HomeMy WebLinkAboutNC0020737_Compliance Evaluation Inspection_20231109ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director CERTIFIED MAIL #: 7020 3160 0000 3283 0779 RETURN RECEIPT REQUESTED; Rick Duncan, Water Resources Director City of Kings Mountain Post Office Box 429 Kings Mountain, NC 28086-0429 SUBJECT: Notice of Violation NORTH CAROLINA Environmental Quality November 9, 2023 Compliance Evaluation Inspection City of Kings Mountain -Pilot Creek WWTP NPDES Permit No. NCO020737 Cleveland County Tracking #: NOV-2023-PC-0555 Dear Mr. Duncan: Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject facility on October 30, 2023, by Mr. Wes Bell of this Office. This Office would like to thank all WWTP staff for their cooperation and assistance that was provided throughout this inspection. Please advise the facility's Operator -in -Responsible Charge (ORC) of our findings by forwarding the enclosed report. This report is being issued as a Notice of Violation (NOV) due to the following: - Unapproved effluent dissolved oxygen measurements were reported on the May and June 2023 monitoring reports; - Flow proportional influent and effluent composite samples were not being collected. Please be advised that the failures to properly sample the effluent dissolved oxygen and collect flow proportional influent and effluent composite samples are violations of the subject NPDES Permit and North Carolina General Statute (G.S.) 143-215.1. Please note that G.S. 143-215.6A provides for a civil penalty of not more than twenty-five thousand dollars ($25,000.00), or twenty-five thousand dollars ($25,000.00) per day when the violation is of a continuing nature, against any person who violates or fails to act in accordance with the terms, conditions, or requirements of any permit issued pursuant to G.S. 143-215.1. Penalties may also be assessed for any damage to surface waters of the State that may result from the violation. North Carolina Department of Environmental Quality I Division of Water Resources Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115 704.663.1699 It is requested that a written response be submitted to this Office by November 30, 2023, detailing the actions taken to address all violations as discussed in this report. In responding, please address your comments to the attention of Mr. Wes Bell. As discussed in the inspection report, the City may submit a variance request to the Division to collect time -based (constant time/constant volume) composite samples only if the daily flow rates do not vary by more than 15%. The request should include a week's worth of daily flow charts, listing of any equalization facilities, flow description throughout the wastewater facility and any other supplemental information that could assist in the Division's decision. Please submit the variance request to the attention of Mr. Bell. Should you have any questions concerning this Notice, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bellkdeq.nc• gov. Enclosure: Inspection Report Cc: NPDES Program Files - Laserfiche Sincerely, Docu Signed by: 4d4tV i1 PU4,ti. F161FB69A2D84A3... Andrew H. Pitner, P.G. Regional Supervisor Water Quality Regional Operations Section Mooresville Regional Office Division of Water Resources, NCDEQ EQ; North Carolina Department of Environmental Quality [ Division of Water Resources Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115 704.663.1699 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 u 3 I NC0020737 I11 121 23/10/26 I17 18I � I 19 I s I 201 I 211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 67 I 72 I n, I 71 I 74 79 I I I I I I I80 701LJ � I 71 [ LL -1 I I Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 09:25AM 23/10/26 20/02/01 Pilot Creek WWTP 200 Potts Creek Rd Exit Time/Date Permit Expiration Date Kings Mountain NC 28086 03:OOPM 23/10/26 23/08/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Rickey Lee Bailey/ORC/704-739-7131/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Ricky Duncan,PO Box 429 Kings Mtn NC 280860429//704-734-4525/7047302152 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenar Records/Reports Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Wes Bell signedby: DWR/MROWQ/704-235-2192/ 11/8/2023 2 re& E�Docu`,','�96D90=437 ... Signature of M r&AYReviewer Agency/Office/Phone and Fax Numbers Date Andrew Pi 0""{'''�' H P'4"f"DWR/MRO WQ/704-663-1699 Ext.2180/ 11/9/2023 F161FB69A2D84A3... EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type NCO020737 I11 12I 23/10/26 117 18 i c i (Cont.) Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On -site Representatives: The following City staff were in attendance during the inspection: Mr. Donnie Spencer, Mr. Lee Bailey and Mr. Kevin Hodges. Record Keeping Section cont'd: Several eDMRs will be revised and resubmitted to correct transcription errors in the following months: - October 2022 (correct units of measurement for influent selenium and thallium); - April 2023 [correct units of measurement for effluent selenium, thallium, and oil & grease (and influent), zinc (and influent), correct ">" symbol to "<" for influent oil & grease, and remove one effluent mercury value — 11th or 13th]; - May 2023 (correct units of measurement for effluent thallium); - July 2023 [add effluent tox value and correct units of measurement for effluent arsenic (and result) and cyanide]. Effluent temperature values should also be added on all eDMRs starting in May 2023. The facility staff must ensure all units of measurement, sample types, etc. are correctly reported on all future eDMRs. Page# Permit: NCO020737 Owner -Facility: Pilot Creek WWTP Inspection Date: 10/26/2023 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new 0 ❑ ❑ ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? ❑ ❑ ❑ Comment: The Division received the City's permit renewal package on 3/7/2023. The City implements a Division -approved Industrial Pretreatment Program. The last compliance evaluation inspection at this facility was performed by DWR staff on 3/22/2022. Record Keeping Are records kept and maintained as required by the permit? Is all required information readily available, complete and current? Are all records maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? Has the facility submitted its annual compliance report to users and DWQ? (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? Is the ORC visitation log available and current? Is the ORC certified at grade equal to or higher than the facility classification? Is the backup operator certified at one grade less or greater than the facility classification? Is a copy of the current NPDES permit available on site? Facility has copy of previous year's Annual Report on file for review? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page# 3 Permit: NCO020737 Inspection Date: 10/26/2023 Record Keeping Owner -Facility: Pilot Creek WWTP Inspection Type: Compliance Evaluation Yes No NA NE Comment: The records reviewed durinq the inspection were orqanized and well maintained. Discharge Monitoring Reports (eDMRs) were reviewed for the period September 2022 through August 2023. A weekly average TSS effluent violation was reported in February 2023. The Division has previously addressed this limit violation through the issuance of a Notice of Violation (NOV). See Summary Section for additional comments. Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 ■ ❑ ❑ ❑ degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ❑ ■ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ❑ ■ Comment: Influent and effluent analyses (including filed) are performed under the City's laboratory certification #222. Meritech. Inc. has also been contracted to provide analytical support. The 10.0 S.U. pH buffer had expired and should be discarded. The lab has an additional 10.0 S.U. standard (not expired) that can be used for all future pH meter calibrations. Influent Sampling Yes No NA NE # Is composite sampling flow proportional? ❑ 0 ❑ ❑ Is sample collected above side streams? EIN ❑ ❑ Is proper volume collected? ■ ❑ ❑ ❑ Is the tubing clean? ■ ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 0 ❑ ❑ ❑ degrees Celsius)? Is sampling performed according to the permit? ❑ 0 ❑ ❑ Comment: The subject permit requires influent composite BOD and TSS samples. The facilit staff were collecting time -based (constant time/constant volume) composite influent samples. Please be advised that flow proportional influent composite samples must be collected as required by the by the subject Permit (Part II, Section A. Composite Sample). The Division may grant a variance to collect time -based composite samples only if the daily flow rates do not vary by more the 15%. A variance request has not been submitted and/or received by the Division. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ 0 ❑ ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Page# 4 Permit: NCO020737 Owner -Facility: Pilot Creek WWTP Inspection Date: 10/26/2023 Inspection Type: Compliance Evaluation Effluent Sampling Yes No NA NE Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ■ ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 0 ❑ ❑ ❑ degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type ❑ 0 ❑ ❑ representative)? Comment: The subiect permit requires composite and qrab effluent samples. The facilitv staff were collecting time -based (constant time/constant volume) composite effluent samples. Please be advised that flow proportional effluent composite samples must be collected as required by the by the subject Permit (Part II, Section A. Composite Sample). The Division may grant a variance to collect time -based composite samples only if the daily flow rates do not vary by more the 15%. A variance request has not been submitted and/or received by the Division. In addition, facility staff had used the values from the in -line dissolved oxygen (DO) monitoring system (continuous) to report the daily DO effluent values on the May and June 2023 eDMRs instead of using a calibrated hand held meter. Please be advised that daily grab samples must be collected and analyzed as required by the subject Permit (Part I, A(1) Effluent Limitations & Monitoring Requirements). Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, 0 ❑ ❑ ❑ and sampling location)? Comment: Operations & Maintenance Yes No NA Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The wastewater treatment facility appeared to be adequately treating wastewater at the NE ❑ ❑ time of the inspection. Process control measurements were being performed with the documentation being maintained on -site. The facility is equipped with a SCADA system and the wastewater treatment plant is visited seven days per week with staff on call for any alarm/emergency conditions. Pump Station - Influent Yes No NA NE Is the pump wet well free of bypass lines or structures? ■ ❑ ❑ ❑ Is the wet well free of excessive grease? 0 ❑ ❑ ❑ Are all pumps present? 0 ❑ ❑ ❑ Are all pumps operable? 0 ❑ ❑ ❑ Are float controls operable? 0 ❑ ❑ ❑ Page# 5 Permit: NCO020737 Inspection Date: 10/26/2023 Owner -Facility: Pilot Creek WWTP Inspection Type: Compliance Evaluation Pump Station - Influent Yes No NA NE Is SCADA telemetry available and operational? 0 ❑ ❑ ❑ Is audible and visual alarm available and operational? ❑ ❑ 0 ❑ Comment: The telemetry type alarm system properly operated during the on -site test on the high water alarm. Bar Screens Yes No NA NE Type of bar screen a.Manual ❑ b.Mechanical Are the bars adequately screening debris? 0 ❑ ❑ ❑ Is the screen free of excessive debris? ■ ❑ ❑ ❑ Is disposal of screening in compliance? 0 ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: Screenings are disposed at a permitted landfill. Chemical Feed Yes No NA NE Is containment adequate? 0 ❑ ❑ ❑ Is storage adequate? ■ ❑ ❑ ❑ Are backup pumps available? ■ ❑ ❑ ❑ Is the site free of excessive leaking? 0 ❑ ❑ ❑ Comment: Sodium hydroxide is added to the influent (prior to aeration basins) to maintain appropriate alkalinity/pH levels. Aeration Basins Mode of operation Type of aeration system Is the basin free of dead spots? Are surface aerators and mixers operational? Are the diffusers operational? Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Is the DO level acceptable?(1.0 to 3.0 mg/1) Yes No NA NE Ext. Air Diffused ❑ ■ ❑ ❑ ❑ ❑ ■ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page# 6 Permit: NCO020737 Inspection Date: 10/26/2023 Aeration Basins Owner -Facility: Pilot Creek WWTP Inspection Type: Compliance Evaluation Yes No NA NE Comment: All three aeration basins were operational and in service. Wastewater staff have initiated adjustments to the influent flow and air distribution sysems within the aeration basins due to operational issues associated with the blowers. Dead spots were observed due to the lack of proper aeration/mixing. The City has purchased three new blowers with the first blower to be received on -site by December 2023. Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ■ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Comment: All three secondary clarifiers (1,3,4) were operational and in service. Note: Afourth clarifier was taken out of service several years ago. The weirs for clarifier #3 were unlevel; however, no evidence of short-circuiting was observed. Plans should be made to level the weirs in the tuture. The sludge blanket level in clarifier #4 was greater than a quarter of the sidewall depth; however, wastewater staff have been wasting and reducing the MLSS level in aeration basin #4. Pumps-RAS-WAS Yes No NA NE Are pumps in place? 0 ❑ ❑ ❑ Are pumps operational? ■ ❑ ❑ ❑ Are there adequate spare parts and supplies on site? ❑ ❑ ❑ ■ Comment: Disinfection -Gas Yes No NA NE Are cylinders secured adequately? ■ ❑ ❑ ❑ Are cylinders protected from direct sunlight? 0 ❑ ❑ ❑ Is there adequate reserve supply of disinfectant? 0 ❑ ❑ ❑ Is the level of chlorine residual acceptable? 0 ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? ■ ❑ ❑ ❑ Page# 7 Permit: NCO020737 Inspection Date: 10/26/2023 Disinfection -Gas Owner -Facility: Pilot Creek WWTP Inspection Type: Compliance Evaluation Is there chlorine residual prior to de -chlorination? Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? If yes, then is there a Risk Management Plan on site? If yes, then what is the EPA twelve digit ID Number? (1000- - ) If yes, then when was the RMP last updated? Comment: Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Yes No NA NE ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ Comment: The facility is equipped with a flow meter (and V-notch weir) at the outlets of the three chlorine contact chambers. All flows from the three flow meters are totalized (automated system) and reported on the eDMRs. All flow meters are calibrated annually (at a minimum) and were last calibrated on 3/8/2023 by Laboratory Instrument Services, LLC. The ORC and staff must ensrue the contracted company that performs the calibrations provides all calibration data including instantaneous confirmation measurements. De -chlorination Yes No NA NE Type of system ? Gas Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑ Is storage appropriate for cylinders? ■ ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Comment: Are the tablets the proper size and type? ❑ ❑ 0 ❑ Are tablet de -chlorinators operational? ❑ ❑ ■ ❑ Number of tubes in use? Comment: Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Page# 8 Permit: NC0020737 Owner -Facility: Pilot Creek WWTP Inspection Date: 10/26/2023 Inspection Type: Compliance Evaluation Effluent Pipe Yes No NA NE Comment: The effluent appeared clear with no floatable solids or foam. Aerobic Digester Yes No NA NE Is the capacity adequate? 0 ❑ ❑ ❑ Is the mixing adequate? 0 ❑ ❑ ❑ Is the site free of excessive foaming in the tank? ■ ❑ ❑ ❑ # Is the odor acceptable? ■ ❑ ❑ ❑ # Is tankage available for properly waste sludge? 0 ❑ ❑ ❑ Comment: Both aerobic diqesters were operational and in service. Solids Handling Equipment Yes No NA NE Is the equipment operational? 0 ❑ ❑ ❑ Is the chemical feed equipment operational? 0 ❑ ❑ ❑ Is storage adequate? ■ ❑ ❑ ❑ Is the site free of high level of solids in filtrate from filter presses or vacuum filters? ❑ ❑ ❑ ■ Is the site free of sludge buildup on belts and/or rollers of filter press? ❑ ❑ ❑ Is the site free of excessive moisture in belt filter press sludge cake? ❑ ❑ ❑ The facility has an approved sludge management plan? 0 ❑ ❑ ❑ Comment: The belt press was operation; however, the unit was not in service at the time of the inspection. Dewatered bio-solids are transported and disposed at a permitted landfill by City staff. Standby Power Yes No NA NE Is automatically activated standby power available? 0 ❑ ❑ ❑ Is the generator tested by interrupting primary power source? 0 ❑ ❑ ❑ Is the generator tested under load? 0 ❑ ❑ ❑ Was generator tested & operational during the inspection? 0 ❑ ❑ ❑ Do the generator(s) have adequate capacity to operate the entire wastewater site? ■ ❑ ❑ ❑ Is there an emergency agreement with a fuel vendor for extended run on back-up 0 ❑ ❑ ❑ power? Is the generator fuel level monitored? 0 ❑ ❑ ❑ Comment: The facility is equipped with two generators (1 — aeration basin #3 blowers and 1 — rest of WWTP) that are serviced twice per year by Carolina Power Solutions. Page# 9