HomeMy WebLinkAboutNC0087866_Compliance Evaluation Inspection_20240209ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director NORTH CAROLINA Environmental Quality February 09, 2024 Gregory T. Flory Piedmont Triad Regional Water Authority PO Box 1326 Randleman, NC 27317-1326 SUBJECT: COMPLIANCE EVALUATION INSPECTION Permit No. NCO087866 John F. Kime WTP Randolph County Dear Mr. Flory: On February 2, 2024, Division of Water Resources (DWR) Winston-Salem Regional Office (WSRO) staff Jesse Barnes conducted a routine compliance evaluation inspection at the John F. Kime WTP in reference to NPDES permit NC0087866. ORC Steve Pope was present during the inspection. A review of the subject permit, records, data, treatment components, sampling methods, outfall area, operations, and maintenance was completed. This review reflected compliance with the subject permit. Item(s) of concern are listed below. Inspection findings are detailed in the attached Water Compliance Inspection Report. Item(s) of Concern Meritech Inc. (NC certified lab #165) has been contracted to analyze some permit -required parameters but has not been listed in the laboratories used on discharge monitoring reports (DMRs). All labs used to analyze required parameters must be listed on that month's DMR. Plans or measures should be taken to address the indicated item(s) of concern. Please be aware that the Division may take enforcement action against any individual who fails to comply with the requirements of all applicable permits, regulations, and/or statutes. Pursuant to NC General Statute (NCGS) 143-215.6A, a civil penalty of not more than twenty-five thousand dollars ($25,000.00) may be assessed against any person who violates or fails to act in accordance with the terms, conditions, or requirements of any permit, or applicable regulations, issued pursuant to G.S. 143-215.1. If you have questions or concerns, contact Jesse Barnes by phone at 336-776-9701 or by email at iesse.barnes@deq.nc.gov. DffNorth Carolina Department of Environmental Quality I Division of Water Resources oan caaouNn Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105 M336.776.9800 oep.m.m or em�nmen� Qualm Sincerely, E�DocuSigned by: c� '..�,� OD2D3CE3F167456... Jennifer F. Graznak, Assistant Regional Supervisor Water Quality Regional Operations Section Winston-Salem Regional Office Division of Water Resources, NCDEQ Attachments: 1. Water Compliance Inspection Report, NCO087866 REQ� North Carolina Department ofEnvironmental Quality I Division ofWater Resources Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Raleigh, North Carolina 27105 NORTH CAROLINA 336.776.9800 naparMeM of EmironmanW 9uallly United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 u 3 I NC0087866 I11 121 24/02/02 I17 18I � I 19 I s I 201 I 211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 67 I 72 I ni I 71 I 74 79 I I I I I I I80 701 I 71 I LL -1 I I LJ Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES Dermit Number) 10:OOAM 24/02/02 17/10/01 John F. Kime WTP 7297 Adams Farm Rd Exit Time/Date Permit Expiration Date Randleman NC 27317 11:30AM 24/02/02 22/08/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Gregory T Flory,PO Box 1326 Randleman NC 273171326//336-498-5510/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenar Records/Reports Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Jesse Barnes Docusigned by: DWR/WSRO WQ/336-776-9701/ 2/9/2024 � 5, -Ba4~0' E 41797473D3194ED... Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date Docusigned by: 14. DWR/WSRo 336-776-9695 2/9/2024 mt-�' --'�u� 33.F1$7�15G EPA Form 3560-� �evCE`J-`J41 Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type NCO087866 I11 12I 24/02/02 117 18 i c i (Cont.) Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On February 2, 2024, Division of Water Resources (DWR) Winston-Salem Regional Office (WSRO) staff Jesse Barnes conducted a routine compliance evaluation inspection at the John F. Kime WTP in reference to NPDES permit NC0087866. ORC Steve Pope was present during the inspection. A review of the subject permit, records, data, treatment components, sampling methods, outfall area, operations, and maintenance was completed. This review reflected compliance with the subject permit. Item(s) of concern are listed below. Inspection findings are detailed in the attached Water Compliance Inspection Report. Item(s) of Concern: 1. Meritech Inc. (NC certified lab #165) has been contracted to analyze some permit -required parameters but has not been listed in the laboratories used on discharge monitoring reports (DMRs). All labs used to analyze required parameters must be listed on that month's DMR. Other observations: The current version of NPDES permit NC0087866 became effective October 1, 2017, and expired at midnight on August 31, 2022. A permit renewal application has been received by DWR and is currently in review. Compliance is evaluated based on the most recently issued permit version. The facility is as described in the subject permit and access to the plant is restricted by a gated fence. The discharge monitoring report (DMR) and corresponding laboratory data for October 2023 were reviewed and appeared to be complete with no errors found. A standby power generator is available on site for use during power failures. The generator is automatically activated, interrupts the primary power source during tests, is tested quarterly under load, and can operate the entire facility. The equalization basin high-level alarms were not tested during the inspection, but a SCADA system is in place and monitored continuously by operators. EQ basin effluent proceeds to a gravity thickener that removes additional solids