HomeMy WebLinkAboutWQ0005233_Application_20231106UNITED STATES MARINE CORPS
MARINE CORPS AIR STATION
POSTAL SERVICE CENTER BOX 8003
CHERRY POINT, NORTH CAROLINA 28533-0003
North Carolina Department of
Environment Quality
Division of Water Resources
Information Processing Center
1617 Mail Service Center
Raleigh, NC 27699-1617
IN REPLY REFER TO:
5090/071009
LN
November 6, 2023
SUBJECT: 2024 WASTEWATER IRRIGATION SYSTEM RENEWAL FOR WQ0005233
Marine Corps Air Station Cherry Point submits the enclosed renewal package for our
wastewater irrigation system, Permit No. WQ0005233 Enlisted Men's Barracks — Atlantic Airfield
Wastewater Treatment Facility. The submittal package includes one original copy of all required
documents. An electronic copy of the submittal package will be uploaded via website provided on
Form WWIS-R 02-21. The permit is scheduled to expire on June 30, 2024.
Should you have any questions, please contact Mr. Richard Weaver of the Environmental
Affairs Department at (252) 466-5917.
Sincerely,
v✓;' 4 �-tom--r
ANTHO Y FERENCE
Dep i� cilities Director
By direction of the
Commanding Officer
Enclosure: 1.2024 Permit Renewal Package for WQ0005233
2024 NON-DISHCARGE SYSTEM RENEWAL FOR W00005233
1, FORM WWIS-R 02-21
2. Current Permit
3. Attachment A — Site Maps
4. Attachment I — Compliance Schedules
*Attachments B-H, and J- L are N/A
WASTEWATER IRRIGATION SYSTEM - RENEWAL
(FORM: WWIS-R 02-21)
DWR
Dlvlsion of Water Resources
State of North Carolina
Department of Environmental Quality
Division of Water Resources
15A NCAC 02T .0500 — WASTEWATER IRRIGATION SYSTEM — RENEWAL
FORM: WWIS-R 02-21
Pursuant to 15A NCAC 02T .0107 h , if the application does not include all required information and the necessary supporting
documentation, the application shall be returned. The application and attachments shall be prepared in accordance with 15A
NCAC 02T .0100, 15A *TCAC 02T .0500, and Division Policies. For more information, visit the Water Quality Permitting
Section's Non -Discharge Branch website. The Applicant shall submit an electronic copy of the application and attachments
uploaded as a single Portable Document Format (PDF) file to https://edocs.deg nc.2ov/Forms/NonDischaree-Branch-Submittal-
Form-Ver2, or emailed to Non-Discharge.Reportsfa ncdenr.gov if less than 20 megabytes (MB).
SECTION I — APPLICANT INFORMATION
1.
Applicant: US MCAS Cherry Point
2.
Permit No.: WQ005233
3.
Signature authority: Anthony A. Ference
Phone number: (252) 466-3807 Office
Title: Deputy Facilities Director
Email: anthony.ference@usmc.mil
4.
Mailing address: USMC Cherry Point, Environmental Affairs
City: Cherry Point
Department, PSC Box 8006
State: NC Zip: 28533-0006
5.
Contact person: Richard Weaver
Primary phone number: (252) 466-5917 Office
Email: richard.weaver@usmc.mil
Secondary phone number: ( ) - Select
I SECTION II — FACILITY INFORMATION I
1. Physical address: Air Base Rd.
City: Atlantic
2. Treatment facility coordinates to the sixth decimal degree:
Latitude: 34.8829'
County: Carteret
State: NC
Parcel No.: N/A
Zip: 28511-
Longitude:-76.3538' Method: Conversion from state coordinate plane
SECTION III — FLOW INFORMATION
1.
Permitted flow: 5000 GPD (The maximum allowable flow based on what has been permitted)
2.
As -built flow: 5000 GPD (The maximum allowable flow based on what has been constructed)
3.
Average flow: 1462 GPD (The average of all reported flows on the previous calendar year's NDMRs)
4.
Hydraulic capacity: 29 % (Divide the average flow in Item 3 by the As -built flow in Item 2)
5.
Wastewater composition: Domestic: 100 % Industrial: % Stormwater: %
1 SECTION IV — BILLING INFORMATION
1. Billing address: USMC Cherry Point, Environmental Affairs Department, PSC Box 8006
City: Cherry Point State: NC Zip: 28533-0006
2. Verify the Applicant does not have any overdue annual fees:
hags://deq.nc. ov/about/divisions/water-resources/water-resources-permits/wq-eyavments
Pursuant to 15A NCAC 02T .0120(c), permits for renewing facilities shall not be granted if the Applicant or any affiliation has
an unpaid annual fee.
FORM: WWIS-R 02-21 Page 1 of 6
SECTION V — OPERATOR IN RESPONSIBLE CHARGE (ORC) INFORMATION
L ORC: Joshua Lee Meadows
Grade: SI Certification No.: 1013608
Mailing address: USMC Cherry Point, Environmental
Affairs Department, PSC Box 8006
City: Cherry Point
State: NC Zip: 28533-
Phone number: (252) 466-6787 Office
Email: joshua.meadows@usmc.mil
2. Back -Up ORC: Jeff Clayton
Grade: SI Certification No.: 998515
Mailing address: USMC Cherry Point, Environmental
Affairs Department, PSC Box 8006
City: Cherry Point
State: NC Zip: 28533-
Phone number: (252) 466-6787 Office
Email: jeffery.clayton@usmc.mil
SECTION VI — OPEN -ATMOSPHERE STRUCTURES
1. List all open -atmosphere treatment and storage structures associated with the renewing permit. Attach additional sheets if
necessary.
Type Parcel No. Volume al Liner Type Freeboard ft Latitude Longitude
YP (gal) YP () g�
Treatment/Storage 247,000 Full, synthetic 2 34.88360-76.35110
Treatment/Storage 78,000 Full, synthetic 2 34.88330-76.35080
Select Select 0- °
Select Select 0- °
SECTION VII — RELATED PERMITS
1. List all wastewater permits (i.e., sewer, collection system, NPDES, residuals) that have interactions with the renewing permit.
Attach additional sheets if necessary.
Permit Type Permit No. Relationship Type
Sewer WQ0044041 Discharging collection system
Select Select
Select Select
Select Select
SECTION VHI — MONITORING WELLS _�:]
1. List all groundwater monitoring wells associated with the renewing permit. Attach additional sheets if necessary.
Well Name Parcel No. Status Gradient Location Latitude Longitude
MW-3
Active
Cross gradient
On Review Boundary
34.8825750-76.3512020
MW-4
Active
Upgradient
Outside Compliance Boundary
34.883903'-76.351864'
MW-5
Active
Cross gradient
On Review Boundary
34.8814310
-76.3503440
MW-6
Active
Cross gradient
Inside Review Boundary
34.8830650
-76.3503160
Select
Select
Select
°
- °
Select
Select
Select
°
- °
Select
Select
Select
°
- °
Select
Select
Select
°
- °
Select
Select
Select
°
- °
Select
Select
Select
°
- °
Select
Select
Select
°
- °
FORM: WWIS-R 02-21 Page 2 of 6
SECTION IX — IRRIGATION FIELDS
1. List all irrigation fields associated with the renewing permit. Attach additional sheets if necessary.
Field County Parcel No. Deeded Owner Area Cover Crop Latitude Longitude
1 Carteret United States of America 0.50 Woodland 34.8817070 '-76.3507440
2
Carteret
Unites States of America
0.50
Woodland
34.8817800 1-76.3498600
3
Carteret
United States of America
0.75
Bermuda
34.8826150
-76.3504930
0
0
0 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
_ 0I
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Total Acreage:
1.75
FORM: WMS-R 02-21 Page 3 of 6
i
ATTACHMENT A — SITE MAP
Was the facility originally permitted or had a major modification issued after September 1, 2006?
® Yes — Pursuant to 15A NCAC 02T .0105(d}, submit a site map pursuant to the requirements in 15A NCAC 02T .05041d1. These
requirements are:
❑ A scaled map of the site with topographic contour intervals not exceeding 10 feet or 25 percent of total site relief and showing
all facility -related structures and fences within the wastewater treatment, storage, and irrigation areas.
❑ Soil mapping units shown on all irrigation sites.
❑ The location of all wells (including usage and construction details if available), streams (ephemeral, intermittent, and
perennial), springs, lakes, ponds, and other surface drainage features within 500 feet of all wastewater treatment, storage,
and irrigation sites.
❑ Delineation of the compliance and review boundaries per 15A NCAC 02L .0107 and .0108, and 15A NCAC 02T .0506(c}
if applicable.
❑ Setbacks as required by 15A NCAC 02T .0506.
❑ Site property boundaries within 500 feet of all wastewater treatment, storage, and irrigation sites.
❑ All habitable residences or places of public assembly within 500 feet of all treatment, storage, and irrigation sites.
❑ No — Skip Attachment A.
ATTACHMENT B — SIGNATURE AUTHORITY DELEGATION
Does the signature authority in Section I, Item 3 meet the requirements pursuant to 15A NCAC 02T .0106(bl?
® Yes — Skip Attachment B.
❑ No — Submit a delegation letter pursuant to 15A NCAC 02T .0106[c} authorizing the signature authority to sign.
I ATTACHMENT C — FLOW REDUCTION
Does the existing permit include an approved flow reduction?
❑ Yes — Submit a copy of the flow reduction approval letter, as well as the measured monthly average amount of wastewater flow
contributed per unit for the 12 months prior to permit renewal. If any of these monthly averages are within 20% of the approved
flow reduction value, the Permittee shall provide a reevaluation of the reduced flow value pursuant to the requirements in 15A
NCAC 02T .0114(f).
® No — Skip Attachment C.
I ATTACHMENT D — CERTIFICATE OF PUBLIC CONVENIENCE AND NECESSITY .MU I
Is the Applicant a Privately -Owned Public Utility?
