HomeMy WebLinkAboutNC0083925_Compliance Evaluation Inspection_20240209ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Shannon V. Becker
Aqua North Carolina Inc
202 Mackenan Dr
Cary, NC 27511
NORTH CAROLINA
Environmental Quality
February 09, 2024
SUBJECT: COMPLIANCE EVALUATION INSPECTION AND NOTICE OF VIOLATION
Tracking Number: NOV-2024-PC-0104
Permit No. NCO083925
Salem Glen Subdivision WWTP
Davidson County
Dear Mr. Becker:
On January 31, 2024, Division of Water Resources (DWR) Winston-Salem Regional Office (WSRO)
staff Jesse Barnes conducted a routine compliance evaluation inspection at the Salem Glen
Subdivision WWTP in reference to NPDES permit NC0083925. ORC Samuel Pegram was present
during the inspection. A review of the subject permit, records, data, laboratory, treatment
components, sampling methods, operations, and maintenance was completed. This review
reflected noncompliance with the subject permit. The determined permit violations and items of
concern are listed below. Inspection findings are detailed in the attached Water Compliance
Inspection Report.
Permit Violations
1. The effluent composite sampler is programmed to collect 100 mL aliquots per pulse and
the frequency of pulses is unknown. Mr. Pegram was asked to provide additional
information to confirm flow proportionality of composite sampling, but no additional
information has been received. Part II, Section A. of the subject permit requires composite
samples to be representative of the wastewater discharge and collected in a manner that
is proportional to the rate of flow. Part II, Section B. (8.) of the subject permit requires the
permittee to furnish any information requested by DWR within a reasonable time in order
to determine permit compliance.
2. The following operations and maintenance violations were noted:
a. Foam was observed covering approximately 60% of the aeration basin's surface.
b. Excessive solids were observed as buildup on the walls and weirs of the secondary
clarifier, as well as excessive floating sludge.
c. Excessive floating solids were observed at the point where the effluent flow meter's
ultrasonic sensor measures the water level. Floating solids at that location may
affect the accuracy of flow measurement.
Part II, Section C. (2.) of the subject permit requires the permittee to properly operate and
maintain all facilities and systems of treatment and control.
D North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
Moan caaouNn 336.776.9800
oep.m.m or em�nmen� Qualm
Items of Concern
1. 1 No records of testing of the standby power generator were available during the inspection.
2. The blower for the equalization tank aerators was not operational during the inspection.
Mr. Pe ram stated that a part is on the way and the blower will be repaired when it arrives.
3. A liquid sodium hydroxide (caustic) feed system was in use during the inspection for pH
control via injection into the equalization tank. A caustic feed system is not listed in the
facility components on the supplement to permit cover sheet. Please submit a permit
modification request to Charles Weaver at charles.weaver@deq.nc.gov to add the sodium
hydroxide feed system to the subject permit.
Plans or measures should be taken to address the indicated violation(s) and/or item(s) of concern,
if applicable. Please be aware that the Division may take enforcement action against any individual
who fails to comply with the requirements of all applicable permits, regulations, and/or statutes.
Pursuant to NC General Statute (NCGS) 143-215.6A, a civil penalty of not more than twenty-five
thousand dollars ($25,000.00) may be assessed against any person who violates or fails to act in
accordance with the terms, conditions, or requirements of any permit, or applicable regulations,
issued pursuant to G.S. 143-215.1.
If you have questions or concerns, contact Jesse Barnes by phone at 336-776-9701 or by email
at jesse.barnes@deq.nc.gov.
Sincerely,
DocuSigned by:
OD2D3CE3F1 B7456...
