HomeMy WebLinkAboutNCG551566_Compliance Evaluation Inspection_20230602ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
White Cross Volunteer Fire Department
Attn: Tony Blake
5722 Old Greensboro Hwy.
Chapel Hill, NC 27516
NORTH CAROLINA
Envirorunenral Quafity
July 12, 2023
Subject: Compliance Evaluation Inspection
Single Family Wastewater Treatment System
General NPDES Permit NCG550000
Certificate of coverage NCG551566
Facility: 5722 Old Greensboro Hwy
Orange County
Dear Mr. Blake,
On June 2, 2023, Curtis Tyree from the Raleigh Regional Office visited your single-family
residence (SFR) wastewater treatment system to evaluate compliance with the subject General
NPDES Permit.
Our records indicate the treatment system consists of two septic tanks; a recirculation tank; two
AdvanTex pods; a control panel with telemetry and Ultraviolet disinfection; and an out fall
discharge pipe.
General NPDES Permit NCG550000 and Certificate of Coverage (COC) NCG551566 authorize
the discharge of domestic wastewater from your treatment system to an unnamed tributary to
Persimmon Nursery Branch to coIlins Creek, classified WS-IV NSW waters in the Cape Fear
River Basin.
Findings during the inspection were as follows:
1. The septic tank shall be checked annually and pumped out every 3 to S years. The system
is under contract by AWT and is inspected two times per year. As of the last time the
system was inspected, the septic tank did not need to be pumped.
2. UV disinfection. The UV disinfection was working at the time of the inspection. The alarms
were set up on telemetry and AWT inspects the system two times per year.
3. Treatment system operation. The treatment system shall he maintained at all times to
prevent seepage of sewage to the surface of the ground. At the time of the inspection, the
system appeared to be well maintained and AWT inspects the system two times per year.
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office 1 3900 Barrett Drive I Raleigh, North Carolina 27609
919 791 4200
4. Outfall location. A visual review of the outfall location shall be executed twice each year
(one at the time of sampling) to ensure that no visible solids or other obvious evidence of
system malfunctioning is observed. Any visible signs of a malfunctioning system shall be
documented, and steps taken to correct the problem. At the time of the inspection, the
outfall location was clear and appeared to be well maintained and free of any obstructions.
There was no water discharging at the time of the inspection.
5. Effluent sampling requirements. Effluent sampling must be conducted annually as part
of your permit requirements. The effluent samples must be analyzed by a North Caroline
Certified Lab and the results must be kept on site for three years. The last effluent
sampling was performed in November 2022 and the results were within the permit limits.
Sampling in 2023 has not been conducted at the time of this inspection.
6. Fees and renewals. COC's with unpaid administering and compliance monitoring fees
will not be automatically renewed. The fees must be paid annually and within 30 days of
notification. All fees have been paid.
If you have questions or comments about this inspection or the requirements of your permit,
please contact Curtis Tyree via email at curt is. t ree de .nc. gov or 919-791-4251.
Sincerely,
Vanessa E. Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NCDEQ
Attachment: EPA Water Compliance Inspection Report
Cc: Laserfiche
D North Carolina Department of Environmental Quality Division of Water Resources
512 North Salisbury Street 1 1611 Mail Service Center 1 Raleigh. North Carolina 27699-161 l
iiwiw`wwwi w .wiYr� prwr
919 707 9000
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C.20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/molday Inspection Type Inspector Fee Type
1 I nt I 2 15 I 3 NCG551566 11 12 23/06/02 17 18 [ (j l 9 j g j 20I I
211 1 1 1 1 1 1 1 1 1 11 1 I 1 1 1„.1 1 1 1 1 1 1 1 �. I I I I I I I I I II—I_I_I I I, 166
_.I
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67 70 LJI 71liI 72 LtiJ 73 L1 74 7 1 1 1 1 1 80
_Lj
Section B: FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:55AM 23/06/02
21/08/18
5722 Old Greensboro Highway
Exit Time/Date
Permit Expiration Date
5722 Old Greensboro Hwy
Chapel Hill NC 27516
11:15AM 23/06/02
25/10/31
Name(s) of Onsite Representative(s�Titles(s)1Phone and Fax Number(s)
Other Facility Data
!1!
Name, Address of Responsible OfiicialMlle/Phone and Fax Number
Tony Blake,5722 Old Greensboro Hwy Chapel Hill NC 2751611919-942-11941 Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Operations & Maintenar N Records/Reports Facility Site Review
Effluent/Receiving Wate 0 Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) AgencyrOfficelPhone and Fax Numbers Date
Curtis R Tyree DWRIRRO WQI919-791-4239J
Signature of Man ement Q A Reviewer AgencylOffice/Phone and Fax Numbers Date
r f / 9- 4 9/-- , fn 7e3'43
EPA Form 3560-3 (Rev 9-94) Previous ed tions are obsolete.
Page#
Y
NPDES yrlmolday :rspection Type 1
NOG551566 23106l02 17 18 1 r l
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The system is under contract with AWT.
The septic tank didn't need to be pumped out as of the lest inspection by AWT.
The advantex system was operating at the time of the inspection.
The system appears to be well maintained.
Page#
Permit: WG551566 Owner- Facility- 5722 Old Greensboro Highway
Inspection Date: 06102/2023 Inspection Type: fompliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ M ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit
Yes
No
NA NE
(If the present permit expires to 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
M
❑
❑
❑
# Are there any special conditions for the permit?
[IN
❑
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection?
M
❑
❑
❑
Comment:
Effluent Moe Yes No NA NE
Is right of way to the outfall properly maintained? M ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ❑
Comment:
Disinfection - UV
Yes
No
NA NE
Are extra UV bulbs available on site?
❑
❑
❑
Are UV bulbs clean?
❑
❑
❑
Is UV intensity adequate?
❑
❑
❑
Is transmittance at or above designed level?
❑
❑
■
❑
Is there a backup system on site?
❑
❑
0
❑
Is effluent clear and free of solids?
M
❑
❑
❑
Comment:
Se tic Tank
Yes No
NA NE
(If pumps are used) Is an audible and visual alarm operational?
M
❑
❑
❑
Is septic tank pumped on a schedule?
■
❑
❑
❑
Are pumps or syphons operating properly?
❑
❑
M
❑
Are high and low water alarms operating properly?
❑
❑
❑
Page# 3
Permit: NCG551566
Inspection Date: 06/02/2023
Septic Tank
Comment:
Owner - Facility: 5722 Old Greensboro Highway
Inspection Type: Compliance Evaluation
Yes No NA NE
Page#