❑ Yes — Pursuant to 15A NCAC 02T .0115(a)(1 }, submit the Certificate of Public Convenience and Necessity from the North
Carolina Utilities Commission demonstrating the Applicant is authorized to hold the utility franchise.
® No — Skip Attachment D.
ATTACHMENT E — OPERATIONAL AGREEMENT
Is the Applicant a Home/Property Owners' Association or Developer of Lots to be Sold?
❑ Yes (Home/Property Owners' Association) — Pursuant to 15A NCAC 02T .0115(a)(2), submit an executed Operational Agreement
(FORM: HOA). Pursuant to 15A NCAC 02T .0115(c), if the applicant is a legally formed Homeowners' or Property Owner's
Association, submit a copy of the Articles of Incorporation, Declarations, and By-laws.
❑ Yes (Developer of Lots to be Sold) — Pursuant to 15A NCAC 02T .0115(a)i21, submit an executed Operational A eement
ARM: DEW Pursuant to 15A NCAC 02T .0115 bl, if the applicant is a developer of lots to be sold, submit a copy of the
Articles of Incorporation, Declarations, and By-laws.
® No — Skip Attachment E.
FORM: WWIS-R 02-21 Page 4 of 6
ATTACHMENT F - DEMONSTRATION OF FUTURE WASTEWATER TREATMENT CAPACITIES
Is the applicant a municipality, county, sanitary district, or public utility?
❑ Yes - Proceed to the next question.
® No - Skip Attachment F.
Does the hydraulic capacity in Section III, Item 4 exceed 70%?
❑ Yes (the hydraulic capacity is greater than 70%, but less than 80%) - Pursuant to 15A NCAC 02T .0118(1), prior to exceeding
80 percent of the system's permitted hydraulic capacity (based on the average flow during the last calendar year), the permittee
shall submit an engineering evaluation of their future wastewater treatment, utilization, and disposal needs. This evaluation shall
outline plans for meeting future wastewater treatment, utilization, or disposal needs by either expansion of the existing system,
elimination or reduction of extraneous flows, or water conservation and shall include the source of funding for the improvements.
If expansion is not proposed or is proposed for a later date, a justification shall be made that wastewater treatment needs will be
met based on past growth records and future growth projections, and as appropriate, shall include conservation plans or other
measures to achieve waste flow reductions.
❑ Yes (the hydraulic capacity greater than 80%) - Proceed to the next question.
® No - Skip Attachment F.
If answered Yes above, does the hydraulic capacity in Section III, Item 4 exceed 80%?
❑ Yes (the hydraulic capacity is greater than 80%) - Pursuant to 15A NCAC 02T .0118(2}, prior to exceeding 90 percent of the
system's permitted hydraulic capacity (based on the average flow during the last calendar year), the permittee shall obtain all
permits needed for the expansion of the wastewater treatment, utilization, or disposal system and, if construction is needed,
submit final plans and specifications for expansion, including a construction schedule. If expansion is not proposed or is proposed
for a later date, a justification shall be made that wastewater treatment needs will be met based on past growth records and future
growth projections, and as appropriate, shall include conservation plans or other specific measures to achieve waste flow
reductions.
❑ No - Skip Attachment F.
ATTACHMENT G -- EASEMENT, ENCROACHMENT, AND LEASE AGREEMENTS
Does the Permittee own all of the land associated with the wastewater collection, treatment, conveyance, and irrigation system?
® Yes - Skip Attachment G.
❑ No - Pursuant to 15A NCAC 02T .0116 c , provide a copy of all easements, lease agreements, and encroachment agreements
allowing the Permittee to operate and maintain the wastewater collection, treatment, conveyance, and irrigation system on
property not owned by the Permittee.
ATTACHMENT H - AFFILIATIONS
Are the Permittee's affiliations of record correct? Check affiliations.
® Yes - Skip Attachment H.
❑ No - Provide the corrected affiliations and their contact information.
ATTACHMENT I - COMPLIANCE SCHEDULES
Does the existing permit include any Compliance Schedules? (See Section I of the most recently issued permit)
® Yes - Submit documentation that the compliance schedules have been met.
❑ No - Skip Attachment I.
ATTACHMENT J - CIVIL PENALTIES AND OUTSTANDING VIOL
Does the Permittee have any existing civil penalties or outstanding violations?
❑ Yes (civil penalties) - Submit payment for the civil penalty, or proof of remission request.
❑ Yes (violations) - Submit a copy of your response to the Notice of Violation.
® No - Skip Attachment J.
FORM: WWIS-R 02-21 Page 5 of 6
I ATTACHMENT K — INDUSTRIAL WASTEWATER
Does the wastewater composition in Section III, Item 5 include any industrial wastewater?
❑ Yes — Proceed to the next question.
® No — Skip Attachment K.
Has the nature of the industrial wastewater changed since the last permit issuance (i.e., changes in industrial process, introduction of
new materials or chemicals, etc.)?
❑ Yes — Provide a chemical analysis of the wastewater pursuant to the requirements in 15A NCAC 02T .0504(h). Provide an
overview of the manufacturing process; an inventory of all chemical and biological materials used in the manufacturing process;
and an overview of the cleaning and treatment methodology.
❑ No — Provide an overview of the manufacturing process; an inventory of all chemical and biological materials used in the
manufacturing process; and an overview of the cleaning and treatment methodology.
ATTACHMENT L — SETBACK WAIVERS I I
Does the existing permit include setback waivers?
❑ Yes — Pursuant to 15A NCAC 02T .0506[4), provide setbacks waivers that have been written, notarized, signed by all parties
involved, and recorded with the county Register of Deeds. Waivers involving the compliance boundary shall be in accordance
with 15A NCAC 02L .0107.
® No — Skip Attachment L.
I,
4 k.)
APPLICANT'S CERTIFICATION
R
D",P4d,v/i ' Co
(Signature auAiority's name as noted in Section I, Item 3)
_attest that this application
has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this
application package are not completed, and that if all required supporting information and attachments are not included, this
application package will be returned as incomplete. I further certify pursuant to 15A NCAC 02T .0120(b 1, that the applicant, or any
parent, subsidiary, or other affiliate of the applicant has: not been convicted of environmental crimes under; not previously abandoned
a wastewater treatment facility without properly closing the facility; not paid a civil penalty; not been compliant with any compliance
schedule in a permit, settlement agreement, or order; not paid an annual fee.
Note: The Applicant's Certification shall be signed pursuant to 15A NCAC 02T .0106 b . An alternate person may be delegated as
the signing official if a letter is provided pursuant to 15A NCAC 02T .0106(c). Pursuant to § 143-215.6A and § 143-215.6B, any
person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class
2 misdemeanor, which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation.
Signature:
Date: (� %76 v",Z (2 '?' 3
THE COMPLETED APPLICATION AND ATTACHMENTS SHALL BE SUBMITTED AS A SINGLE PDF FILE VIA:
Email:
Non-Discharge.Reoortsiia ncdenr.gov
Lasertiche Upload:
htt i)s://edocs.de(i.nc.2ov/Forms/NonDischarv-e-Branch-
Submittal-Form-Vert
FORM: WWIS-R 02-21 Page 6 of 6
CURRENT PERMIT
(WQ0005233)
ROY COOPER
Covemor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH
Director
NORTH CAROLINA
Eavlronmentat Quality
February 4, 2020
CHARLES E. SCHULZ - DEPUTY FACILITIES DIRECTOR
US MCAS CHERRY POINT
PSC Box 8006
CHERRY POINT, NORTH CAROLINA 28533-0006
Subject: Permit No. WQ0005233
Enlisted Men's Barracks —
Atlantic Airfield WWTF
Wastewater Irrigation System
Carteret County
Dear Mr. Schulz:
In accordance with your permit major modification request received September 3, 2019, and
subsequent additional information received December 16, 2019, we are forwarding herewith Permit No.
WQ0005233 dated February 4, 2020, to US MCAS Cherry Point for the construction and operation of the
permitted modifications, as well as the continued operation of the existing wastewater treatment and
irrigation facilities.
The following modifications to the subject permit are as follows: The existing dual 60 gallon per
minute (GPM) influent pump station is being replaced with new dual 80 GPM pump station.
This permit shall be effective from the date of issuance through June 30, 2024, shall void Permit
No. WQ0005233 issued April 15, 2019, and shall be subject to the conditions and limitations therein. The
Permittee shall submit a renewal application no later than January 2, 2024.
Please pay attention to the monitoring requirements listed Attachments A, B, and C for they may
differ from the previous permit issuance. Failure to establish an adequate system for collecting and
maintaining the required operational information shall result in future compliance problems.
The following permit conditions are new since the last permit issuance dated April 15, 2019;
➢ Condition I.1. — The Permittee shall submit an Engineering Certification for the permitted
modification.
➢ Condition 1.2. — This conditions requires that the Permittee notify the Wilmington Regional
Office, telephone number (910) 796-7215, at least two business days in advance of initial
operation of the modified facilities so that the Division can conduct a startup inspection.
➢ Condition II.12.c. — Setbacks for the new pump station have been listed.
➢ Condition Ill.17. — An automatically activated standby power source capable of powering the
80 GPM pump station shall be on site and operational at all times.
Q North Carolina Department of Environmental Quality Division of Water Resources
512 North Salisbury Street 1617 Mad Service Center Raleigh, North Carolina 27699-1617
s++om► 919.707.9000
Mr. Charles E. Schulz
February 4, 2020
Page 2 of 2
➢ Condition IV.9.c. —The maintenance log shall contain the date and results of power interruption
testing on alternate power supply.
