811 Page 7 of 10
Vl. GENERAL
1. The Permittee's failure to comply with this permit's conditions and limitations may subject the
Permittee to a Division enforcement action. [G.S. 143-215.6A, 143-215.6B, 143-215.6C]
2. This permit is effective only for the nature and volume of wastes described in the permit application
and Division -approved plans and specifications. [G.S. 143-215.1(d)1
3. There are no variances to administrative codes or general statutes governing the construction or
operation of the permitted facilities unless the Permittee specifically requested a variance in the
application and the Division approved the variance as noted in this permit's facility description. [15A
NCAC 02T .0105(b), 02U .0105]
4. This permit does not exempt the Permittee from complying with all statutes, rules, regulations, or
ordinances that other jurisdictional government agencies (e.g., local, state, and federal) may require.
[15A NCAC 02T .0108(b)(1)(A), 02U .01081
5. The Permittee shall retain this permit and the Division -approved plans and specifications for the life of
the permitted facilities. [15A NCAC 02T .0105(o), 02T .0116(d), 02U .0105, 02U .0116]
6. The Permittee shall comply with all permit conditions and requirements until the proper closure of the
permitted facilities, or until another appropriate authority permits the facilities. [15A NCAC 02T
.0105 , 02U .0105]
7. This permit is subject to revocation or modification upon 60-day notice from the Division Director in
whole or part for:
a. Violation of any terms or conditions of this permit or 15A NCAC 02U.
b. Obtaining a permit by misrepresentation or failure to disclose all relevant facts.
c. The Permittee's refusal to allow authorized Department employees upon presentation of
credentials:
I. To enter the Permittee's premises where a system is located or where the Permittee keeps any
Division -required records under the terms and conditions of this permit.
ii. To have access to any permit -required documents and records.
iii. To inspect any monitoring equipment or method as required in this permit.
iv. To sample any pollutants.
d. The Permittee's failure to pay the annual fee for administering and compliance monitoring.
e. A Division determination that the conditions of this permit conflict with the North Carolina
Administrative Code or General Statutes.
[ 15A NCAC 02T .0110, 02U .0110]
WQ0044259 Version 1.0 Shell Version 230811 Page 8 of 10
8. Unless the Division determines that the Permittee needs a permit modification for the construction of
facilities to resolve non-compliance with any environmental statute or rule, or the Division Director
grants a variance, expansion of the permitted facilities shall not occur if any of the following apply:
a. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has been convicted of
environmental crimes under G.S. 143-215.6B or under Federal law that would otherwise be
prosecuted under G.S. 143-215.6B, and the Permittee or any parent, subsidiary, or other affiliate of
the Permittee has abandoned or exhausted all appeals of this conviction.
b. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has previously abandoned
a wastewater treatment facility without properly closing the facility in accordance with its permit
or 15A NCAC 02U.
c. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid a civil
penalty, and the Permittee or any parent, subsidiary, or other affiliate of the Permittee has
abandoned or exhausted all appeals of this penalty.
d. The Permittee or any parent, subsidiary, or other affiliate of the Permittee is currently not compliant
with any compliance schedule in a permit, settlement agreement, or order.
e. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid an annual
fee pursuant to 15A NCAC 02T .0105(e)(2) via 15A NCAC 02U .0105.
[ 15A NCAC 02T .0120(b), 02T .0120(d), 02U .0120]
9. Unless the Division Director grants a variance, the Division shall not renew this permit if the Permittee
or any affiliation has not paid an annual fee pursuant to 15A NCAC 02T .0I05(e)(2). [15A NCAC 02T
.0120 c , 02T .0120(d), 02U .0105, 02U .0120]
10. The Permittee shall pay an annual fee for each year of the term of this permit pursuant to the schedule
in G.S. 143-215.31)(a). The Permittee shall continue to pay annual fees for any facility operating on
an expired permit that the Division has not rescinded or revoked. [15A NCAC 02T .0105(e)(2), 02U
.0105]
Permit issued this the 1st day of March 2024
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
DocuSigned by: �}
Wc+��a svi e� ! ho? su�cvt�
D1043082680C483...
Richard E. Rogers, Jr., Director
Division of Water Resources
By Authority of the Environmental Management Commission
Permit Number WQ0044259
WQ0044259 Version 1.0 Shell Version 230811 Page 9 of 10
Permit No. WQ0044259 Reclaimed Water Conjunctive Utilization System
Carolina Poultry Power RG2, LLC March 1, 2024
Carolina Poultry Power — Wilson CUS Wilson County
ENGINEERING CERTIFICATION
❑ Partial ❑ Final
I, , as a duly licensed North Carolina Professional
Engineer, having ❑ periodically / ❑ fully observed the construction of the permitted facilities, do hereby
state to the best of my abilities that the facility was constructed in compliance with G.S. 143-215.1,
Administrative Code Title 15A Subchapter 02U, this permit, and the Division -approved plans and
specifications.
Documentation of any variation to this permit, and the Division -approved plans and specifications, is in the
attached as -built drawings.
Description of variations:
Professional Engineer's Name
Firm Name Firm No.
Address
City StaME& Zip Code
Telephone ANELEmail Seal, Signature, and Date
THE PERMITTEE SHALL SUBMIT THE COMPLETED ENGINEERING CERTIFICATION, INCLUDING
ALL SUPPORTING DOCUMENTATION, VIA THE NON -DISCHARGE ONLINE PORTAL.
