Loading...
HomeMy WebLinkAboutNC0003433_Table 7-8 2L Exceedances in Ash Pore Water_20150902TABLE 7-8 1SA NCAC 2L EXCEEDANCES IN ASH PORE WATER CAPE FEAR STEAM ELECTRIC PLANT DUKE ENERGY PROGRESS, LLC, MONCURE, NC Analytical Parameter pH Antimony Arsenic Beryllium Boron Chromium Cobalt Iron Manganese Nickel Sulfate Thallium Total Dissolved Solids Vanadium Zinc Reporting Units S.U. ug/1 ug/1 ug/I ug/I ug/I ug/1 ug/1 ug/I ug/1 mg/I ug/1 mg/1 ug/1 mg/1 15A NCAC 02L Standard 6.5-8.5 1* 10 4* 700 10 1* 300 50 100 250 0.2* 500 0.3* 1 Sample ID Sample Collection Date Analytical Results ABMW-01 05/08/2015 BE BE 582 BE 2270 BE BE 1620 161 BE BE BE BE 0.522 BE ABMW-03 05/20/2015 BE 3.59 341 BE 6360 BE BE BE 124 BE 410 0.422 820 22.1 BE ABMW-04 05/14/2015 BE BE 1010 BE 1350 BE BE 3630 395 BE BE BE BE BE BE PZ-06 08/05/2015 BE 2.3 647 BE 5380 BE 18.7 3050 1110 BE BE 0.255 760 11.1 BE PZ-07 08/06/2015 4.0 BE 193 318 BE 138 1050 2140000 26300 2050 18000 12.6 12000 1880 3.45 PZ-08 08/05/2015 BE 2.85 124 BE BE BE 17.8 2390 2170 BE BE 1.31. 620 6.43 BE Prepared by: BER/SRW Checked by: CIS Notes: 0 - Bold highlighted concentration indicates exceedance of the 15A NCAC 02L Standard, Appendix 2, April 1, 2013. ug/I = microgram per liter mg/I = milligrams per liter S.U. = Standard Units * - Interim Maximum Allowable Concentrations (IMACs) of the 15A NCAC 02L Standard, Appendix 1, April, 1, 2013. BE = indicates concentration was below the 15A NCAC 02L Standard, April 1, 2013. P:\Duke Energy Progress.1026\103. Cape Fear Ash Basin GW Assessment\1.11 CSA Reporting\Tables\Table 7-8 2L Exceedances in Ash Pore Water.xlsx Page 1 of 1