If any parts, requirements, or limitations contained in this permit are unacceptable, the Permittee
has the right to request an adjudicatory hearing upon written request within 30 days following receipt of
this permit. This request shall be in the form of a written petition, conforming to Chapter 150B of the North
Carolina General Statutes, and filed with the Office of Administrative Hearings at 6714 Mail Service
Center, Raleigh, NC 27699-6714. Otherwise, this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this permit, please contact Erick Saunders at (919) 707-3659 or
erickson.saunders�—wncdenr.y .
Sincerely,
Daniel Smith, Director
" Division of Water Resources
cc: Carteret County Health Department (Electronic Copy)
Wilmington Regional Office, Water Quality Regional Operations Section (Electronic Copy)
J. Kevin Avolis, PE — Avolis Engineering, PA (Electronic Copy)
Beth Buffington — Protection and Enforcement Branch (Electronic Copy)
Laserfiche File (Electronic Copy)
Digital Permit Archive (Electronic Copy)
Central Files
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENTAL QUALITY
RALEIGH
WASTEWATER IRRIGATION SYSTEM PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
US MCAS Cherry Point
Carteret County
FOR THE
continued operation of a 5,000 gallon per day (GPD) wastewater treatment and irrigation facility consisting
of
continued operation and subsequent abandonment of the existing pump station consisting of: the existing
wet well and dual 60 gallon per minute (GPM) pumps; and all associated piping, valves, controls, and
appurtenances; the
construction and operation of a replacement pump station consisting of a new wet well and dual 80 GPM
submersible grinder pumps; and all associated piping, valves, controls, and appurtenances; and the
continued operation of, an existing 100 kilowatt (kW) generator that will serve as a standby power source
for the new pump station; a 247,000 gallon synthetically lined primary stabilization lagoon; a 78,000 gallon
synthetically lined polishing and storage pond; a tablet chlorinator;. dual irrigation pumps with flow
measuring and recording equipment; an emergency pump connection; a 1.75 acre spray irrigation area
consisting of three fields; and all associated piping, valves, controls, and appurtenances
to serve the Enlisted Men's Barracks — Atlantic Airfield WWTF, with no discharge of wastes to surface
waters, pursuant to the application received November 3, 2019, subsequent additional information received
December 16, 2019, and in conformity with the Division -approved plans and specifications considered a
part of this permit.
This permit shall be effective from the date of issuance through June 30, 2024, shall void Permit No.
WQ0005233 issued April 15, 2619, and shall be subject to the following conditions and limitations:
WQ0005233 Version 5.1 Shell Version 200201 Page I of 11
I. SCHEDULES
Upon completion of construction and prior to operation of the permitted modifications, the Permittee
shall submit an engineering certification from a North Carolina licensed Professional Engineer
certifying that the permitted facility has been constructed in accordance with G.S. 143-215.1,
Administrative Code Title 15A Subchapter 02T, this permit, and the Division -approved plans and
specifications. For phased and partially certified facilities, the Permittee shall retain the responsibility
to track further construction approved under this permit, and shall provide a final engineering
certification upon project completion. Mail the Engineering Certification to the Division of Water
Resources, Non -Discharge Branch, 1617 Mail Service Center, Raleigh, NC 27699-1617, or Non-
Discharge.Reports r ncdenr.gov. [15A NCAC 02T .0116(a)]
2. The Permittee shall notify the Wilmington Regional Office, telephone number (910) 796-7215, at least
two business days in advance of initial operation of the constructed facilities so that the Division can
conduct a startup inspection. [15A NCAC 02T .0108(b)(1)(B)]
3. The Permittee shall request renewal of this permit on Division -approved forms no later than January 2,
2024. [15A NCAC 02T .0105(b), 02T .0109]
H. PERFORMANCE STANDARDS
The Permittee shall maintain and operate the subject non -discharge facilities so there is no discharge to
surface waters, nor any contravention of groundwater or surface water standards. In the event the
facilities fail to perform satisfactorily, including the creation of nuisance conditions due to improper
operation and maintenance, or failure of the irrigation areas to assimilate the effluent, the Permittee
shall take immediate corrective actions, including Division required actions, such as the construction
of additional or replacement wastewater treatment or disposal facilities. [15A NCAC 02T
.0108(b)(1)(A)]
2. This permit shall not relieve the Permittee of their responsibility for damages to groundwater or surface
water resulting from the operation of this facility. [15A NCAC 02T .0108(b)(1)(A)]
3. Groundwater monitoring wells shall be constructed in accordance with 15A NCAC 02C .0108
(Standards of Construction for Wells Other than Water Supply), and any other jurisdictional laws and
regulations pertaining to well construction. [15A NCAC 02C .0108]
4. Effluent quality shall not exceed the limitations specified in Attachment A. [15A NCAC 02T .0505(b)]
5. Application rates, whether hydraulic, nutrient, or other pollutant, shall not exceed those specified in
Attachment B. [15A NCAC 02T .0505(c), 02T .0505(n)]
6. The Permittee shall connect the irrigation system to a rain or moisture sensor designed to prevent
irrigation during precipitation events or wet conditions. [15A NCAC 02T .0505(x)]
7. Wastewater irrigation fields permitted on or after December 30, 1983 have a compliance boundary that
is either 250 feet from the wastewater irrigation area, or 50 feet within the property boundary,
whichever is closest to the wastewater irrigation area. Any exceedance of groundwater standards at or
beyond the compliance boundary shall require corrective action. Division -approved relocation of the
compliance boundary shall be noted in Attachment B. Multiple contiguous properties under common
ownership and permitted for use as a disposal system shall be treated as a single property with regard
to determination of a compliance boundary. [15A NCAC 02L .0106(d)(2), 02L .0107(b), 02T .0105(h),
G.S. 143-215.1(i), G.S. 143-215.1(k)]
8. The review boundary is midway between the compliance boundary and the wastewater irrigation area.
Any exceedance of groundwater standards at or beyond the review boundary shall require preventative
action. [15A NCAC 02L .0106(d)(1), 02L .0108]
WQ0005233 Version 5.1 Shell Version 200201 Page 2 of 11
9. The Permittee shall apply for a permit modification to establish a new compliance boundary prior to
any sale or transfer of property affecting a compliance boundary (i.e., parcel subdivision). [ 15A NCAC
02L .0107(c)]
10. No wells, excluding Division -approved monitoring wells, shall be constructed within the compliance
boundary except as provided for in 15A NCAC 02L .0107(g). [15A NCAC 02L .0107]
11. Except as provided for in 15A NCAC 02L .0107(g), the Permittee shall ensure any landowner who is
not the Permittee and owns land within the compliance boundary shall execute and file with the Carteret
County Register of Deeds an easement running with the land containing the following items:
a. A notice of the permit and number or other description as allowed in 15A NCAC 02L .0107(f)(1);
b. Prohibits construction and operation of water supply wells within the compliance boundary; and
c. Reserves the right of the Permittee or the State to enter the property within the compliance boundary
for purposes related to the permit.
The Director may terminate the easement when its purpose has been fulfilled or is no longer needed.
[15A NCAC 02L .0107(f)]
12. The facilities herein were permitted per the following setbacks:
a. Fields 1 and 2 were modified July 12, 2010, and Field 3 was originally permitted on February 7,
2018. The setbacks for spray irrigation sites originally permitted or modified from September 1,
2006 to August 31, 2018 are as follows (all distances in feet):
i.
Each habitable residence or place of assembly under separate ownership:
4001
ii.
Each habitable residence or place of assembly owned by the Permittee:
200
iii.
Each private or public water supply source:
100
iv.
Surface waters:
100
v.
Groundwater lowering ditches:
100
vi.
Surface water diversions:
25
vii.
Each well with exception of monitoring wells:
100
viii.
Each property line:
1502
ix.
Top of slope of embankments or cuts of two feet or more in vertical height:
15
x.
Each water line:
10
xi. Subsurface groundwater lowering drainage systems: 100
xii. Each swimming pool: 100
xiii. Public right of way: 50
xiv. Nitrification field: 20
xv. Each building foundation or basement: 15
1 Habitable residences or places of assembly under separate ownership constructed after the
facilities herein were originally permitted or subsequently modified are exempt from this
setback.
s Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[15A NCAC 02T .0506(a), 02T .0506(e), 02T .0506(f)]
WQ0005233 Version 5.1 Shell Version 200201 Page 3 of 11
b. The storage and treatment units were originally permitted July 12, 2010. The setbacks for storage
and treatment units originally permitted or modified from September 1, 2006 to August 31, 2018
are as follows (all distances in feet):
L Each habitable residence or place of assembly under separate ownership: 1001
ii. Each private or public water supply source: 100
iii. Surface waters: 50
iv. Each well with exception of monitoring wells: 100
v. Each property line: 502
' Habitable residences or places of assembly under separate ownership constructed after the
facilities herein were originally permitted or subsequently modified are exempt from this
setback.
2 Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[15A NCAC 02T .0506(b), 02T .0506(e), 02T .0506(f)]
c. The 80 GPM influent pump station was originally permitted February 4, 2020. The setbacks for
storage and treatment units originally permitted or modified on or after September 1, 2018 are as
follows (all distances in feet):
L Each habitable residence or place of assembly under separate ownership: 100'
ii. Each private or public water supply source: 100
iii. Surface waters: 50
iv. Each well with exception of monitoring wells: 100
v. Each property line: 50,
' Habitable residences or places of assembly under separate ownership constructed after the
facilities herein were originally permitted or subsequently modified are exempt from this
setback.