Jennifer F. Graznak, Assistant Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Attachments:
1. Water Compliance Inspection Report, NCO083925
REQ� North Carolina Department ofEnvironmental Quality I Division ofWater Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Raleigh, North Carolina 27105
NORTH CAROLINA 336.776.9800
naparMeM of EmironmanW 9uallly
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0083925 I11 121 24/01/31 I17 18I � I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I ni I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
01:OOPM 24/01/31
19/01/01
Salem Glen Subdivision WWTP
5180 Dock Davis Rd
Exit Time/Date
Permit Expiration Date
Clemmons NC 27012
02:30PM 24/01/31
23/12/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Samuel E. Pegram/ORC/704-489-9404/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Lauren A Raup-Plummer,202 Mackenan Ct Cary NC
27511/P.E./919-653-6977/9194601788 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Jesse Barnes Docusigned by: DWR/WSRO WQ/336-776-9701/
2/9/2024
� 5, -Ba4~0'
E
41797473D3194ED...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Docusigned by:
DwR/wslto 336-776-9695 2/9/2024
Fj
'--OD2D3CE3F1B7456.-
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO083925 I11 12I 24/01 /31 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On January 31, 2024, Division of Water Resources (DWR) Winston-Salem Regional Office (WSRO)
staff Jesse Barnes conducted a routine compliance evaluation inspection at the Salem Glen
Subdivision WWTP in reference to NPDES permit NC0083925. ORC Samuel Pegram was present
during the inspection. A review of the subject permit, records, data, laboratory, treatment
components, sampling methods, operations, and maintenance was completed. This review reflected
noncompliance with the subject permit. The determined permit violations and items of concern are
listed below. Inspection findings are detailed in the attached Water Compliance Inspection Report.
Permit Violations:
1. The effluent composite sampler is programmed to collect 100 mL aliquots per pulse and the
frequency of pulses is unknown. Mr. Pegram was asked to provide additional information to confirm
flow proportionality of composite sampling, but no additional information has been received. Part II,
Section A. of the subject permit requires composite samples to be representative of the wastewater
discharge and collected in a manner that is proportional to the rate of flow. Part ll, Section B. (8.) of
the subject permit requires the permittee to furnish any information requested by DWR within a
reasonable time in order to determine permit compliance.
2. The following operations and maintenance violations were noted:
a. Foam was observed covering approximately 60% of the aeration basin's surface.
b. Excessive solids were observed as buildup on the walls and weirs of the secondary clarifier, as
well as excessive floating sludge.
c. Excessive floating solids were observed at the point where the effluent flow meter's ultrasonic
sensor measures the water level. Floating solids at that location may affect the accuracy of flow
measurement.
Part II, Section C. (2.) of the subject permit requires the permittee to properly operate and maintain all
facilities and systems of treatment and control.
Items of Concern:
1. No records of testing of the standby power generator were available during the inspection.
2. The blower for the equalization tank aerators was not operational during the inspection. Mr.
Pegram stated that a part is on the way and the blower will be repaired when it arrives.
3. A liquid sodium hydroxide (caustic) feed system was in use during the inspection for pH control via
injection into the equalization tank. A caustic feed system is not listed in the facility components on
the supplement to permit cover sheet. Please submit a permit modification request to Charles Weaver
at charles.weaver@deq.nc.gov to add the sodium hydroxide feed system to the subject permit.
Other observations:
The current version of NPDES permit NC0083925 became effective January 1, 2019, and expired at
midnight on December 31, 2023. DWR has received the permittee's renewal application, and a
renewed permit version is in draft. The most recently issued permit version is used in evaluating
compliance until a new version is issued.
The data monitoring report (DMR) and associated laboratory data for September 2023 were reviewed
during the inspection and appeared to be complete with no errors found. Calibration records for the
field pH meter and field thermometers were reviewed and appeared to be complete.
A propane -fueled standby power generator is on site for use during power failures. The generator is
automatically activated, interrupts the primary power source during tests, is tested under load, can
power the entire facility, and was tested and appeared to be operational during the inspection.
The high-level float control for the equalization tank was pulled for a test and successfully triggered
Page#
Permit: NCO083925
Inspection Date: 01/31/2024
Owner -Facility: Salem Glen Subdivision WWTP
Inspection Type: Compliance Evaluation
the high-level alarm during the inspection. The audible, visual, and telemetric alarms appeared to be
operating properly during the inspection.
