HomeMy WebLinkAboutNC0025321_System Performance Annual Report 2021_2022013116 South Main Street · P.O. Box 100 · Waynesville, NC 28786 Phone (828) 452-2491 Fax (828)456-2000
Web Address: www.waynesvillenc.gov
This institution is an equal opportunity provider
Gary Caldwell, Mayor Robert W. Hites, Jr. Town Manager
Julia Freeman, Mayor Pro Tem William E. Cannon, Jr., Town Attorney
Clarence “Chuck” Dickson, Alderman
Jon Feichter, Alderman
Anthony Sutton, Alderman
Wastewater system performance report
January 1,2021-December 31,2021
Town of Waynesville Public Works Department
PO Box 100
Waynesville, NC 28786
(828) 456-3706
Town of Waynesville Wastewater Treatment Plant
Facility Name: Town of Waynesville Wastewater Treatment plant
Permit Number: NC0025321
Operator In Responsible Charge (ORC) Jeffery Evans WWTP Superintendent
(828) 713-7920 Jeffreyevans@waynesvillenc.Gov
Description of Treatment Process
The Town of Waynesville WWTP Is a 6 MGD activated sludge treatment plant and includes influent flow
measurement, bar screen, primary clarifiers, gravity sludge thickeners aeration, secondary clarifiers,
gaseous chlorine disinfection, and gaseous sulfur dioxide dichlorination. Solids are belt filter pressed and
hauled to the White Oak Landfill. The treated wastewater is discharged into the Pigeon River under
permit number NC0025321.
Summary of Violations During 202
The Town of Waynesville WWTP was issued several monthly NOVs. The NOVs were for TSS, BOD, Fecal
coliform, and DO. The NOVs received was due largely to the age of the plant and large rain events. We
are currently in the process of a nearly 30-million-dollar plant upgrade. This biggest culprit of failing the
permit limit is the secondary clarifiers are under sized and function poorly. The have-to-have extensive
maintenance due to the engineered design. Every effort is made to stay proactive of the maintenance,
however there are still numerous mechanical issue the must be handled reactively.
Month Avg. Daily Discharge (mgal/day) Monthly Flow (mgal) Minimum Flow Rate (mgd)
Maximum Flow Rate (mgd)
Jan-21 4.18 129.5 1.788 6.124
Feb-21 5.06 141.8 3.258 6.124
Mar-21 4.98 154.5 1.401 6.124
Apr-21 4.41 132.2 2.849 6.124
May-21 3.79 117.5 2.581 6.124
Jun-21 3.08 92.3 2.16 6.106
Jul-21 2.99 92.8 2.05 6.112
Aug-21 3.45 106.9 2.36 6.124
Sep-21 3.4 102.1 2.11 6.12
Oct-21 3.68 114 1.98 6.12
Nov-21 2.82 84.5 1.95 6.05
Dec-21 2.94 91.3 1.88 6.07
2021 Total Flow MGD 1359.4
2021 Yearly Gallons 1359400000
Public Notification
This report will be available for public viewing on the Town of Waynesville’s website
(WWW.townofwaynesvillenc.gov)
Certification
I certify under the penalty of law that this report is complete and accurate to the best of my
knowledge. I further certify that this report will be made available to the customers of the named
system
________________________
Jeff Stines
Public works director
Town of Waynesville Public Works Department