2 Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[15A NCAC 02T .0506(b), 02T .0506(e), 02T .0506(f)]
M. OPERATION AND MAINTENANCE REQUIREMENTS
1. The Permittee shall operate and maintain the subject facilities as a non -discharge system. [15A NCAC
02T .0500]
2. The Permittee shall maintain an Operation and Maintenance Plan, which shall include operational
functions, maintenance schedules, safety measures, and a spill response plan. [15A NCAC 02T
.0507(a)]
3. Upon the Water Pollution Control System Operators Certification Commission's (WPCSOCC)
classification of the subject non -discharge facilities, the Permittee shall designate and employ a certified
operator in responsible charge (ORC), and one or more certified operators as back-up ORCs. The ORC
or their back-up shall operate and visit the facilities as required by the WPCSOCC. [15A NCAC 02T
.0117]
4. The Permittee shall maintain vegetative cover on the irrigation sites, such that crop health is optimal,
allows even effluent distribution, and allows inspection of the irrigation system. [15A NCAC 02T
.0507(b)]
WQ0005233 Version 5,1 Shell Version 200201 Page 4 of 11
5. The Permittee shall take measures to prevent effluent ponding in or runoff from the irrigation sites
listed in Attachment B. [15A NCAC 02T .0507(c)]
6. The Permittee shall not irrigate treated effluent during inclement weather, or when the soil is in a
condition that will cause ponding or runoff. [15A NCAC 02T .0505(x)]
7. Irrigation equipment shall be tested and calibrated once per permit cycle. [15A NCAC 02T .0507(d)]
8. Only treated effluent from the Enlisted Men's Barracks — Atlantic Airfield WWTF shall be irrigated on
the sites listed in Attachment B. [15A NCAC 02T .0501 ]
9. The Permittee shall not allow vehicles or heavy machinery on the irrigation area, except during
equipment installation or maintenance activities. [15A NCAC 02T .0507(e)]
10. The Permittee shall prohibit public access to the wastewater treatment, storage, and irrigation facilities.
[I 5A NCAC 02T .0505(q)]
11. The Permittee shall dispose or utilize generated residuals in a Division -approved manner. [15A NCAC
02T .0508, 02T .1100].
12. The Permittee shall not divert or bypass untreated or partially treated wastewater from the subject
facilities. [15A NCAC 02T .05050)]
13. Freeboard in the 247,000 gallon synthetically lined primary stabilization lagoon and the 78,000 gallon
synthetically lined polishing/storage pond shall not be less than two feet at anytime. [15A NCAC 02T
.0505(d)]
14. Gauges to monitor waste levels in the 247,000 gallon synthetically lined primary stabilization lagoon
and the 78,000 gallon synthetically lined polishing/storage pond shall be provided. These gauges shall
have readily visible permanent markings, at inch or tenth of a foot increments, indicating the following
elevations: maximum liquid level at the top of the temporary liquid storage volume; minimum liquid
level at the bottom of the temporary liquid storage volume; and the lowest point on top of the dam.
[15A NCAC 02T .0507(f)]
15. A protective vegetative cover shall be established and maintained on all berms, pipe runs, erosion
control areas, surface water diversions, and earthen embankments (i.e., outside toe of embankment to
maximum allowable temporary storage elevation on the inside of the embankment). Trees, shrubs, and
other woody vegetation shall not be allowed to grow on the earthen dikes or embankments. Earthen
embankments shall be kept mowed or otherwise controlled and accessible. [ 15A NCAC 02T .0507(g)]
16. Metering equipment shall be tested and calibrated annually. [15A NCAC 02T .0507(d)]
17. An automatically activated standby power source capable of powering the 80 GPM pump station shall
be on site and operational at all times. [15A NCAC 02T .0305(h)(B)]
WQ0005233 Version 5.1 Shell Version 200201 Page 5 of 11
IV. MONITORING AND REPORTING RE,., UIREMENTS
1. The Permittee shall conduct and report any Division required monitoring necessary to evaluate this
facility's impact on groundwater and surface water. [15A NCAC 02T .0108(c)]
2. A Division -certified laboratory shall conduct all analyses for the required effluent, groundwater, and
surface water parameters. [15A NCAC 02H .0800]
3. Flow through the treatment facility shall be continuously monitored, and daily flow values shall be
reported on Form NDMR. Facilities with a permitted flow less than 10,000 GPD may estimate their
flow from water usage records provided the water source is metered. [15A NCAC 02T .0105(k), 02T
.0108(c)]
4. The Permittee shall monitor the treated effluent at the frequencies and locations for the parameters
specified in Attachment A. [15A NCAC 02T .0108(c)]
5. The Permittee shall maintain records tracking the amount of effluent irrigated. These records shall
include the following information for each irrigation site listed in Attachment B:
a. Date of irrigation;
b. Volume of effluent irrigated;
c. Site irrigated;
d. Length of time site is irrigated;
e. Continuous weekly, monthly, and year-to-date hydraulic (inches/acre) loadings;
f. Continuous monthly and year-to-date loadings for any non -hydraulic parameter specifically
limited in Attachment B;
g. Weather conditions; and
h. Maintenance of cover crops.
[15ANCAC 02T .0108(c)]
6. Freeboard (i.e., waste level to the lowest embankment elevation) in the 247,000 gallon synthetically
lined primary stabilization lagoon and the 78,000 gallon synthetically lined polishing/storage pond shall
be measured to the nearest inch or tenth of a foot, and recorded weekly. Weekly freeboard records shall
be maintained for five years, and shall be made available to the Division upon request. [15A NCAC
02T .0108(c)]
7. Three copies of all monitoring data (as specified in Conditions IV.3. and IV.4.) on Form NDMR for
each PPI and three copies of all operation and disposal records (as specified in Conditions N.S. and
IV.6.) on Form NDAR-1 for every site in Attachment B shall be submitted on or before the last day of
the following month. If no activities occurred during the monitoring month, monitoring reports are still
required documenting the absence of the activity. All information shall be submitted to the following
address:
Division of Water Resources
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
[15A NCAC 02T .0105(1)]
WQ0005233 Version 5.1 Shell Version 200201 Page 6 of 11
The Permittee shall maintain a record of all residuals removed from this facility. This record shall be
maintained for five years, and shall be made available to the Division upon request. This record shall
include:
a. Name of the residuals hauler;
b. Non -Discharge permit number authorizing the residuals disposal, or a letter from a municipality
agreeing to accept the residuals;
c. Date the residuals were hauled; and
d. Volume of residuals removed.
[15A NCAC 02T .0508(b)]
9. A maintenance log shall be kept at this facility. This log shall be maintained for five years, and shall
be made available to the Division upon request. This log shall include:
a. Date of flow measurement device calibration;
b. Date of irrigation equipment calibration;
c. Date and results of power interruption testing on alternate power supply;
d. Visual observations of the plant and plant site; and
e. Record of preventative maintenance (e.g., changing of equipment, adjustments, testing, inspections
and cleanings, etc.).
[15A NCAC 02T .0507(h)]
10. Monitoring wells MW-3, MW-4, MW-5, and MW-6 shall be sampled at the frequencies and for the
parameters specified in Attachment C. All mapping. well construction forms. well abandonment forms
and monitoring data shall refer to the permit number and the well nomenclature as , rovide_d in
Attachment C and Figure 1. [15A NCAC 02T .0105(m)]
11. Two copies of the monitoring well sampling and analysis results shall be submitted on a Compliance
Monitoring Form (GW-59), along with attached copies of laboratory analyses, on or before the last
working day of the month following the sampling month. The Compliance Monitoring Form (GW-59)
shall include this permit number, the appropriate well identification number, and one GW-59a
certification form shall be submitted with each set of sampling results. All information shall be
submitted to the following address:
Division of Water Resources
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
[15A NCAC 02T .0105(m)]
12. An annual representative soils analysis (i.e., Standard Soil Fertility Analysis) shall be conducted on
each irrigation site listed in Attachment B. These results shall be maintained at the facility for five
years, and shall be made available to the Division upon request. Each Standard Soil Fertility Analysis
shall include the following parameters:
Acidity
Base Saturation (by calculation)
Calcium
Cation Exchange Capacity
Copper
[15A NCAC 02T .0108(c)]
Exchangeable Sodium Percentage
Magnesium
Manganese
Percent Humic Matter
pH
Phosphorus
Potassium
Sodium
Zinc
W00005233 Version 5.1 Shell Version 200201 Page 7 of 11
V.
13. Noncompliance Notification:
The Permittee shall report to the Wilmington Regional Office, telephone number (910) 796-7215,
within 24 hours of first knowledge of the following:
a. Treatment of wastes abnormal in quantity or characteristic, including the known passage of a
hazardous substance.
b. Any process unit failure (e.g., mechanical, electrical, etc.) rendering the facility incapable of
adequate wastewater treatment.
c. Any facility failure resulting in a discharge to surface waters.
d. Any time self -monitoring indicates the facility has gone out of compliance with its permit
limitations.
e. Ponding in or runoff from the irrigation sites.
