HomeMy WebLinkAboutNC0089893_For CEI 12/11/2023_20240123CDM Constructors Inc.
9220 Cleveland Ave, Suite 100
Rancho Cucamonga, Ca. 91730
CALIBRATION REPORT
Job Name.
Job No.
Tag No.
P&ID No.
Application Type
Transmitter
Process Range
Reference Value
4.00 mA
8.00 mA
12.00 mA
16.00 mA
20.00 mA
Digital
Process Range
Range
N/A
Process Solution Standards
Process Range
Standard Value
REMARKS:
Transmitter has a low/empty calibration of 3' and a high calibration 1'. This is due to the parshall flume being 2' in height and the transducer being located 1' above the top of the
flume. The blanking distance of the transducer is 1'.
X
Remarks
Transmitter:
MAKE
MODEL#
SERIAL #
EXP.
Transmitter
Positioner
Other
Input
Trip
N/A
Displayed Value
Siemens
7ML5050-OBA12-1DAO-Z+Z11 (LUT400)
PBD/P1300088
Union County
231695
FIT-4803
I-1101
Output
0 GPM
2100 GPM
DeadBand
N/A
As Calibrated
Standard Value
As Calibrated
Reference Value
4.00 mA
8.00 mA
12.00 mA
16.00 mA
20.00 mA
As Calibrated
Range
N/A
Displayed Value
Controller
Switch
Instrument Type.
Manufacturer.
Process Range.
Process Area.
Input
Trip
N/A
Notes
Calibrated By:
Date:
Witnessed by:
Jeff Leonard
10/31/2023
Sensor:
MAKE
MODEL
SERIAL #
EXP.
Output
0 GPM
2100 GPM
DeadBand
N/A
Flow Transmitter
Siemens
0 - 2100 GPM
NPDES FLOW
Siemens
7ML1116-1BA20-OA Y17 (XRS-5)
PBD/P1186514
Notes
Notes
PHONE: 1 909-579-3500
FAX: 1 909-980-5185
Signal Conditioner
Indicator