HomeMy WebLinkAboutWQCS00027_NOV-2023-DV-0426_20240112pKe k P.O. Box 308
1000 Jackson Street
�o Roanoke Rapids, NC 27870
Roanoke Rapids Sanitary District (252)537-9137
Fax: (252)537-3064
1,T9RY U�w .rrsd.ore
January 8, 2024
CERTIFIED MAIL: 7005 3110 0001 6339 2784
RETURNED RECEIPT REQUESTED
Vanessa E. Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section f ,P{ f'
Raleigh Regional OfficeCY
1628 Mail Service Center
•'rca
Raleigh, NC 2769 1628
Notice of Violation - Tracking Number:
Re: Collection System Permit Number: WQ SO 027 23-DV-0426"''%Ur�of��
Roanoke Rapids Sanitary District (RRSD)
Halifax County �,Pu
Dear Ms. Manuel,
Please be advised that ongoing remedial action is being taken to correct the deficiencies in the
collection system contributing to the sanitary sewer overflow in the referenced NOV received
January 2, 2024.
On November 13, 2023, during a normally programmed exercise of the generator at the
Greenbriar Pump Station the battery backup failed. When the pump station attempted to transfer
back to utility power after exercising the generator under load, the battery backup failed to
maintain the programmable logic controller (PLC) until it could restart on utility power. This
resulted in pump station failure and a complete loss of communications with the monitoring
system. A technician was dispatched and discovered the battery backup failure. Corrective action
was taken to restart the pump station. We currently perform quarterly and annual preventative
maintenance on all our pump station backup generators. We will now include annual
replacement of all batteries regardless of their condition to prevent a recurring circumstance.
We trust our actions are deemed adequate and prudent. Roanoke Rapids Sanitary District greatly
appreciates your time and consideration in this matter. Should you require additional
information, please do not hesitate to contact us.
Sincerely,
Z
Thomas C. Wrenn
Chief Executive Officer
cc: James E. Ken, II, Chairman
David W. Scott, ORC
File