Emergencies requiring reporting outside normal business hours shall call the Division's Emergency
Response personnel at telephone number (800) 662-7956, (800) 858-0368, or (919) 733-3300. All
noncompliance notifications shall file a written report to the Wilmington Regional Office within five
days of first knowledge of the occurrence, and this report shall outline the actions proposed or taken to
ensure the problem does not recur. [15A NCAC 02T .0108(b)(1)(A)]
1. The Permittee shall perform inspections and maintenance to ensure proper operation of the wastewater
treatment and irrigation facilities. [15A NCAC 02T .0507(i)]
2. The Permittee shall inspect the wastewater treatment and irrigation facilities to prevent malfunctions,
facility deterioration, and operator errors that may result in discharges of wastes to the environment,
threats to human health, or public nuisances. The Permittee shall maintain an inspection log that
includes the date and time of inspection, observations made, and maintenance, repairs, or corrective
actions taken. The Permittee shall maintain this inspection log for a period of five years from the date
of the inspection, and this log shall be made available to the Division upon request. [15A NCAC 02T
.0507(h), 02T .0507(i)]
3. Division authorized representatives may, upon presentation of credentials, enter and inspect any
property, premises, or place related to the wastewater treatment and irrigation facilities permitted herein
at any reasonable time for determining compliance with this permit. Division authorized
representatives may inspect or copy records maintained under the terms and conditions of this permit,
and may collect groundwater, surface water, or leachate samples. [G.S. 143-215.3(a)(2)]
WQ0005233 Version 5.1 Shell Version 200201 Page 8 of 11
VI. GENERAL CONDITIONS
1. Failure to comply with the conditions and limitations contained herein may subject the Permittee to a
Division enforcement action. [G.S. 143-215.6A, 143-215.613, 143-215.6C]
2. This permit is effective only with respect to the nature and volume of wastes described in the permit
application, and Division -approved plans and specifications. [G.S. 143-215.1(d)]
3. Unless specifically requested and approved in this permit, there are no variances to administrative codes
or general statutes governing the construction or operation of the facilities permitted herein. [15A
NCAC 02T .0105(n)]
4. The issuance of this permit does not exempt the Permittee from complying with all statutes, rules,
regulations, or ordinances that other jurisdictional government agencies (e.g., local, state, and federal)
may require. [15A NCAC 02T .0105(cx6)]
5. If the permitted facilities change ownership, or the Permittee changes their name, the Permittee shall
submit a permit modification request on Division -approved forms. The Permittee shall comply with
all terms and conditions of this permit until the permit is transferred to the successor -owner. [G.S. 143-
215.1(d3)]
6. The Pennittee shall retain a set of Division -approved plans and specifications for the life of the facilities
permitted herein. [15A NCAC 02T .0105(o)]
7. The Permittee shall maintain this permit until the proper closure of all facilities permitted herein, or
until the facilities permitted herein are permitted by another authority. [15A NCAC 02T .01050)]
8. This permit is subject to revocation or modification upon 60-day notice from the Division Director, in
whole or part for:
a. violation of any terms or conditions of this permit or Administrative Code Title 15A Subchapter
02T;
b. obtaining a permit by misrepresentation or failure to disclose all relevant facts;
c. the Permittee's refusal to allow authorized Department employees upon presentation of credentials:
i. to enter the Permittee's premises where a system is located or where any records are required
to be kept;
ii. to have access to any permit required documents and records;
iii. to inspect any monitoring equipment or method as required in this permit; or
iv. to sample any pollutants;
d. the Permittee's failure to pay the annual fee for administering and compliance monitoring; or
e. a Division determination that the conditions of this permit are in conflict with North Carolina
Administrative Code or General Statutes.
[I 5A NCAC 02T .0110]
WQ0005233 Version 5.1 Shell Version 200201 Page 9 of 11
4. Unless the Division Director grants a variance, expansion of the facilities permitted herein shall not
occur if any of the following apply:
a. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has been convicted of
environmental crimes under G.S. 143-215.6B, or under Federal law that would otherwise be
prosecuted under G.S. 143-215.6B, and all appeals of this conviction have been abandoned or
exhausted.
b. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has previously abandoned
a wastewater treatment facility without properly closing the facility.
c. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid a civil
penalty, and all appeals of this penalty have been abandoned or exhausted.
d. The Permittee or any parent, subsidiary, or other affiliate of the Permittee is currently not compliant
with any compliance schedule in a permit, settlement agreement, or order.
e. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid an annual
fee.
[ 15A NCAC 02T .0120(b), 02T .0120(d)]
10. This permit shall not be renewed if the Permittee or any affiliation has not paid the required annual fee.
[15A NCAC 02T .0120(c)]
Permit issued this the 41s day of February 2020
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
�4-
? DanSmith, Director
Division of Water Resources
By Authority of the Environmental Management Commission
Permit Number WQ0005233
WQ0005233 Version 5.1 Shell Version 200201 Page 10 of I
Permit No. WQ0005233 Wastewater Irrigation System
US MCAS Cherry Point February 4, 2020
Enlisted Men's Barracks — Atlantic Airfield WWTF Carteret County
ENGINEERING CERTIFICATION
❑ Partial ❑ Final
I, , as a duly licensed North Carolina Professional
Engineer, having ❑ periodically / ❑ fully observed the construction of the permitted facilities, do hereby
state to the best of my abilities that the facility was constructed in compliance with G.S. 143-215.1,
Administrative Code Title 15A Subchapter 02T, this permit, and the Division -approved plans and
specifications.
Documentation of any variation to this permit, and the Division -approved plans and specifications, is in the
attached as -built drawings.
Description of variations:
F
Professional Engineer's Name
Firm Name
Address
City State
Telephone Emsil
k
Zip Code
Seal, Signature, and Date
THE COMPLETED ENGINEERING CERTIFICATION, INCLUDING ALL SUPPORTING
DOCUMENTATION, SHALL BE SENT TO THE FOLLOWING ADDRESS:
NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY
DIVISION OF WATER RESOURCES
NON -DISCHARGE BRANCH
By U.S. Postal Service By Courier/Special Deliver
1617 MAIL SERVICE CENTER 512 N. SALISBURY ST.
RALEIGH, NORTH CAROLINA 27699-1617 RALEIGH, NORTH CAROLINA 27604
WQ0005233 Version 5.1 Shell Version 200201 Page 11 of 11
THIS PAGE BLANK
a
�
y
A
10
to
tool
E;
C7
C7
C�
C7
C�7
of
C�7
010
�
w
D
a
o•
?
�
�
�"
�
+
>'
�
7"
y
�+
"
,�F.
eee���
W.
$off
O
m
M
M
m
m
m
M
M
M
M
M
e
a
e
C
1
Fr A
~ C
p y
N
R
i
O
i p y
b
p
C� izz
d
�
G
E
PA. e�
E E C7 0
E
E
E 7
_�
CT
cd N
O
I`
ti y
w N
00
VA
� � � °
o
v
vow
p•' �° •v � o
F
cd
p
O d y O
as
i�
a
w 19,
•�
Wm
o
U U U W r-Li Z
Z
Z
•�-+ R- Pr un m
y
3
C
V enkO
R U c
S
v
r
N
tn
h
C.
N CD N
CD
pO O � O M k
%o m to
0 o c n o
1
f r.i Cy
0
fn
M
N
O
r
�-�
a
w
a
x
N
2
�
k
�
�
B
q
q
A
§
#
k
2
m
k
$ §
(
7
7
r
i f j 3 j
&�
CD
§ 5 CD
a
)
$
#
k
in
§
/
/
/
/
§
&
R
t
2
R
E
00
k
§
&
/
/
/
k
;
q
k§
S
§
A
S
/
�
a
_
2
k
�
<
�
W
a
x
F
i o o
++ a O
y ACL
n F
O Or.
t0
0 .ri 1••� V ems+ (^+
a 42 A
a •p U r G
00
` 5 =o
�✓
> ai G
O EltA
A •� ��v
•v N C
aUi � � y m �' o � � °' �' •n
o
bA > 00
b0 y �� (� N Y
3 c g� b ono 0
o ra o
o T m ow o o c
14 O g
;: u m � � o � � m o• o •moo 'o aAi � o
.0 o Ei on $
>' T U
�::.a �F� � � � o Tad
'ZO �d �p � CD pa�•� Ob � � �� T�� O
p a+ ti •aOa C pC �' ->oa�Oi �
W x oO ^
..
o L:'s° o
em =.4o Vq
�! ill ,a�3 T c caa p
i�Uoau 0T
3
,-,
eo 3^ UU
�' ^'oo"n o � � o0 0 o a gi q^ a.a °'� ��•d �
•� Oy > Q .2
C
b0 rnrnWWd dFFa Tn UO
x °' °' •s oo �' F ' o[ moo+
M a V ✓ (� p 1�1 "C� C% CSS U h N ►�I CS �C
^. N
U
A
A
1
406-
ATTACHMENT A - SITE MAPS
W00005233 Atlantic Airfield WWTF - Site Map
CUI
Legend
Building N
B Well
Fence
• Wastewater Utility Node - Pumping Station W E
Wastewater Utility Segment
Road Centerline
MilitaryReservation Boundary S
SCALE 1:1,369
0.035 0.0175 0 0.035
r rr Kilometers
0.035 0.0175 0 0.035
Miles
ELEVATION IN FEET
20 FOOT CONTOUR INTERVAL
CONTACT
u I
INFORMATION
Prepared 10116/2023
b Timoth S. Ward
V
CUI - Controlled Unclassified Information
Controlled by OASD Sustainment
�P
y y
Controlled Category; CTI
GIS Analyst / BLDG 87 FAMD
f aDistribution Authorized to DOD and U.S.
MCAS-Cherry Point, NC
DoD Contractors only; 10/1612023
timothy.Ward.Ctr@usmc.mil
Other requests for this document shall be
252 466d783
Referred to OASD(S), DISDI Program
POC; osd.pentagon.ousdati.mbx.disdi-helpdesk@mail.mil
PROJECTION, DATUM AND
REFERENCE GRID STATEMENT
FOR REFERENCE ONLY
NOT TO BE USED FOR TARGETING OR NAVIGATION
SPHEROID ..........:..........
GEODETIC REFERENCE SYSTEM 1980
Disclaimer.
Although every effort has been made to ensure the accuracy of information,
PROJECTION ..................
UNIVERSAL TRANSVERSE MERCATOR
errors and conditions originating from the physical sources used to develop the
VERTICAL DATUM ......
NORTH AMERICAN VERTICAL DATUM 1988
database may be reflected in the data suppled. The requestor must be aware
HORIZONTAL DATUM
................ NORTH AMERICAN DATUM 1983
of data conditions and ultimately bear responsibility for the appropriate use
CONTROLLED BY ........
USGS, NATIONAL GEODETIC SURVEY POINTS
of the Information with respect to possible errors, original map scale, collection
GRID ..................................
1000 - METER UTM ZONE 18
methodology, currency of data, and other specific conditions to certain data.
GRATICULE
HALF MINUTE LATITUDE TICS
This Information does not depict all possible resources. Field verification of
................
-LONGITUDE
all data Is required for site -specific projects. This Information is deemed
reliable, but not guaranteed.