The six -bulb UV disinfection system appeared to be operating properly during the inspection, with a
backup tablet tube chlorination and de -chlorination system also in place. Three backup UV bulbs and
quartz sleeves were on site during the inspection and Mr. Pegram also has access to more backup
disinfection supplies at the Aqua NC offices.
A Teledyne ISCO effluent flow meter was in use and appeared to be operating properly during the
inspection. The flow meter is calibrated annually, and records reviewed during the inspection
indicated it was last calibrated on January 23, 2024.
An ISCO 5800 composite sampler was in use and appeared to be operating properly during the
inspection. The composite sample storage temperature was observed to be 1 ° C. Mr. Pegram stated
that the composite sampler has been programmed to collect 100 mL aliquots per pulse and the timing
of pulses is unknown.
The outfall area was not observed during the inspection due to muddy conditions, safety concerns,
and time constraints.
Page#
Permit: NCO083925 Owner -Facility: Salem Glen Subdivision WWTP
Inspection Date: 01/31/2024 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
■
❑
❑
❑
application?
Is the facility as described in the permit?
❑
■
❑
❑
# Are there any special conditions for the permit?
❑
■
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: A liquid sodium hydroxide (caustic) feed system was in use during the inspection
for pH
control via injection into the equalization tank. A caustic feed system is not listed in the
facility components on the supplement to permit cover sheet.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Is a copy of the current NPDES permit available on site?
■
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
■
❑
Comment:
Page# 4
Permit: NCO083925 Owner -Facility: Salem Glen Subdivision WWTP
Inspection Date: 01/31/2024 Inspection Type: Compliance Evaluation
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
■
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
❑
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Standby Power
Yes
No
NA
NE
Is automatically activated standby power available?
0
❑
❑
❑
Is the generator tested by interrupting primary power source?
■
❑
❑
❑
Is the generator tested under load?
0
❑
❑
❑
Was generator tested & operational during the inspection?
0
❑
❑
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
0
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up
❑
❑
❑
■
power?
Is the generator fuel level monitored?
0
❑
❑
❑
Comment:
Bar Screens
Yes
No
NA
NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Page# 5
Permit: NCO083925
Inspection Date: 01/31/2024
Bar Screens
Comment:
Owner -Facility: Salem Glen Subdivision WWTP
Inspection Type: Compliance Evaluation
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Comment: The blower for the equalization tank aerators was not operational durinq the
Yes No NA NE
Yes
No
NA
NE
❑
■
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
❑
❑
❑
inspection. Mr. Pe -gram stated that a part is on the way and the blower will be repaired
when it arrives.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
■
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
❑
■
❑
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
■
Comment: Foam was observed coverinq approximately 60% of the aeration basin's surface.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ■ ❑ ❑
❑ ■ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Page# 6
Permit: NC0083925
Inspection Date: 01/31/2024
Owner -Facility: Salem Glen Subdivision WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier
Yes
No
NA
NE
Is the site free of excessive floating sludge?
❑
0
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
■
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
❑
0
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4
of the sidewall depth) ❑
❑
❑
Comment: Excessive solids were observed as buildup on the walls and weirs of the secondar
clarifier, as well as excessive floating sludge.
Pumps-RAS-WAS
Yes
No
NA
NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
❑
❑
❑
■
Are there adequate spare parts and supplies on site?
❑
❑
❑
Comment:
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Comment:
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑ ■
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Page# 7
Permit: NCO083925 Owner -Facility:
Inspection Date: 01/31/2024 Inspection Type:
Salem Glen Subdivision WWTP
Compliance Evaluation
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment:
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
❑
0
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
0
❑
❑
❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
❑
❑
❑
representative)?
Comment: The effluent composite sampler is programmed to collect 100 mL aliquots
per pulse
and the frequency of pulses is unknown. Mr. Pegram was asked to provide additional
information to confirm flow proportionality of composite sampling, but no additional
information has been received.
Page# 8