WQ0044259 Version 1.0 Shell Version 230811 Page 10 of 10
ATTACHMENT A — LIMITATIONS AND MONITORING REQUIREMENTS
Carolina Poultry Power RG2, LLC
PPI 001— Distributed Reclaimed Water for Conjunctive Utilization
Certification Date: March 1, 2024
Permit Number: WQ0044259 Version: 1.0
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING REQUIREMENTS
PCS
Parameter Description
Units of
Monthly Total
Monthly
Daily Minimum
Daily Maximum
Measurement
Sample
Code
Measure
Geometric Mean
Frequency
Type
WQ01
Flow, Reclaimed Water Distributed
gallons
Monthly
Estimate
WQ0044259 Version 1.0 Attachment A Page 1 of 1
THIS PAGE BLANK
ATTACHMENT B — APPROVED LAND APPLICATION SITES AND LIMITATIONS
Carolina Poultry Power RG2, LLC
Certification Date: March 1, 2024
Permit Number: WQ0044259 Version: 1.0
UTILIZATION AREA INFORMATION
APPLICATION LIMITATIONS
Site
Owner Parcel No.
County
Latitude
Longitude
Net
Dominant
Approved Use
Parameter
Rate
Units
Acreage
Soil Series
01
City of Wilson' 3720-86-1702.000
Wilson
35.685681'
-77.896763'
__
__
Heat Exchange
01284 — Non -Discharge Application Rate
--
GPI)
Irrigation
Make-
02
Stockport Limited Partnership' 3720-96-6201.000
Wilson
35.685652'
-77.889805'
--
up/cooling
01284 — Non -Discharge Application Rate
--
GPD
water
Total:
--
1. Stockport Limited Partnership and the City of Wilson have executed and recorded with the Wilson County Register of Deeds an Easement and Maintenance Agreement (Book 2983 Page 512).
Stockport Limited Partnership and Carolina Poultry Power RG2, LLC have executed and recorded with the Wilson County Register of Deeds a notarized Memorandum of Lease (Book 2983 Page
528).
WQ0044259 Version 1.0 Attachment B Page 1 of 1
OF WILSON WATER I
TEWATER TREATMENT PLAN
Stanlonsbur Rd S
>n. NC 2789
,
CT SITE LOCATION
t5.34"N
t l V
L
OCATION MAP
:16000
TRUE NORTH
]FISTING POND WITH NEW EVAPORATION ..
CLING SYSTEM AND SPRAY NO22LE
CONFIGLIRAn ,
i Swam
ro
_ t PUMP HOUSE �' • ^
r• t TATION
VICINITY PLAN
• 1 " = 160'-0"
TRUE NORTH
CAROLINA POULTRY POWER PLANT RG2
EVAPORATIVE COOLING POND SYSTEM
WILSON NORTH CAROLINA
h.�
OF
SS DRIV
Revision
Revision Sd)edule
SHEETINDEX
Sheet Number
Sheer Name
Orrrent Revision
1%1
PROJECT COVER
1
1962
LOCATION AND VICINITY PLANS
1
Im
SITE PLAN, TYPICAL TRENCH DETAIL AND SCHEDULES
1
1964
SITE PLAN AND SECTION
1
1965
EVAPORATION SYSTEM INTERCONNECTION
1
1966
COOLING LOOP PLUMBING PLAN, ELEVATION, ONE -LINE AND SCHEDULE
1
1967
CONDENSER LOOP P&ID AND SPECIFICATIONS
1
1968
CONSTRUCTION NOTES
1
_. .T.
r
dry
l
ol
' �S Sip Cr
�
p�"r•FCAI?
*i
SEAL' '�• f
28308¢. 4
i,
a�
i�r
�
fNC� l� r 5❑�'�ti�`
For
P5uo20171iy
CHECb op
CAROLINA POULTRY POWER RG2 TJX!PAF 00M29
EVAPORATIVE COOLING POND SYSTEM fie. e?I r?1T3 sz
LOCATION AND VICINITY PLANS � m r:
r co arc
221Z3
P00 drAC
Rev. By Aped By
Approved
0.461
102 l23 wca.b« , uwix
Dale CM R62 W =N, NC 3 B
wrrrwc*na c.*� sEc.�en r.o. wet-rca.+r u
1411A 8480 196R B 1
MEi71 A: C0T4DKNSATF
PRESSLRE: 1 Pal❑
FLOW- 81.0DOP1LfR
TEMPERATURE, 159°F
MFDIA: STEAM (LOW)
PRESS UILE:10 PSIG
FLOW: 81,00041HR
TEMPERATURE: 239 "F
FC DT VALVES WITH
b' B' S' BASKET SCREEN —
./ TLF--l.9"
MEDIA: CIRCULATING WATER FE
PRESSLtRI 115 P51G
FLOW: 1250.6PM
TEMPERATURE: 80 °F —[:x] ss
1ir
1
I
1
ti
M Ef3IA!CtRCULATING WATER
PRESSURE; 73 PSIG
FLOW: 1250. GPM
7 EMrtRATLFR C 2� Ir
HEAT I
EXCHANGER J
�tl --� E• 8- S01 20 STEEL PIPES z ��
VALVE
FLANC; ED TO HEAT EXCHANGERS
HEAT NOTE This is a standard Iie:11 exchanger designed to
E}[t:HANGF� ensure there is no mixture of the two media (pond
wv ler and stern from boiler) m!ver lnix- Simp ly put,
no wasirwater from the power plant goes hark to the
(rind.
CITY OF WILSON WATER
TREATMENT PLANT
RECLAIMED
WATER
RECLAIMED
POND WATER
MAKEUP
VALVE
L::�
`15►ryfttiilllry►rrr
s e 1
2S,oI3 �
r!1!!!l111151511