WQ0005233 Atlantic Airfield WWTF - Review and' Compliance Boundaries
CONTACT INFORMATION �Z V V I
Prepared1011612023 o CUl- ControlledUndaesifiedInformation
b Timothy S. Ward �r Controlled by DASD Sustainment
Legend y y X Controlled Category; CTI
GIS Analyst! BLDG 87 FAMD 1 Distribution Authorized to DOD and U.S.
C Well MCAS-Cherry Point NC DoD Contractors only; 10n62023
Building r requests for
document shall
N timothy.ward.etr@usmc.mil D Relert d to OAStarr , DISDI Program
be
— D.mb .chc Program
125_Ft. Review Boundary (262) 466.4783 POC; osd.penfegon.ousdatl.mbx.6sdMelpdesk@mai.mil
SCALE 1:1,555
250_Ft. Com liance_Bounda PROJECTION, DATUM AND FOR REFERENCE ONLY
P ry NOT TO BE USED FOR TARGETING OR NAVIGATION
a.0a o.Oz o o.oa REFERENCE GRID STATEMENT
Fence Kilometers Disclaimer.
0.aa 0.02 0 0.0a SPHEROID . .. ............... GEODETIC REFERENCE SYSTEM 1980
500 Ft._Com liance Bounda Although every anon has been made a ensure the accuracy of o develop
t
P — ry - ' ---- � Miles PROJECTION ..................UNIVERSAL TRANSVERSE MERCATOR errors end conditions originating from Me physical sources used to develop Me
Wastewater Utility Segment VERTICAL DATUM ...... NORTH AMERICAN VERTICAL DATUM 1988 database may be reflected in the data supplied. The requester must be aware
ELEVATION IN FEET HORIZONTAL DATUM ................ NORTH AMERICANDATUM 1983 of data conifilions and ultimately bear responsibility for the appropriate me
Road Centerline CONTROLLED BY ........ USGS, NATIONAL GEODETIC SURVEY POINTS of the infarmetion with respect to possible errors, original map scale, collection
GRID .........................■ 20 FOOT CONTOUR INTERVAL .... 1000 - METER UTM ZONE 18 methodology, currency of data, and other specific conditions to certain data.
a
MilltaryReservatlon Boundary ' ' ' ' ' ' ' ' This information does not depict all possible resources. Field verification of
..
�....r .. .. - GRATICULE ................HALF MINUTE LATITUDE -LONGITUDE TICS all date Is required for sibs -specific projects. This Information Is deemed
reliable, but not guaranteed.
WQ0005233 Atlantic Airfield WWTF Contours
76 : "WW
CUI
SCALE 1:8,384
0.2 0.1 0 02
e u u Kilometer=
0.2 0.1 0 0
Miles
20 FOOT CONTOUR INTERVAL
76°20'0W
CONTACT INFORMATION
Prepared 10/17/2023
by Timothy S. Ward
GIS Analyst J BLDG 87 FAMD
MCAS-Cherry Point, NC
Umothy.ward.ctr@usmc.mil
(252)466-4783
PROJECTION, DATUM AND
REFERENCE GRID STATEMENT
[�
C U
+
CUI - Controlled Unclassified Information
Controlled by OASD Sustainment
controlled Category; CTI
to DOD and U.S.
DisDoD
Con
oCorhtractors only; 101172023
Other requests for tlhis document shall be
Retarred to OASD(S), DISDI Program
POC;
osd.pentagon.ousda6.mbx.dlsdMelpdesk@mai.mil
FOR REFERENCE ONLY
NOT TO BE USED FOR TARGETING OR NAVIGATION
SPHEROID..
GEODETIC REFERENCE SYSTEM 1980
Declaimer:
every effort has been made to ensure the
Pore
PROJECTION ..................
UNIVERSAL TRANSVERSE MERCATOR
andugh
t,
anon end conditions originating from the physical sources used to develop the
sourcesd to develop
used
VERTICAL DATUM ......
NORTH AMERICAN VERTICAL DATUM 1988
database may be reflected in the data supplied. The requeetor must be aware
HORIZONTAL DATUM ................
NORTH AMERICAN DATUM 1983
of data conditions and ultimately, bear responsibility for the appropriate use
CONTROLLED BY ........
USGS, NATIONAL GEODETIC SURVEY POINTS
of the Information with respect to possible errors, original map scale, collection
GRID ..........................methodology,
1000 -METER UTM ZONE 18
currency ofdats, and other specific conditions to certain data.
GRATICULE ................
.......
HALF MINUTE LATITUDE -LONGITUDE TICS
This Information does not depict all possible resources. Field vetficaton of
all date is required for siteapecific projects. This information is deemed
reliable, but not guaranteed.
cUl
-�' Cut- Controlled Unclassified Information .
Coritroledla Cate Sy;CTI M
�y controled caeegory; cn
g Distribution Authorized to DOD and U.S.
DoD Contractors only; 1011=023
Other requests for this document shall be
Referred to OASD(S), DISDI Program
POC; osdAentagon.Quad- d.mbx.dlsdi-helpdesk@mal.mll
FOR REFERENCE ONLY
NOT TO BE USED FOR TARGETING OR NAVIGATION
Disclaimer:
Although every effort has been made to ensure the accuracy of Information,
errors and conditions originating from the physical sources used to develop the
database may be reflected In the data suppled. The requestor must be aware
of data condition and ultimately bear responsibility for the appropriate use
of the information with respect to passible mom, original map scale, collection
methodology, currency of data, and other specific conditions to certain data.
This information does not depict all possible resources. Field verification of
all data is required for she-apecifw projects. This Information Is deemed
reliable• but not guaranteed.
W00005233 Atlantic Airfield WWTF - Irrigation Fields and Soils
SCALE 1:1,371
0.035 0.0175 0 0.035
r Rrbmvters
0.035 0.0175 0 0.035
6nififin=jifimm=6fisimmmmomminniml Miles
ELEVATION IN FEET
20 FOOT CONTOUR INTERVAL
Property Boundary line
CONTACT INFORMATION
Prepared 1011812023
by Timothy S. Ward
GIS Analyst I BLDG 87 FAMD
MCAS-Cherry Point, NC
timothyward.ctr@usmc.mil
(252) 466-4783
PROJECTION, DATUM AND
REFERENCE GRID STATEMENT
SPHEROID .. .................
GEODETIC REFERENCE SYSTEM 1980
PROJECTION ..................
UNIVERSAL TRANSVERSE MERCATOR
VERTICAL DATUM ......
NORTH AMERICAN VERTICAL DATUM 1988
HORIZONTAL DATUM ................
NORTH AMERICAN DATUM 1983
CONTROLLED BY ........
USGS, NATIONAL GEODETIC SURVEY POINTS
GRID ..................................
1000- METER UTM ZONE 18
GRATICULE . .... .......
HALF MINUTE LATITUDE -LONGITUDE TICS
vU1
Legend
Q Irrigation Field
Building
Well
Fence
Wastewater Utility Node - Pumping
Wastewater Utility Segment
Road Centerline
MilitaryReservation Boundary
Soils-MUSYM
<all other values>
USYM
AaA
Ag
Apt
AuB
BH
Be
Bf
Bn
ByB
' CH
CL
CT
Cd
CnB
CO
CrB
Cu
DA
DO
De
Dm
Du
Fr
GOA
HB
KuB
LF
i
Ln
Lu
Ly
MA
Mc
Mn
Mu
Nc
Nd
Ne
Nh
NoA
NoB
On
PO
Pa
Ra
Ro
Se
f StA
Tm
TO
WaB
WS
WUB
ATTACHEMENT I — COMPLIANCE SCHEDULES
The current permitted modification under Permit number WQ0044041 is still under construction.
Once completed the Fast Track Sewer Engineering Certification and the Sewer Engineering
Certification Checklist will be provided. Permit WQ0044041 is attached for reference.
DocuSign Envelope ID: 68C431A2-6293-409D-BF65-136416A3BD7B
A yTITF
ROY COOPER'
T
GOve MIDI'
ELIZABETH BISER
Secretory
RICHARD E. ROGERS, JR,
NORTH CAROLINA
EnWronmental Quality
Director
January 18, 2023
Anthony Ference, Deputy Facilities Director
US MCAS Cherry Point
4223 Access Road, PSC Box 8006
Cherry Point, NC 28533
Subject: Permit No. k4NWMUllMP
US MCAS Cherry Point
P246 Range Operations Pump Station and Sewer
Wastewater Collection System Extension
Carteret County
Dear Mr. Ference:
In accordance with your application received December 2, 2022, and revised application received
December 21, 2022, we are forwarding herewith Permit No. WQ0044041 dated January 18, 2023, to the
US MCAS Cherry Point (Permittee) for the construction and operation upon certification of the subject
wastewater collection system extension. This permit shall be effective from the date of issuance until
rescinded and shall be subject to the conditions and limitations as specified therein. This cover letter shall
be considered a part of this permit and is therefore incorporated therein by reference.
Please pay particular attention to the following conditions contained within this permit:
Special Conditions:
Condition 1.1: Each pump station shall be clearly and conspicuously posted using a weatherproof sign
with the address, a pump station identifying name/number, 24-Hour Emergency
telephone number, and name of the owner/operator of the sewer system/pump station
and instructions to call the number in the event of alarm activation or other emergency.
Simplex pump stations or vacuum sewer pits serving a single-family residence may have
a placard or sticker without the address placed on the control panel in lieu of a sign. [15A
NCAC 02T .0305(h)(2)]
Standard Conditions:
Condition 11.1: This permit shall not be automatically transferable; a request must be made and
approved.
Condition 11.4: Requires that the wastewater collection facilities be properly operated and maintained
in accordance with 15A NCAC 2T .0403 or any individual system -wide collection system
permit issued to the Permittee.
