Loading...
HomeMy WebLinkAboutNC0038377_Table 7-8 2L Exceedances in Ash Pore Water_20150902TABLE 7-8 15A NCAC 2L EXCEEDANCES IN ASH PORE WATER MAYO STEAM ELECTRIC PLANT DUKE ENERGY PROGRESS, LLC, ROXBORO, NC Analytical Parameter pH Antimony Arsenic Barium Boron Cobalt Iron Manganese Thallium Total Dissolved Solids Vanadium Reporting Units S.U. ug/I ug/I ug/I ug/I ug/I ug/I ug/I ug/I mg/I ug/I 15A NCAC 02L Standard 6.5-8.5 1* 10 700 700 1* 300 50 0.2* 500 0.3* Sample ID Sample Collection Date Analytical Results ABMW-01 06/11/2015 9.1 BE BE BE BE BE BE BE BE BE BE ABMW-01 06/25/2015 BE 38 518 925 4560 6.09 1370 2280 2.47 540 314 ABMW-02 06/17/2015 BE BE 1020 BE 9200 BE 356 1110 BE BE 3.53 ABMW-03 06/17/2015 BE BE 193 BE 1940 BE 3890 451 0.289 BE 0.68 ABMW-04 06/22/2015 BE BE 499 BE 4930 1 1.49 940 1 641 1 BE 520 2.84 Prepared by: BER/SRW Checked by: JAW Notes: Rechecked by: EMB - Bold highlighted concentration indicates exceedance of the 15A NCAC 02L Standard, Appendix 2, April 1, 2013. ug/I = microgram per liter mg/I = milligram per liter S.U. = Standard Unit BE = indicates concentration was below the 15A NCAC 02B Standard, May 1, 2007 * — Interim Maximum Allowable Concentrations (IMACs) of the 15A NCAC 02L Standard, Appendix 1, April 1, 2013. P:\Duke Energy Progress.1026\105. Mayo Ash Basin GW Assessment Plan\1.11 CSA Reporting\Tables\Report Tables\Table 7-8 2L Exceedances in Ash Pore Water.xlsx Page 1 of 1