HomeMy WebLinkAboutWQ0014306_NOV-2024-LV-0097_20240130DocuSlgn Envelope ID: B9CE11DO-98F14AC5-81CA-8DA823BDF06C
J
ROY COOPER
-
EUZABE H S. BISFR '4�o.r. ' ' . ....
iYaeresy-
UNA
RICHARD E ROGERS. �R . NORTH GtRQ Ua
Fnvironntanmf Qcoft
D"or .
Certified Mail # 7022 1670 0000 9974 8976
Return Recelut Reauested
January 30, 2024
Raymond L Gottlieb, Manager
Sandler Utilities at Mill Run L L C
448 Viking Dr Ste 200
Virginia Beads, VA 23452-7331
SUBJECT: NOTICE OF VIOLATION & INTENT TO ASSESS CIVIL PENALTY
Tracking Number: NOV-2024-LV-0097
Permit No. WQG014306
Eagle Creek WWTP
Curritudk County
Dear Mr. Gottlieb:
A review of the August 2023 Non -Discharge Monitoring
Report (NDMR) for the subject facility revealed the
violation(s) indicated below:
Limit Ex ante Violation(s):
Sample
Limit
Reported
.
Location Parameter
Date
Value
Value
Type of Violation -
001 Turbidity, HCH Turbldimtter
8/4/2023
10
49
Daily Maximum Exceeded
(00076)
001 Turbidity, HCH Turbldlmlber
8/5/2023
10
123
Daily Maximum Exceeded
(00076)
001 Turbidity, HCH Turbldlmlter
8/9/2023
10
11.2
Daily Maximum Exceeded
(00076)
001 Turbidity, HCH Turbidimiter
8/11/2023
10
10.4
Dally Maximum Exceeded
(00076)
001 Turbidity, HCH Turbldlmiter
8/12/2023
10
11.3
Dally Maximum Exceeded
(00076)
001 Turbidity, HCH Turbidlmlter
8/16/2023
10
22
Dally Maximum Exceeded
(00076)
77a.M1 c..►.. Dq.�mn� ar..ta. iw w" air f D%+d INV—rt.�.�,:
wk ft'gt_0.'A0fkr 1 wW-bh;_Sq—"f* +a*o.�nSrEet
DocuSign Envelope ID: B9CE11Do-98F1-4AC5-81CA-81DA823131DF06C
Sample
_ Limit
Reported
Location
Parameter
Date
Value
Value
Type of Violation
001
Turbidity, HCH Turbldimlter
8/17/2023
10
48
Daily Maximum Exceeded
(00076)
001
Turbidity, HCH Turbldlmlter
8/19/2023
10
13.4
Dally Maximum Exceeded
(00076)
001
Turbidity, HCH Turbidlmiter
8/20/2023
10
16.2
Daily Maximum Exceeded
(00076)
001
Turbidity, HCH Turbldimlter
8/21/2023
10
49
Daily Maximum Exceeded
(00076)
001
Turbidity, HCH Turbidlmiter
8/22/2023
10
32
Dally Maximum Exceeded
(00076)
001
Turbidity, HCH Turbldlmlter
8/23/2023
10
18
Dally Maximum Exceeded
(00076)
001
Turbidity, HCH Turbidlmiter
8/24/2023
10
38
Dally Maximum Exceeded
(00076)
001
Turbidity, HCH Turbldimlter
8/25/2023
10
11.6
Dally Maximum Exceeded
(00076)
001
Turbidity, HCH Turbldimlter
8/27/2023
10
11.4
Dally Maximum Exceeded
(00076)
001
Turbidity, HCH Turbldlmlter
8/28/2023
10
13.8
Dally Maximum Exceeded
(00076)
001
Turbidity, HCH Turbldlmlter
8/29/2023
10
25.7
Dally Maximum Exceeded
(00076)
001
Turbidity, HCH Turbldlmiter
8/30/2023
10
53.4
Dally Maximum Exceeded
(00076)
001
BOD, 5-Day (20 Deg. C)
8/31/2023
10
10.5
Monthly Average Exceeded
(00310)
001
Turbidity, HCH Turbldlmiter
8/31/2023
10
17.5
Dally Maximum Exceeded
(00076)
002
Nitrogen, Ammonia Total (as
8/31/2023
4
4.6
Monthly Average Exceeded
N)(00610)
A Notice of Violation/Intent to Issue Civil Penalty is being issued for the noted violation of North Carolina General',
Statute (G.S.) 143-215.1 and the facility's Non -discharge Permit. Pursuant to G.S. 143-215.6A, a civil penalty of
not more than twenty-five thousand dollars ($25,000.00) may be assessed against any person who violates or
falls to act in acoordance with the terms, conditions, or requirements of any permit issued pursuant to G.S.
143-215.1.
D'"Mw't do.,k_. Aoo+e IWw« aw—A..w.
WxFr}mk*-d OlOx II Na+C+.�u216N
i
DocuSign Envelope ID: B9CE11Do-98F1-4AC5-81CA-8DA823BDF08C
If you wish to provide additional information regarding the noted violation, request technical assistance, or
discuss overall compliance please respond in writing within ten (10) business days after receipt of this Notice. A
review of your response will be considered along with any information provided on the submitted Monitoring
Report(s). You will then be notified of any civil penalties that may be assessed regarding the violations. If no
response Is received In this Office within the 10-day period, a civil penalty assessment may be
prepared.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law. If the violations are of a continuing nature, not _related to operation and/or maintenance problems,
and you anticipate remedial construction activities, then you may wish to consider applying for a Special Order by
Consent.
Reminder: Pursuant to Permit Condition 11 In Section 4, the Permittee is required to verbally notify the Regional
Office as soon as possible, not to exceed 24 hours, from first knowledge of any non-compliance at
the facility including limit violations, bypasses of, or failure of a treatment unit. A written report may
be required within 5 days if directed by Division staff. Prior notice should be given for anticipated or
potential problems due to planned maintenance activities, taking units off-line, etc.
If you have any questions concerning this matter or to apply for an SOC, please contact Robert Tankard (252)
948-3921 or Victoria Herdt (252) 948-3844 of the Washington Regional Office.
Cc: Laserfiche
Sincerely,
ETAIF."
4EEAF.F7_
Robert Tankard, Assistant Regional Supervisor