Division of Water Resources — Wilmington Regional Office
127 Cardinal Drive Extension, Wilmington, North Carolina 28405
Phone: 910-796-7215\ Internet: www.deg.nc.gov
DocuSign Envelope ID: 68C431A2-6293-409D-BF65-136416A3BD7B
Condition 11.7: Upon completion of construction and prior to operation of these permitted facilities, the
completed Engineering Certification form with checklist attached to this permit shall be
submitted with the required supporting documents to the address provided on the form.
Permit modifications are required for any changes resulting in non-compliance with
this permit, regulations, or the Minimum Design Criteria. [15A NCAC 02T.01161
Condition 11.13: If the Perm ittee/Appl ica nt holds a system -side collection system operation,
maintenance and management permit (WQCS-prefix) from the Division, then the
following applies: For all newly constructed, modified and rehabilitated pump stations,
all equipment and components shall be sealed within a corrosion -resistant coating or
encasement to the extent practicable and equivalent to the minimum design criteria
unless the permittee can demonstrate it is not practicable or another form of corrosion
resistance is employed. [15A NCAC 02T .0108 (b)]
It shall be responsibility of the Permittee to ensure that the as -constructed project meets the appropriate
design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina
General Statute §143-215.6A through §143-215.6C, construction of additional or replacement
wastewater collection facilities, and/or referral of the North Carolina -licensed Professional Engineer to
the licensing board.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to
request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This
request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General
Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC
27699-6714. Unless such demands are made, this permit shall be final and binding.
If you need additional information concerning this matter, please contact Tyler Benson at (910) 796-7215
or via e-mail at T 1er.Bensona ncdenr.pov.
Sincerely,
CDocuSipTned by:
-TO.K 11�wt'YI�On.
7F141E73W3456...
Tom Tharrington, Assistant Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
Cc: Robin Austin, Catlin Engineers and Scientist (Laserfiche info via email)
Upload to Laserfiche
Permit No. WQ0044041 January 18, 2023 Page 2 of 9
DocuSign Envelope ID: 68C431A2-6293-409D-BF65-136416A3BD7B
J_
NORTH CAROLINA
FnrlronmenfolQualify
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted to the
US MCAS CHERRY POINT
CARTERET COUNTY
for the construction and operation upon certification of a 140—gallon per minute pump station with duplex
grinder pumps, on -site audible and visual high water alarms, telemetry, and a permanent generator with
automatic transfer switch, as well as approximately 524 linear feet of 3-inch force main to serve the P246
Range Operations Center with 17-employees and 3-visitors (719 gallons per day (34.2 gpd/unit)) as part
of the P246 Range Operations Pump Station and Sewer project, and the discharge of 719 gallons per day
of collected domestic wastewater into the US MCAS Cherry Point existing sewerage system, pursuant to
the application received December 2, 2022, and revised application received December 21, 2022, and in
conformity with 15A NCAC 2T; the Division's Gravity Sewer Minimum Design Criteria adopted February
12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump
Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting data subsequently
filed and approved by the Department of Environmental Quality and considered a part of this permit.
This permit shall be effective from the date of issuance until rescinded and shall be subject to the specified
conditions and limitations contained therein.
Permit Number: WQ0044041
Issued Today: January 18, 2023
CDxu3igned by:
To4- T1+..r•nI'll
7F141E731361`3456...
Tom Tharrington, Assistant Regional Supervisor
Wilmington Regional Office
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
By Authority of the Director and The Environmental Management Commission
Permit No. WQ0044041 January 18, 2023 Page 3 of 9
DocuSign Envelope ID: 68C431A2-6293-409D-BF65-136416A3BD7B
SUPPLEMENT TO PERMIT COVER SHEET
US MCAS CHERRY POINT is hereby authorized to:
Construct, and then operate upon certification the aforementioned wastewater collection extension. The
sewage and wastewater collected by this system shall be treated in the Atlantic Airfield Wastewater
Treatment Facility in accordance with Permit Number WQ0005233.
Permitting of this project does not constitute an acceptance of any part of the project that does not meet
15A NCAC 2T, the Division of Water Resources' (Division) Gravity Sewer Minimum Design Criteria adopted
February 12, 1996 as applicable; and the Division's Minimum Design Criteria for the Fast -Track Permitting
of Pump Stations and Force Mains adopted June 1, 2000 as applicable, unless specifically mentioned
herein. Division approval is based on acceptance of the certification provided by a North Carolina -licensed
Professional Engineer in the application. It shall be the Permittee's responsibility to ensure that the as -
constructed project meets the appropriate design criteria and rules.
Construction and operation is contingent upon compliance with the Standard Conditions and any Special
Conditions identified below.
I. SPECIAL CONDITIONS
1. Each pump station shall be clearly and conspicuously posted using a weatherproof sign with the
address, a pump station identifying name/number, 24-Hour Emergency telephone number, and name
of the owner/operator of the sewer system/pump station and instructions to call the number in the
event of alarm activation or other emergency. Simplex pump stations or vacuum sewer pits serving a
single-family residence may have a placard or sticker without the address placed on the control panel
in lieu of a sign. [15A NCAC 02T .0305(h)(2)]
11. STANDARD CONDITIONS
I. This permit shall not be transferable. In the event there is a desire for the wastewater collection
facilities to change ownership, or there is a name change of the Permittee, a formal permit request
shall be submitted to the Division accompanied by documentation from the parties involved, and
other supporting materials as may be appropriate. The approval of this request shall be considered
on its merits and may or may not be approved. [15A NCAC 02T.0104; G.S 143-215.1(d3)]
2. This permit shall become voidable unless the wastewater collection facilities are constructed in
accordance with the conditions of this permit; 15A NCAC 2T; the Division's Gravity Sewer Minimum
Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for
the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and
other supporting materials unless specifically mentioned herein. [15A NCAC 02T.01101
3. This permit shall be effective only with respect to the nature and volume of wastes described in the
application and other supporting data. [15A NCAC 02T .0110]
4. The wastewater collection facilities shall be properly maintained and operated at all times. The
Permittee shall maintain -compliance with an individual system -wide collection system permit for the
Permit No. WQ0044041 January 18, 2023 Page 4 of 9
DocuSign Envelope ID: 68C431A2-6293-409D-BF65-136416A3BD7B
operation and maintenance of these facilities as required by 15A NCAC 2T .0403. If an individual
permit is not required, the following performance criteria shall be met: [15A NCAC 02T .0108(b)]
The sewer system shall be effectively maintained and operated at all times to prevent discharge
to land or surface waters, and to prevent any contravention of groundwater standards or surface
water standards.
b. A map of the sewer system shall be developed and shall be actively maintained.
c. An operation and maintenance plan including pump station inspection frequency, preventative
maintenance schedule, spare parts inventory and overflow response has been developed and
implemented.
Pump stations that are not connected to a telemetry system shall be inspected every day (i.e. 365
days per year). Pump stations that are connected to a telemetry system shall be inspected at
least once per week.
e. High -priority sewer lines shall be inspected at least once per every six -months and inspections are
documented.
f. A general observation of the entire sewer system shall be conducted at least once per year.
g. Overflows and bypasses shall be reported to the appropriate Division regional office in accordance
with 15A NCAC 2B .0506(a), and public notice shall be provided as required by North Carolina
General Statute §143-215.1C.
h. A Grease Control Program is in place as follows:
For public owned collection systems, the Grease Control Program shall include at least
biannual distribution of educational materials for both commercial and residential users and
the legal means to require grease interceptors at existing establishments. The plan shall also
include legal means for inspections of the grease interceptors, enforcement for violators and
the legal means to control grease entering the system from other public and private satellite
sewer systems.
2. For privately owned collection systems, the Grease Control Program shall include at least bi-
annual distribution of grease education materials to users of the collection system by the
permittee or its representative.
3. Grease education materials shall be distributed more often than required in Parts (1) and (2)
of this Subparagraph if necessary to prevent grease -related sanitary sewer overflows.
Right-of-ways and easements shall be maintained in the full easement width for personnel and
equipment accessibility.
j. Documentation shall be kept for Subparagraphs (a) through (i) of this Rule for a minimum of three
years with exception of the map, which shall be maintained for the life of the system.
5. Noncom fiance Notification:
The Permittee shall report by telephone to a water resources staff member at the Wilmington
Regional Office, telephone number (910) 796-7215, as soon as possible, but in no case more than 24
hours or on the next working day, following the occurrence or first knowledge of the occurrence of
either of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable
of adequate wastewater transport, such as mechanical or electrical failures of pumps, line
blockage or breakage, etc.; or
Permit No. WQ0044041 January 18, 2023 Page 5 of 9
DocuSign Envelope ID: 68C431A2-6293-409D-BF65-136416A3BD76
b. Any SSO and/or spillover 1,000 gallons; or
c. Any 550 and/or spill, regardless of volume, that reaches surface water
Voice mail messages or faxed information is permissible, but this shall not be considered as the initial
verbal report. Overflows and spills occurring outside normal business hours may also be reported to
the Division of Emergency Management at telephone number (800) 858-0368 or (919) 733-3300.
Persons reporting any of the above occurrences shall file a spill report by completing and submitting
Part I of Form CS-SSO (or the most current Division approved form) within five days following first
knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to
ensure that the problem does not recur. Part II of Form CS-SSO (or the most current Division approved
form) can also be completed to show that the SSO was beyond control. [G.S. 143-215.1C(a1)]
6. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to
interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater
to the surface waters of the State. [15A NCAC 02T.0108(b)]
Upon completion of construction and prior to operation of these permitted facilities, the completed
Engineering Certification form with checklist attached to this permit shall be submitted with the
required supporting documents to the address provided on the form. A complete certification is one
where the form is fully executed and the supporting documents are provided as applicable. Any
wastewater flow made tributary to the wastewater collection system extension prior to completion
of this Engineer's Certification shall be considered a violation of the permit and shall subject the
Permittee to appropriate enforcement actions.
