HomeMy WebLinkAboutNC0068799_CEI_20231130DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E
ROY COOPER
Co,ernor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
o-`"` sreve4
l��QWM'�a
NORTH CAROLINA
Environmental Quality
SENT VIA ELECTRONIC MAIL ONLY, NO HARD COPY WILL BE MAILED
December 21, 2023
Brian Osteen, Owner
Greystone Enterprises Inc
Email: bosteen215@gmail.com
SUBJECT: Compliance Inspection Report
Greystone Subdivision
NPDES WW Permit No. NCO068799
Henderson County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Greystone Subdivision
on 11/30/2023. This inspection was conducted to verify that the facility is operating in compliance with
the conditions and limitations specified in NPDES WW Permit No. NC0068799. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact me, Rachel Rose with the Water
Quality Regional Operations Section in the Asheville Regional Office, at 828-296-4500 or via email at
rachel.rose@deq.nc.gov.
Sincerely,
DocuSi�g/ne�d bye:
Ev
G�3
SACE19D3940C494...
Rachel Rose, Environmental Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Laserfiche
Juanita James (BORC, James & James Environmental)
o m' D NOrlhCarolingnpl cc120f0U S.Highwal 701l IDa—. North C Resources
Ashc+llk Rc9knal Officc 209p U.S. Highway 70 Swannanoa, North Camllna 25776
62&296.4500
DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0068799 I11 121 23/11/30 I17 18I � I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:OOAM 23/11/30
21/07/01
Greystone Subdivision
NCSR 1513
Exit Time/Date
Permit Expiration Date
Hendersonville NC 28792
11:OOAM 23/11/30
25/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Juanita Reed James/ORC/828-697-0063/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Brian Osteen,9 Greystone Dr Hendersonville NC 28792//828-693-5534/
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar 0 Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
12/21/2023
Eazo
Lauren EArmeni DWR/ARO WQ/828-296-4500/
12/21/2023
Mara G Chamlee DWR/ARO WQ/828-296-4500/
I�AaYa
C
Rachel J�ILt-
Rose DWR/ARO WQ/828-296-4500/ 12/21/2023
�LG'9
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Ell—s°"'" 12/21/2023
ottt
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E
NPDES yr/mo/day Inspection Type (Cont.)
NCO068799 I11 12I 23/11/30 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Rachel Rose, Lauren Armeni, and Mara Chamlee, with the ARO Regional Office (ARO), met with
Juanita James (BORC, James & James Environmental), Hannah Turner (General Manager, James &
James Environmental), and Jeff Singleton (Maintenance Tech, James & James Environmental) to
conduct a Compliance Evaluation Inspection on November 30, 2023 for the Greystone Subdivision
WWTP. This inspection was conducted to determine whether the facility is being operated and
maintained in compliance with NPDES Permit No. NC0068799.
The following items were noted during the inspection:
Operations & Maintenance: There was significant rusting of the grating throughout the facility,
especially the grating between the aeration basin and digester. It is suggested to replace the grating
for the safety of the workers.
Secondary Clarifier: The floating solids seemed excessive at the time of the inspection, however, the
skimmer is turned on manually by the ORC and had not yet been turned on for the day at the time of
the inspection. When it was turned on briefly during the inspection, the skimmer was working and the
top layer of solids was clearing up efficiently.
Effluent Pipe: The right of way needs to be maintained to allow for regular observation of the effluent
pipe.
Standby Power: The control panel for the WWTP does not have the correct connection requirements
to be powered by a generator and there is no generator currently available. The subdivision is on city
water which allows for flow to reach the WWTP if the power went out, so updating the control panel to
be able to connect to a portable backup generator to have a form of standby power available is
suggested if funds are available.
Page#
DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E
Permit: NCO068799 Owner -Facility: Greystone Subdivision
Inspection Date: 11/30/2023 Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: The process controls analyzed are pH, DO, and observation of aeration basin foam
and sludge return thickness. There is significant rusting of grating throughout
facility.
See summary for details.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Page# 3
DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E
Permit: NCO068799 Owner -Facility: Greystone Subdivision
Inspection Date: 11/30/2023 Inspection Type: Compliance Evaluation
Record Keeping
Yes
No
NA
NE
Is the backup operator certified at one grade less or greater than the facility
0
❑
❑
❑
classification?
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment:
Bar Screens
Yes
No
NA
NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
■
❑
❑
❑
Is disposal of screening in compliance?
■
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Aeration Basins
Yes
No
NA
NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
■
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
Comment: The diffusers are set on an automatic timer cycle of 30 minutes on and 30 minutes off
The settleability was recorded at approximately 46% or 540 mL/1000 mL at the time of
the inspection.
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
0
❑
❑
❑
Page# 4
DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E
Permit: NCO068799 Owner -Facility: Greystone Subdivision
Inspection Date: 11/30/2023 Inspection Type: Compliance Evaluation
Secondary Clarifier
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
■
❑
❑
❑
■
❑
❑
❑
❑
■
❑
❑
Comment: The sludge blanket measured to be at 3 ft out of 9 ft of water at the time of the
inspection; however, the BORC indicated that it was time to waste at the facility. The
solids are pumped every 4-6 months or as needed. The last pumping service was done
on November 21, 2023 by Mike's Septic Tank Service. See summary for details.
Aerobic Digester
Yes
No
NA
NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
❑
❑
❑
Is the site free of excessive foaming in the tank?
❑
❑
❑
■
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: The aerobic digester diffusers were not runninq at the time of the inspection because it
only runs when the facility is wasting. The diffusers are set on an automatic timer cycle
of 30 minutes on and 30 minutes off when the facility is wasting. The digester is
pumped when the secondary clarifier is pumped.
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? 0 ❑ ❑ ❑
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Number of tubes in use? 2
Is the level of chlorine residual acceptable? ❑ ❑ ❑
Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑
Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑
Comment: One of the tubes is broken and cloqqed with old tablets and needs to be replaced and
cleaned out. The chlorine contact chamber is pumped when the secondary clarifier is
pumped.
De -chlorination Yes No NA NE
Type of system ? Tablet
Page# 5
DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E
Permit: NCO068799
Inspection Date: 11/30/2023
De -chlorination
Is the feed ratio proportional to chlorine amount (1 to 1)?
Owner -Facility: Greystone Subdivision
Inspection Type: Compliance Evaluation
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: A bucket and timer is used to measure the effluent flow.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: The permit requires grab samples.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: The right of way needs to be maintained. See summary for details.
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
N
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Yes
No
NA NE
❑
■
❑
❑
■
❑
❑
❑
❑
❑
■
❑
Page# 6
DocuSign Envelope ID: 9BDDA491-C13E-47BE-9903-4D1598125B3E
Permit: NC0068799 Owner -Facility: Greystone Subdivision
Inspection Date: 11/30/2023 Inspection Type: Compliance Evaluation
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Yes
No
NA
NE
❑
■
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
Comment: There is no ability to connect to a generator to the WWTP if the power were to go out.
See summary for details.
Page# 7