HomeMy WebLinkAboutNCG551085_Inspection Letter_20230712 July 12, 2023 Wade Davis 2525 Holly Ln. Durham, NC 27712 Subject: NOTICE OF DEFICIENCY NOD-2023-PC-0200 Compliance Evaluation Inspection Single Family Wastewater Treatment System General NPDES Permit NCG550000 Certificate of Coverage NCG551085 Facility: 2525 Holly Ln Durham County Dear Wade Davis On June 28, 2023, Chris Smith from the Raleigh Regional Office visited your single-family residence (SFR) wastewater treatment system to evaluate compliance with the subject General NPDES Permit. DWR Staff attempted to contact you prior to the inspection. No one was at home at the time of the inspection. Our records indicate the treatment system consists of a septic tank, pump tank, effluent pump, two recirculating sub-surface sand filters in parallel, 4:1 ratio box, tablet chlorinator with chlorine contact chamber, discharge pipe and a rip-rap apron for post aeration, and associated appurtenances. General NPDES Permit NCG550000 and Certificate of Coverage (COC) NCG551085 authorize the discharge of domestic wastewater from your treatment system to receiving waters designated as Haw River (classified WS-IV, NSW) in the Cape Fear River Basin. The authorized discharge is in accordance with the effluent limits and monitoring requirements established within the General Permit. The checked boxes below show what conditions were noted at your facility: 1. Treatment system operation: The wastewater treatment system shall be maintained at all times to prevent seepage of sewage to the surface of the ground. 2. Pumping the septic tank: You are required to inspect the septic tank at least yearly to determine if solids must be removed or if other maintenance is necessary. Septic tanks should be pumped out every five years or when the solids level is found to be more than 1/3 of the liquid depth in the septic tank compartment, whichever is DocuSign Envelope ID: 2E880EEC-D0D2-4BA6-A58E-7FDE0FB3807D Wade Davis, NCG551085 July 12, 2023 Page 2 of 3 greater. A pumping company can check the status periodically and determine when pumping is required. Within 30-days of receiving this letter, please send a copy of the most recent receipt/invoice to this office showing the date the septic tank was last checked and/or pumped out. The General NPDES Permit requires the permittee to retain records associated with sewage disposal activities for a period of at least 5 years. 3. Chlorine tablets in the chlorinator: You are reminded that it is required that chlorine tablets be maintained in the chlorinator to ensure proper disinfection of the discharged wastewater. Chlorine tablets provide effective disinfection and prevent/limit harmful bacteria from discharging to the environment. The product label for these tablets must indicate the tablets are approved for wastewater use and not for swimming pools. Part 1, Section D (1) of General NPDES Permit NCG550000 requires the permittee to inspect the tablet chlorinator weekly to ensure there is an adequate supply of tablets for continuous and proper operation. Section D (4) requires the permittee to maintain all system components, including...disinfection units...at all times and in good operating order. The inspector did not observe any chlorine tablets in the chlorinator. 4. Analyzing the effluent: Part 1. C., Effluent Limitations and Monitoring Requirements, within General Permit NCG550000 requires a permittee to sample and analyze the effluent leaving his/her treatment system prior to discharge annually. Parameters to be sampled and analyzed include Flow, BOD (Biochemical Oxygen Demand), Total Suspended Solids, Fecal Coliform and Total Residual Chlorine. Within 30-days of receiving this letter, please let this office know if you have monitored your effluent discharge within the last 12 months, and provide this office with a copy of the lab results if you have. If you have not monitored your effluent, then please collect a representative sample of the effluent, have it analyzed by a certified commercial laboratory and submit the results to this office no later than October 12, 2023. If, during this time, you are unable to collect a representative sample of the effluent discharge due to insufficient flow from the discharge pipe, then update this office with that information and continue to monitor the discharge and if conditions for sampling become favorable, then arrange to collect a sample. Failure to monitor the effluent discharge as required is a violation of NPDES General Permit NCG550000. 5. Discharge outlet location. The permittee is required to conduct a visual review of the outfall location at least twice each year (one at the time of sampling) to ensure that no visible solids or other obvious evidence of system malfunctioning is observed. Any visible signs of a malfunctioning system shall be documented and steps taken to correct the problem. The end of discharge pipe was not visible nor accessible the day of the inspection. To comply with the general permit monitoring requirements, you need to be able to sample and analyze the effluent from your SFR system through the DocuSign Envelope ID: 2E880EEC-D0D2-4BA6-A58E-7FDE0FB3807D Wade Davis, NCG551085 July 12, 2023 Page 3 of 3 discharge pipe. The outfall could not be located during the inspection due to the area being overgrown with vegetation. You need to keep the area around the discharge pipe cleared of vegetation, soil and leaves. Please take the necessary steps to ensure the discharge outlet is visible and accessible. Maintaining the area will allow you to monitor the discharge and to collect effluent samples as required by the subject permit. Part II Section B.14 of General Permit NCG550000 requires the permittee to “pay the annual administering and compliance monitoring fee within thirty days after being billed by the Division.” Division records indicate the required annual fee ($60 per year) for the period ending October 31, 2023 and due November 3, 2022, has been paid. There are no overdue fees for the subject COC. The wastewater treatment system should be periodically inspected to ensure the treatment components are always maintained and in good operating order. You are also reminded to maintain all monitoring data and associated maintenance records onsite for a minimum of three years and available for inspection. This inspection report is being issued as a Notice of Deficiency because of issues noted in items 3 and 5 above. Within 30-days receipt of this letter, please submit a written response to this office indicating the actions you will take or have taken to comply with or resolve the issues noted above. If you have questions or comments about this inspection or the requirements to take corrective action (if applicable), then please contact Vanessa Manuel at 919-791-4232. Sincerely, Vanessa E. Manuel, Assistant Regional Supervisor Water Quality Regional Operations Section Raleigh Regional Office Division of Water Resources, NCDEQ Attachment(s): EPA Water Compliance Inspection Report Cc: Laserfiche DocuSign Envelope ID: 2E880EEC-D0D2-4BA6-A58E-7FDE0FB3807D