HomeMy WebLinkAboutNC0023981_Compliance Evaluation Inspection_20220208DocuSign Envelope ID: 9597C6C5-1850-4E3D-B3FA-1339ADD9989B
ROY COOPER
Governor
ELIZABETH S. BISER �. • , ,I
Secretary
S. DANIEL SMITH NORTH CAROUNA
Director Environmental Qualify
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
February 9, 2022
Elisa R. Triplett, Wastewater Superintendent
City of Lenoir Lower Creek WWTP
E-mail: I rtriplett@CI. LENOIR. NC. US
SUBJECT: Compliance Inspection Report
Lower Creek WWTP
NPDES WW Permit No. NCO023981
Caldwell County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Lower Creek WWTP on
2/08/2022. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0023981. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact me with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
tim.heim@ncdenr.gov.
Sincerely,
E DocuSigned
by:
Tim ffe"A"V , Environmental Engineer
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Ec: LF, Radford Thomas — City of Lenoir
y,"Mm'xFn.I'D ��� Norlh Carolina oepar[merrtaf Environmental Qualrcy l owus ,rw—Rew—,
Asheville Regional Office 1209005, Highway 7C 15wannan- Noah Carolha 2877E
828.296 Me
DocuSign Envelope ID: 9597C6C5-1850-4E3D-B3FA-1339ADD9989B
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO023981 111 121 22/02/08 I17 18 LC] I 19 I s I 201
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:30AM 22/02/08
21/08/01
Lower Creek WWTP
1905 Broadland Rd
Exit Time/Date
Permit Expiration Date
Lenoir NC 28645
12:OOPM 22/02/08
26/02/28
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Donnie Robert Hawkins/ORC/828-757-2198/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Elisa Robbins Triplett,PO Box 958 Lenoir NC 286450958H828-757-4462/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Other
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
2/9/2022
Timothy H Heim -rim A9 Rum DWR/ARO WQ/828-296-4665/
Mikal Willmer 0828"°s"" 'a DWR/Division of Water Qua lity/828-296-4686/
e by
CM wwu 2/9/2022
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
-- ; 2/9/2022
C
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 9597C6C5-1850-4E3D-B3FA-1339ADD9989B
NPDES yr/mo/day Inspection Type (Cont.)
NCO023981 I11 12I 22/02/08 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim and Mikal Willmer of the Asheville Regional Office performed a Compliance Inspection of the
Facility on February 8, 2022. Lisa Triplett and Donnie Hawkins (City of Lenoir) were present and
assisted with the inspection. The facility appeared well maintained and operated at the time of the
inspection, and in compliance with Permit NC0023981.
A significant number of upgrades and improvement have been made to the facility since the last
inspection, including:
Installation of new influent and effluent flow proportional samplers.
Conversion to the use of liquid hypochlorite for disinfection.
Installation of a new sludge storage tank with submersible mixers.
Repair of diffusers in the north aeration basin (full replacement is planned in the future).
Installation of new mixers in the anoxic zone of the aeration basin.
Installation of a new SCADA system.
Installation of a new solids handling process, including a gas powered sludge drying system
(Currently in commissioning phase)
The following additional items were noted at the time of the inspection:
During high influent flow events, some solids and debris overtop the gate valve and enter the plant
via the mechanical bar screen influent channel. Consider installation of a second mechanical bar
screen in this influent channel.
The facility does not have a permanent backup to the single sludge return pump. Consider installing
a second sludge return pump.
Page#
DocuSign Envelope ID: 9597C6C5-1850-4E3D-B3FA-1339ADD9989B
Permit: NCO023981 Owner -Facility: Lower Creek WWTP
Inspection Date: 02/08/2022 Inspection Type: Compliance Evaluation
Other
Yes No NA NE
Comment: The facility appeared well maintained and operated at the time of the inspection, and in
compliance with Permit NC0023981.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
■
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Compliance schedule for metals.
Pump Station - Influent
Yes
No
NA
NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
■
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
M
❑
❑
❑
Comment:
Grit Removal Yes No NA NE
Type of grit removal
a.Manual ❑
b.Mechanical
Is the grit free of excessive organic matter? 0 ❑ ❑ ❑
Is the grit free of excessive odor? 0 ❑ ❑ ❑
Page# 3
DocuSign Envelope ID: 9597C6C5-1850-4E3D-B3FA-1339ADD9989B
Permit: NCO023981 Owner -Facility: Lower Creek WWTP
Inspection Date: 02/08/2022 Inspection Type: Compliance Evaluation
Grit Removal Yes No NA NE
# Is disposal of grit in compliance? 0 ❑ ❑ ❑
Comment:
Aeration Basins
Yes
No
NA
NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
■
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
Comment:
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
■
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
■
❑
❑
❑
Is the site free of excessive floating sludge?
■
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
0
❑
❑
❑
Comment:
Influent Sampling
Yes
No
NA NE
# Is composite sampling flow proportional?
■
❑
❑ ❑
Is sample collected above side streams?
❑
❑
■ ❑
Is proper volume collected?
0
❑
❑ ❑
Page# 4
DocuSign Envelope ID: 9597C6C5-1850-4E3D-B3FA-1339ADD9989B
Permit: NCO023981 Owner -Facility: Lower Creek WWTP
Inspection Date: 02/08/2022 Inspection Type: Compliance Evaluation
Influent Sampling
Yes
No
NA
NE
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment:
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment:
Disinfection -Liquid
Yes
No
NA NE
Is there adequate reserve supply of disinfectant?
0
❑
❑
❑
(Sodium Hypochlorite) Is pump feed system operational?
0
❑
❑
❑
Is bulk storage tank containment area adequate? (free of leaks/open drains)
0
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Comment:
Page# 5