If the permit is issued to a private entity with an Operational Agreement, then a copy of the Articles
of Incorporation, Declarations/Covenants/Restrictions, and Bylaws that have been appropriately
filed with the applicable County's Register of Deeds office shall be submitted with the certification.
A complete certification is one where the form is fully executed and the supporting documents are
provided as applicable. Supporting documentation shall include the following:
a. One copy of the project construction record drawings (plan & profile views of sewer lines & force
mains) of the wastewater collection system extension. Final record drawings should be clear on
the plans or in accepted electronic format and are defined as the design drawings that are marked
up or annotated with after construction information and show required buffers, separation
distances, material changes, etc.
b. One copy of the supporting applicable design calculations including pipe and pump sizing, velocity,
pump cycle times, and level control settings, pump station buoyancy, wet well storage, surge
protection, detention time in the wet well, and force main, ability to flush low points in force
mains with a pump cycle, and downstream sewer capacity analysis. If a portable power source or
pump is dedicated to multiple stations, an evaluation of all the pump stations' storage capacities
and the rotation schedule of the portable power source or pump, include travel timeframes, shall
be provided.
c. Changes to the project that do not result in non-compliance with this permit, regulations, or the
Minimum Design Criteria should be clearly identified on the record drawings, on the certification
in the space provided, or in written summary form.
Prior to Certification (Final or Partial): Permit modifications are required for any changes resulting in
non-compliance with this permit (includinp, pipe length changes of 10% or greater by type & size
increased flow, um station design capacity design increases of 5% or greater, and increases in the
number/type of connections), regulations, or the Minimum Design Criteria. Requested modifications
Permit No. WQ0044041 January 18, 2023 Page 6 of 9
DocuSign Envelope ID: 68C431A2-6293-409D-BF65-136416A3BD7B
or variances to the Minimum Design Criteria will be reviewed on a case -by -case basis and each on its
own merit. Please note that variances to the Minimum Design Criteria should be requested and
approved during the permitting process prior to construction. After -construction requests are
discouraged by the Division and may not be approved, thus requiring replacement or repair prior to
certification & activation. [15A NCAC 02T .0116]
8. Gravity sewers installed greaterthan ten percent belowthe minimum required slope perthe Division's
Gravity Sewer Minimum Design Criteria shall not be acceptable and shall not be certified until
corrected. If there is an unforeseen obstacle in the field where all viable solutions have been
examined, a slope variance can be requested from the Division with firm supporting documentation.
This shall be done through a permit modification with fee. Such variance requests will be evaluated
on a case -by -case basis. Resolution of such request shall be evident prior to completing and submitting
the construction certification. [ 15A NCAC 02T.0105(n)]
9. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of
the wastewater collection facilities. [15A NCAC 02T .0116]
10. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2T; the Division's
Gravity Sewer Design Criteria adopted February 12,1996 as applicable; the Division's Minimum Design
Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as
applicable; and other supporting materials may subject the Permittee to an enforcement action by
the Division, in accordance with North Carolina General Statutes §143-215.6A through §143-215.6C,
construction of additional or replacement wastewater collection facilities, and/or referral of the North
Carolina -licensed Professional Engineer to the licensing board. [15A NCAC 02T .0104; 15A NCAC 02T
.0108(b-c)]
11. In the event that the wastewater collection facilities fail to perform satisfactorily, including the
creation of nuisance conditions, the Permittee shall take immediate corrective action, including those
as may be required by this Division, such as the construction of additional or replacement facilities.
[15A NCAC 02T .0110; 15A NCAC 02T .0108(b)]
12. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes,
rules, regulations, or ordinances that may be imposed by the Division any other Federal, State, or Local
government agencies which have jurisdiction or obtaining other permits which may be required by
the Division or any other Federal, State, of Local government agencies. [G.S. 143-215.1(b)]
13. If the Permittee/Applicant holds a system -side collection system operation, maintenance and
management permit (WQCS-prefix) from the Division, then the following applies: For all newly
constructed, modified and rehabilitated pump stations, all equipment and components shall be sealed
within a corrosion -resistant coating or encasement to the extent practicable and equivalent to the
minimum design criteria unless the permittee can demonstrate it is not practicable or another form
of corrosion resistance is employed. [15A NCAC 02T .0108 (b)]
Permit No. WQ0044041 January 18, 2023 Page 7 of 9
DocuSign Envelope ID: 68C431A2-6293-409D-BF65-136416A3BD7B
FAST TRACK SEWER ENGINEERING CERTIFICATION
PERMITTEE: US MCAS Cherry Point
PERMIT #: WQ0044041
PROJECT: P246 Range Operations Pump Station and Sewer
ISSUE DATE: January 18, 2023
COUNTY: Carteret
This project shall not be considered complete nor allowed to operate in accordance with Condition 7 of this permit until
the Division has received this Certification and all required supporting documentation. Consequently, it should be
submitted in a manner that documents the Division's receipt. Send the required documentation to the Wilmington
Regional Supervisor, Water Quality Section at the address at the bottom.
The Permittee is responsible for tracking all partial certifications up until a final certification is received. Certifications
shall include Phase/Section-covered, line size & len the installed and listing of lots connections to be served and pump
station desi n if a licable. A Final Certification shall be a complete set of record drawings and design calculations
regardless of whether partials have been submitted.
PERMITTEE'S CERTIFICATION
I, the undersigned agent for the Permittee, hereby state that this project has been constructed pursuant to the applicable
standards & requirements, the Professional Engineer below has provided applicable design/construction information to
the Permittee, and the Permittee is prepared to operate & maintain the wastewater collection system permitted herein
or portions thereof.
Printed Name, Title
Signature
ENGINEERS CERTIFICATION
Date
as a duly registered Professional Engineer in the State of North Carolina, having been
authorized to ( periodically, ❑ weekly, LJ full time) observe the construction of the project name and location as
referenced above for the above Permittee hereby state that, to the best of my abilities, due care and diligence was used
in the observation of the following construction:
a 14 allon per minute nUMV station with du lex arinder pumps, on -site audible and visual high water alarms
telemet and a ermanent 4renerator with automatic trans er switch as well as approximately S24 linear feet of 3-
inch force main to serve the P246 Ran e Operations Center with 17-em to ees and 3-visitors 1719 1117allonsper day 34.2
d dav; unit 11 1 as art of the P246 Rance Operations Pump Station and Sewer ProJect and the discharge ot 719 gallons per
such that the construction was observed to be built in compliance of this permit; 15A NCAC 2T; the Division of Water
Resources' (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's
Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as
applicable; and other supporting materials.
North Carolina Professional Engineer's Seal w/signature & date
❑ Final ❑ Partial (include description)
Certification Comments/Qualifiers (attach if necessary):
NC DWR — Water Quality Regional Operations Section
Wilmington Regional Office
i
Er
• ...... I
127 Cardinal Drive Extension Wilmington, NC 28405
Phone: 910-796-7215 FAX:910-350-2004
DocuSign Envelope ID: 68C431A2-6293-409D-BF65-136416A3BD7B
SEWER ENGINEERING CERTIFICATION CHECKLIST
To be completed by the certifying engineer prior to operation of the permitted sewers, per 15A NCAC 02T.0116.
Certifying Engineer: _ _
Certification Review Date:
Project Name:
WQ00
Project County:
1) Has permittee information changed since the permit was issued (or last modified): change of mailing address,
change of ownership, transfer from developer to HOA/POA, etc. ❑ Yes ❑ No
• If yes, please provide either a change of ownership form or new contact information. Note that transfer of
permits from the developer to the HOA/POA must occur with the first certification.
2) Have the as -built drawings have been signed, sealed, and dated by an N.C. PE? ❑ Yes ❑ No
3) Final Engineering certification? ❑ Yes ❑ No
• If Partial Engineering certification, provide detailed narrative including what is being certified in the current
phase, what was previously certified (if applicable), and what is left to be certified.
4) Adequate information related to sewer lines: ❑ Yes ❑ No ❑ N/A
• Three feet minimum cover has been provided for all sewers unless ferrous pipe was installed.
• Minimum diameters for gravity sewers are 8-inches for public lines and 6-inches for private lines.
• Manholes have been installed: At the end of each line, at all changes in grade, size, or alignment, at all
intersections, and at distances not greater than 425 feet; minimum diameter shall be 4 feet (48-inches).
5) Adequate information related to pump stations: ❑ Yes ❑ No ❑ N/A
• Ensure power reliability option was selected per 15A NCAC 02T.0305(h).
6) Was project construction completed in accordance with all of the following: ❑ Yes ❑ No ❑ N/A
• 15A NCAC 02T, Minimum Design Criteria MDC for the permitting of Gravity Sewers latest version), and MDC
for the Permitting of Pump Stations and Force Mains (latest version)?
If not, a variance approval is required in accordance with 15A NCAC QZL.0105tbl prior to certification and operation.
• Contact the Central Office to discuss the variance to determine a course of action.
• Applicant must submit two copies of the variance request form, plans, specifications, calculations, and any other
pertinent information to the Central Office (one hard copy, one digital copy).
• The central office will review the variance request, and if approvable, specific language regarding the variance
will be incorporated into the permit, either via a special condition or a supplementary letter. A copy of the
reissued permit with variance language or the variance letter must be maintained with the original documents.
7) Does the project contains high priority lines (15A NCAC 02T .0402(2))? ❑ Yes ❑ No
• If yes, ensure that the permit already contains the necessary condition related to high priority lines 15A NCAC
02T.0403 (a)(5). If the permit does not include this language, the Fast Track reviewer will reissue the permit with
the appropriate language.
8) Are Permit modifications are required for any changes resulting in non-compliance with this permit (including pipe
length difference of 10% or greater, change in flow, pump station design capacity design change of 5% or greater, and
change in the number/type of connections)? ❑ Yes ❑ No
• If yes, a permit modification request must be submitted to the appropriate Regional Office, and a modified
permit with revised certification must be issued prior to certification and operation.