Loading...
HomeMy WebLinkAboutNC0068799_CEI_20231130DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E ROY COOPER Co,ernor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director o-`"` sreve4 l��QWM'�a NORTH CAROLINA Environmental Quality SENT VIA ELECTRONIC MAIL ONLY, NO HARD COPY WILL BE MAILED December 21, 2023 Brian Osteen, Owner Greystone Enterprises Inc Email: bosteen215@gmail.com SUBJECT: Compliance Inspection Report Greystone Subdivision NPDES WW Permit No. NCO068799 Henderson County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Greystone Subdivision on 11/30/2023. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in NPDES WW Permit No. NC0068799. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. If you should have any questions, please do not hesitate to contact me, Rachel Rose with the Water Quality Regional Operations Section in the Asheville Regional Office, at 828-296-4500 or via email at rachel.rose@deq.nc.gov. Sincerely, DocuSi�g/ne�d bye: Ev G�3 SACE19D3940C494... Rachel Rose, Environmental Specialist Water Quality Regional Operations Section Asheville Regional Office Division of Water Resources, NCDEQ ATTACHMENTS: Inspection Report Ec: Laserfiche Juanita James (BORC, James & James Environmental) o m' D NOrlhCarolingnpl cc120f0U S.Highwal 701l IDa—. North C Resources Ashc+llk Rc9knal Officc 209p U.S. Highway 70 Swannanoa, North Camllna 25776 62&296.4500 DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 u 3 I NC0068799 I11 121 23/11/30 I17 18I � I 19 I s I 20L] 21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 67 I 72 I n, I 71 I 74 79 I I I I I I I80 701 I 71 I LL -1 I I LJ Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 10:OOAM 23/11/30 21/07/01 Greystone Subdivision NCSR 1513 Exit Time/Date Permit Expiration Date Hendersonville NC 28792 11:OOAM 23/11/30 25/11/30 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Juanita Reed James/ORC/828-697-0063/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Brian Osteen,9 Greystone Dr Hendersonville NC 28792//828-693-5534/ Yes Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenar 0 Records/Reports Self -Monitoring Progran 0 Sludge Handling Dispo: Effluent/Receiving Wate Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date 12/21/2023 Eazo Lauren EArmeni DWR/ARO WQ/828-296-4500/ 12/21/2023 Mara G Chamlee DWR/ARO WQ/828-296-4500/ I�AaYa C Rachel J�ILt- Rose DWR/ARO WQ/828-296-4500/ 12/21/2023 �LG'9 Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date Ell—s°"'" 12/21/2023 ottt EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E NPDES yr/mo/day Inspection Type (Cont.) NCO068799 I11 12I 23/11/30 117 18 i c i Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Rachel Rose, Lauren Armeni, and Mara Chamlee, with the ARO Regional Office (ARO), met with Juanita James (BORC, James & James Environmental), Hannah Turner (General Manager, James & James Environmental), and Jeff Singleton (Maintenance Tech, James & James Environmental) to conduct a Compliance Evaluation Inspection on November 30, 2023 for the Greystone Subdivision WWTP. This inspection was conducted to determine whether the facility is being operated and maintained in compliance with NPDES Permit No. NC0068799. The following items were noted during the inspection: Operations & Maintenance: There was significant rusting of the grating throughout the facility, especially the grating between the aeration basin and digester. It is suggested to replace the grating for the safety of the workers. Secondary Clarifier: The floating solids seemed excessive at the time of the inspection, however, the skimmer is turned on manually by the ORC and had not yet been turned on for the day at the time of the inspection. When it was turned on briefly during the inspection, the skimmer was working and the top layer of solids was clearing up efficiently. Effluent Pipe: The right of way needs to be maintained to allow for regular observation of the effluent pipe. Standby Power: The control panel for the WWTP does not have the correct connection requirements to be powered by a generator and there is no generator currently available. The subdivision is on city water which allows for flow to reach the WWTP if the power went out, so updating the control panel to be able to connect to a portable backup generator to have a form of standby power available is suggested if funds are available. Page# DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E Permit: NCO068799 Owner -Facility: Greystone Subdivision Inspection Date: 11/30/2023 Inspection Type: Compliance Evaluation Permit (If the present permit expires in 6 months or less). Has the permittee submitted a new application? Is the facility as described in the permit? # Are there any special conditions for the permit? Is access to the plant site restricted to the general public? Is the inspector granted access to all areas for inspection? Comment: Operations & Maintenance Is the plant generally clean with acceptable housekeeping? Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge Judge, and other that are applicable? Yes No NA NE ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ❑ ■ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Comment: The process controls analyzed are pH, DO, and observation of aeration basin foam and sludge return thickness. There is significant rusting of grating throughout facility. See summary for details. