HomeMy WebLinkAboutNC0003433_Table 9-5 2B Exceedances in Seeps and Surface Water_20150902TABLE 9-5
15A NCAC 2B EXCEEDANCES IN SEEPS AND SURFACE WATER
CAPE FEAR STEAM ELECTRIC PLANT
DUKE ENERGY PROGRESS, LLC, MONCURE, NC
Analytical Parameter
pH
Arsenic
Cadmium
Lead
Nickel
Nickel
Selenium
Sulfate
Total
Dissolved
Solids
Zinc
TOT
DIS
DIS
DIS
TOT
TOT
DIS
Reporting Units
S.U.
ug/I
ug/l
ug/l
ug/1
ug/I
ug/l
mg/I
ug/I
mg/I
15A NCAC 02B Standard
6-9
10
0.15
0.54
16
25
5
250
500
0.036
Sample ID
Sample
Collection Date
Analytical Results
S-04
06/11/2015
BE
408
BE
BE
BE
519
10.6
BE
BE
BE
S-16
05/28/2015
2.7
200
1.09
BE
230
251
BE
2300
2500
0.659
S-16
06/11/2015
2.9
118
BE
BE
352
206
BE
2700
2600
0.802
SW-85DS
06/11/2015
BE
BE
BE
BE
BE
27.4
BE
BE
BE
BE
SW-BA1
05/20/2015
BE
BE
BE
BE
BE
BE
BE
BE
BE
0.052
SW-BA1 DUP
05/20/2015
BE
BE
BE
BE
BE
BE
BE
BE
BE
0.164
SW-BA2
05/20/2015
BE
BE
BE
1.55
BE
BE
BE
BE
BE
0.04
SW-CFDG
05/28/2015
BE
BE
BE
BE
BE
BE
BE
BE
BE
0.04
SW-CFDG DUP
06/11/2015
BE
BE
BE
BE
BE
BE
BE
BE
BE
0.059
Prepared by: BER/SRW Checked by: RLP
Notes:
0 - Bold highlighted concentration indicates exceedance of the 15A NCAC 02B Standard, April 22, 2015.
S.U. = Standard Unit
ug/I = micrograms per liter
mg/I = milligrams per liter
BE = indicates concentration was below (or within range for pH) the 15A NCAC 02B Standard, April 22, 2015.
DUP = Duplicate
DIS = Dissolved
TOT = Total
P:\Duke Energy Progress. 1026\103. Cape Fear Ash Basin GW Assessment\l.11 CSA Reporting\Tables\Table 9-5 2B Exceedances in Seeps and Surface Water Page 1 of 1