from the wastewater and acts essentially as a secondary clarifier. The gravity thickener appeared to be operating properly during the inspection. Sludge removed from the gravity thickener and EQ basin is processed with an on -site belt press and stored in a drying bed area until it can be land applied by EMA. All solids handling equipment appeared to be operating properly during the inspection. Influent wastewater from the WTP contains bleach, therefore a liquid calcium thiosulfate feed system is used to achieve de -chlorination. Additionally, pH is adjusted with a liquid sodium hydroxide (caustic) feed system. Both de -chlorination and caustic feed systems appeared to be operating properly during the inspection. Mr. Pope verbally confirmed that the effluent flow meter is calibrated annually and was last calibrated in October 2023. Records of flow meter calibration were not requested during the inspection due to time constraints. The effluent pipe, outfall area, and receiving waters were observed during the inspection and appeared to be operating properly with a trace amount of foam present at the outfall area. An installed composite sampler is used for grab sample collection and sampling methods appeared to be compliant with the subject permit. The upstream hardness sampling location and methods were verbally verified by Mr. Pope and appeared to be compliant with the subject permit. Page# Permit: NCO087866 Owner - Facility: John F. Kime WTP Inspection Date: 02/02/2024 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ■ ❑ ❑ ❑ application? Is the facility as described in the permit? ■ ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ■ ❑ ❑ Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? ■ ❑ ❑ ❑ Comment: Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ■ ❑ ❑ ❑ Is all required information readily available, complete and current? ■ ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ■ ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ■ ❑ ❑ ❑ Is the chain -of -custody complete? ■ ❑ ❑ ❑ Dates, times and location of sampling ■ Name of individual performing the sampling ■ Results of analysis and calibration ■ Dates of analysis ■ Name of person performing analyses ■ Transported COCs ■ Are DMRs complete: do they include all permit parameters? ■ ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ■ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ ❑ ■ ❑ operator on each shift? Is the ORC visitation log available and current? ■ ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ■ ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility ■ ❑ ❑ ❑ classification? Is a copy of the current NPDES permit available on site? ■ ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ■ ❑ Comment: Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? ■ ❑ ❑ ❑ Page# 3 Permit: NCO087866 Owner - Facility: John F. Kime WTP Inspection Date: 02/02/2024 Inspection Type: Compliance Evaluation Laboratory Yes No NA NE Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ ❑ degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ❑ Comment: Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Standby Power Yes No NA NE Is automatically activated standby power available? 0 ❑ ❑ ❑ Is the generator tested by interrupting primary power source? 0 ❑ ❑ ❑ Is the generator tested under load? 0 ❑ ❑ ❑ Was generator tested & operational during the inspection? ❑ ❑ ❑ Do the generator(s) have adequate capacity to operate the entire wastewater site? 0 ❑ ❑ ❑ Is there an emergency agreement with a fuel vendor for extended run on back-up ❑ ❑ ❑ ■ power? Is the generator fuel level monitored? 0 ❑ ❑ ❑ Comment: Equalization Basins Yes No NA NE Is the basin aerated? ❑ ❑ 0 ❑ Is the basin free of bypass lines or structures to the natural environment? 0 ❑ ❑ ❑ Is the basin free of excessive grease? 0 ❑ ❑ ❑ Are all pumps present? ❑ ❑ ❑ Are all pumps operable? ❑ ❑ ❑ Are float controls operable? ❑ ❑ 0 ❑ Are audible and visual alarms operable? ❑ ❑ ❑ # Is basin size/volume adequate? 0 ❑ ❑ ❑ Page# 4 Permit: NC0087866 Owner - Facility: John F. Kime WTP Inspection Date: 02/02/2024 Inspection Type: Compliance Evaluation Equalization Basins Yes No NA NE Comment: De -chlorination Yes No NA NE Type of system ? Liquid Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ❑ Is storage appropriate for cylinders? ❑ ❑ 0 ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Comment: Are the tablets the proper size and type? ❑ ❑ ■ ❑ Are tablet de -chlorinators operational? ❑ ❑ ■ ❑ Number of tubes in use? Comment: Chemical Feed Yes No NA NE Is containment adequate? 0 ❑ ❑ ❑ Is storage adequate? 0 ❑ ❑ ❑ Are backup pumps available? 0 ❑ ❑ ❑ Is the site free of excessive leaking? ■ ❑ ❑ ❑ Comment: Solids Handling Equipment Yes No NA NE Is the equipment operational? ■ ❑ ❑ ❑ Is the chemical feed equipment operational? 0 ❑ ❑ ❑ Is storage adequate? 0 ❑ ❑ ❑ Is the site free of high level of solids in filtrate from filter presses or vacuum filters? 0 ❑ ❑ ❑ Is the site free of sludge buildup on belts and/or rollers of filter press? ■ ❑ ❑ ❑ Is the site free of excessive moisture in belt filter press sludge cake? 0 ❑ ❑ ❑ The facility has an approved sludge management plan? ❑ ❑ ❑ Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0 ❑ ❑ ❑ Page# 5 Permit: NCO087866 Owner - Facility: Inspection Date: 02/02/2024 Inspection Type: John F. Kime WTP Compliance Evaluation Flow Measurement - Effluent Yes No NA NE Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ ❑ Comment: Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? ❑ ❑ ❑ ■ Is the tubing clean? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ ❑ degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, 0 ❑ ❑ ❑ and sampling location)? Comment: Page# 6