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ■ ❑ ❑ ❑ Is all required information readily available, complete and current? ■ ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ■ ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ■ ❑ ❑ ❑ Is the chain -of -custody complete? ■ ❑ ❑ ❑ Dates, times and location of sampling ■ Name of individual performing the sampling ■ Results of analysis and calibration ■ Dates of analysis ■ Name of person performing analyses ■ Transported COCs ■ Are DMRs complete: do they include all permit parameters? ■ ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ■ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ ❑ ■ ❑ operator on each shift? Is the ORC visitation log available and current? ■ ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ■ ❑ ❑ ❑ Page# 3 DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E Permit: NCO068799 Owner -Facility: Greystone Subdivision Inspection Date: 11/30/2023 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Is the backup operator certified at one grade less or greater than the facility 0 ❑ ❑ ❑ classification? Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: Bar Screens Yes No NA NE Type of bar screen a.Manual b.Mechanical ❑ Are the bars adequately screening debris? 0 ❑ ❑ ❑ Is the screen free of excessive debris? ■ ❑ ❑ ❑ Is disposal of screening in compliance? ■ ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ ■ ❑ Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ ❑ Comment: The diffusers are set on an automatic timer cycle of 30 minutes on and 30 minutes off The settleability was recorded at approximately 46% or 540 mL/1000 mL at the time of the inspection. Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ 0 ❑ Are weirs level? 0 ❑ ❑ ❑ Page# 4 DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E Permit: NCO068799 Owner -Facility: Greystone Subdivision Inspection Date: 11/30/2023 Inspection Type: Compliance Evaluation Secondary Clarifier Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ■ ❑ ❑ Comment: The sludge blanket measured to be at 3 ft out of 9 ft of water at the time of the inspection; however, the BORC indicated that it was time to waste at the facility. The solids are pumped every 4-6 months or as needed. The last pumping service was done on November 21, 2023 by Mike's Septic Tank Service. See summary for details. Aerobic Digester Yes No NA NE Is the capacity adequate? 0 ❑ ❑ ❑ Is the mixing adequate? ❑ ❑ ❑ Is the site free of excessive foaming in the tank? ❑ ❑ ❑ ■ # Is the odor acceptable? 0 ❑ ❑ ❑ # Is tankage available for properly waste sludge? 0 ❑ ❑ ❑ Comment: The aerobic digester diffusers were not runninq at the time of the inspection because it only runs when the facility is wasting. The diffusers are set on an automatic timer cycle of 30 minutes on and 30 minutes off when the facility is wasting. The digester is pumped when the secondary clarifier is pumped. Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? 0 ❑ ❑ ❑ Number of tubes in use? 2 Is the level of chlorine residual acceptable? ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑ Comment: One of the tubes is broken and cloqqed with old tablets and needs to be replaced and cleaned out. The chlorine contact chamber is pumped when the secondary clarifier is pumped. De -chlorination Yes No NA NE Type of system ? Tablet Page# 5 DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E Permit: NCO068799 Inspection Date: 11/30/2023 De -chlorination Is the feed ratio proportional to chlorine amount (1 to 1)? Owner -Facility: Greystone Subdivision Inspection Type: Compliance Evaluation Is storage appropriate for cylinders? # Is de -chlorination substance stored away from chlorine containers? Comment: Are the tablets the proper size and type? Are tablet de -chlorinators operational? Number of tubes in use? Comment: Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Comment: A bucket and timer is used to measure the effluent flow. Effluent Sampling Is composite sampling flow proportional? Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: The permit requires grab samples. Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: The right of way needs to be maintained. See summary for details. Yes No NA NE ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ N Yes No NA NE ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ Yes No NA NE ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ Yes No NA NE ❑ ■ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ Page# 6 DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E Permit: NC0068799 Owner -Facility: Greystone Subdivision Inspection Date: 11/30/2023 Inspection Type: Compliance Evaluation Standby Power Is automatically activated standby power available? Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? Yes No NA NE ❑ ■ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ Comment: There is no ability to connect to a generator to the WWTP if the power were to go out. See summary for details. Page# 7