HomeMy WebLinkAboutWQ0005233_Compliance Evaluation Inspection_20240124DocuSign Envelope ID: OD0212D4-6715-4E14-B33C-15CF62E7291A
ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Richard Weaver
US MCAS Cherry Point
4223 Access Rd
Psc Box 8006
Cherry Point, NC 28533-0006
NORTH CAROLINA
Environmental Quality
January 24, 2024
SUBJECT: Compliance Inspection Report
Enlisted Men's Barracks - Atlantic Airfield WWTF
Non -discharge Permit No. WQ0005233
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Enlisted Men's Barracks
- Atlantic Airfield WWTF on 1/23/2024. This inspection was conducted to verify that the facility is
operating in compliance with the conditions and limitations specified in Non -discharge Permit No.
WQ0005233. The findings and comments noted during this inspection are provided in the enclosed
copy of the inspection report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Geoff Kegley with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
geoff.kegley@deq.nc.gov.
ATTACHMENTS
Cc: DWR Laserfiche files
Sincerely,
DocuSigned by:
E
°"".mn5�o^ for
CMIC8ECUCD446_.
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
D North Carolina Department of Environmental quality I Division of Water Resources
,./ Wiimington Regional office 1127 Cardinal Drive Extension I Wilmington. North Carolina 26405
910.796,7215
DocuSign Envelope ID: OD0212D4-6715-4E14-B33C-15CF62E7291A
Compliance Inspection Report
Permit: WQ0005233 Effective: 02/04/20 Expiration: 06/30/24 Owner: US MCAS Cherry Point
SOC: Effective: Expiration: Facility: Enlisted Men's Barracks -Atlantic Airfield WWT
County: Carteret Air Base Rd
Region: Wilmington
Atlantic NC 28511
Contact Person: Timothy Lawrence Title:
Directions to Facility:
Off Highway 70 in Atlantic in northeastern Carteret County
System Classifications: SI,
Primary ORC: Jeffrey A Clayton
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 01/23/2024 Entry Time 11:45AM
Primary Inspector: Geoff Kegley ocuSigned by:
Secondary Inspector(s):
E�D
017E2515MB417...
Certification: 998515
Phone: 252-466-4598
Phone: 252-466-6787
Exit Time: 01:OOPM
Phone:
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Miscellaneous Questions Record Keeping Treatment Lagoons
End Use -Irrigation Treatment Disinfection Standby Power
Wells
(See attachment summary)
Page 1 of 6
DocuSign Envelope ID: OD0212D4-6715-4E14-B33C-15CF62E7291A
Permit: WQ0005233 Owner - Facility: US MCAS Cherry Point
Inspection Date: 01/23/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Enlisted Men's Barracks -Atlantic Airfield WWTF was conducted on January 23, 2024.
The purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations
specified in Non -Discharge Permit WQ0005233. Rich Weaver and Jeff Clayton were present during the inspection.
This 5, 000 gallon per day (GPD) wastewater treatment and irrigation facility treats domestic wastewater and consists of:
• Pump station consisting of a new wet well and dual 80 GPM submersible grinder pumps, with a 100 kilowatt generator
• 247,000 gallon synthetically lined primary stabilization lagoon
• 78,000 gallon synthetically lined polishing and storage pond
• tablet chlorinator
• dual irrigation pumps with flow measuring and recording equipment
• emergency pump connection
• 1.75 acre spray irrigation area consisting of three fields:
o Field 1: 0.5 acres
o Field 2: 0.5 acres
o Field 3: 0.75 acres
The facility is compliant with the Non -Discharge Permit WQ0005233. Please review the comment sections of the inspection
report for more details.
Page 2 of 6
DocuSign Envelope ID: OD0212D4-6715-4E14-B33C-15CF62E7291A
Permit: WQ0005233 Owner - Facility: US WAS Cherry Point
Inspection Date: 01/23/2024 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Infiltration System
❑
Reuse (Quality)
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Single Family Drip
❑
Recycle/Reuse
❑
Lagoon Spray, LR
Standby Power Yes No NA NE
Is automatically activated standby power available? ❑ ❑ ❑
Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑
Is generator operable? ❑ ❑ ❑
Does generator have adequate fuel? ❑ ❑ ❑
Comment: The generator is on a routine maintenance schedule, log maintained onsite. The audible
alarm for high water in the pump station was not working at the time of inspection, but the light
was operable. A work order has been placed for replacement/repair.
Treatment Disinfection
Yes No NA NE
Is the system working?
0
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑ ❑ ❑
Is there adequate detention time (>=30 minutes)?
❑ ❑ ❑
Is the system properly maintained?
❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑ ❑ ❑
Is the chlorinator accessible?
❑ ❑ ❑
If tablets, are tablets present?
❑ ❑ ❑
Are the tablets the proper size and type?
❑ ❑ ❑
Is contact chamber free of sludge, solids, and growth?
❑ ❑ ❑
If UV, are extra UV bulbs available?
❑
❑ ❑
If UV, is the UV intensity adequate?
❑
❑ ❑
# Is it a dual feed system?
❑ ❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1000-
Page 3 of 6
DocuSign Envelope ID: OD0212D4-6715-4E14-B33C-15CF62E7291A
Permit: WQ0005233 Owner - Facility: US MCAS Cherry Point
Inspection Date: 01/23/2024 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
If yes, then when was the RMP last updated?
Comment: There was one Effluent exceedance for fecal in November 2023,
otherwise compliant since
last inspection.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑ ❑ ❑
NDAR?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑ ❑ ❑
Is effluent sampled for same parameters as GW?
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑ ❑ ❑
Are annual soil reports available?
❑ ❑ ❑
# Are PAN records required?
❑0
❑ ❑
# Did last soil report indicate a need for lime?
❑0
❑ ❑
If so, has it been applied?
❑
❑ 0❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
❑ ❑ ❑
Do lab sheets support data reported on GW-59s?
❑ ❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Were Operational and Maintenance records complete?
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑ ❑ ❑
Is a copy of the SOC readily available?
❑
❑ ❑
No treatment units bypassed since last inspection?
❑
0 ❑ ❑
Comment: One anomalous groundwater exceedance for TDS in MW-3 in November 2023, otherwise
compliant since last inspection.
End Use -Irrigation
Yes No NA NE
Are buffers adequate?
❑ ❑ ❑
Is the cover crop type specified in permit?
❑
❑ ❑
Is the crop cover acceptable?
❑ ❑ ❑
Is the site condition adequate?
❑ ❑ ❑
Is the site free of runoff / ponding?
❑ ❑ ❑
Page 4 of 6
DocuSign Envelope ID: OD0212D4-6715-4E14-B33C-15CF62E7291A
Permit: WQ0005233 Owner - Facility: US WAS Cherry Point
Inspection Date: 01/23/2024 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Is the acreage specified in the permit being utilized?
0
❑ ❑ ❑
Is the application equipment present?
0
❑ ❑ ❑
Is the application equipment operational?
0
❑ ❑ ❑
Is the disposal field free of limiting slopes?
0
❑ ❑ ❑
Is access restricted and/or signs posted during active site use?
0
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
How close is the closest water supply well?
❑
❑ ❑
Is municipal water available in the area?
❑
❑ ❑
# Info only: Does the permit call for monitoring wells?
0
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
0
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Are monitoring wells damaged?
❑
0 ❑ ❑
Comment: Irrigation fields are well maintained and securely fenced.
Rain sensors were installed to
prevent irrigation during rainfall. Field 3 was dosed during
inspection and irrigation pattern
was uniform and spray heads were all operable. No evidence of ponding or runoff was
observed. Annual Soil analysis is performed. Groundwater monitoring wells were maintained,
capped and locked.
STABILIZATION LAGOON
Treatment Lagoons Yes No NA NE
Lagoon Type None
Primary/Secondary Primary
Influent structure 0 ❑ ❑ ❑
Banks/berms (seepage and erosion) 0 ❑ ❑ ❑
Vegetation (excessive vegetation on banks/berms) ❑ 0 ❑ ❑
Liner ❑ ❑ ❑ ❑
Liner Type Full, synthetic
Baffles/curtains ❑ ❑ 0 ❑
Freeboard Marker 0 ❑ ❑ ❑
Required freeboard 2
Feet
Actual freeboard 4
Feet
Are increments clearly marked on gauge at adequate intervals? 0 ❑ ❑ ❑
Has the water level gauge been surveyed w/ respect to lowest point on dike? wall? ❑ ❑ ❑
Page 5 of 6
DocuSign Envelope ID: OD0212D4-6715-4E14-B33C-15CF62E7291A
Permit: WQ0005233 Owner - Facility: US MCAS Cherry Point
Inspection Date: 01/23/2024 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
No Evidence of overflow
❑
0 ❑ ❑
Acceptable color
0
❑ ❑ ❑
Floating mats
❑
0 ❑ ❑
Excessive solids buildup
❑
0 ❑ ❑
Aerators/mixers
❑
❑ 0 ❑
Effluent structure
0
❑ ❑ ❑
Lagoon cover
❑
❑ 0 ❑
Page 6 of 6