Loading...
HomeMy WebLinkAboutNC0003433_Table 9-5 2B Exceedances in Seeps and Surface Water_20150902TABLE 9-5 15A NCAC 2B EXCEEDANCES IN SEEPS AND SURFACE WATER CAPE FEAR STEAM ELECTRIC PLANT DUKE ENERGY PROGRESS, LLC, MONCURE, NC Analytical Parameter pH Arsenic Cadmium Lead Nickel Nickel Selenium Sulfate Total Dissolved Solids Zinc TOT DIS DIS DIS TOT TOT DIS Reporting Units S.U. ug/I ug/l ug/l ug/1 ug/I ug/l mg/I ug/I mg/I 15A NCAC 02B Standard 6-9 10 0.15 0.54 16 25 5 250 500 0.036 Sample ID Sample Collection Date Analytical Results S-04 06/11/2015 BE 408 BE BE BE 519 10.6 BE BE BE S-16 05/28/2015 2.7 200 1.09 BE 230 251 BE 2300 2500 0.659 S-16 06/11/2015 2.9 118 BE BE 352 206 BE 2700 2600 0.802 SW-85DS 06/11/2015 BE BE BE BE BE 27.4 BE BE BE BE SW-BA1 05/20/2015 BE BE BE BE BE BE BE BE BE 0.052 SW-BA1 DUP 05/20/2015 BE BE BE BE BE BE BE BE BE 0.164 SW-BA2 05/20/2015 BE BE BE 1.55 BE BE BE BE BE 0.04 SW-CFDG 05/28/2015 BE BE BE BE BE BE BE BE BE 0.04 SW-CFDG DUP 06/11/2015 BE BE BE BE BE BE BE BE BE 0.059 Prepared by: BER/SRW Checked by: RLP Notes: 0 - Bold highlighted concentration indicates exceedance of the 15A NCAC 02B Standard, April 22, 2015. S.U. = Standard Unit ug/I = micrograms per liter mg/I = milligrams per liter BE = indicates concentration was below (or within range for pH) the 15A NCAC 02B Standard, April 22, 2015. DUP = Duplicate DIS = Dissolved TOT = Total P:\Duke Energy Progress. 1026\103. Cape Fear Ash Basin GW Assessment\l.11 CSA Reporting\Tables\Table 9-5 2B Exceedances in Seeps and Surface Water Page 1 of 1