HomeMy WebLinkAboutWQ0015052_NOV-2023-LM-0091_20231031ROY COOPER
Gwernor
ELIZABETH S. BISER
secmtary
RICHARD E. ROGERS, JR.
Director
9A7Z o-
i
x
NORTH CAROLINA
Environmental Quality
Certified Mail # 7019 2970 0001 3140 2408
Return Receipt Requested
October 31, 2023
William Galen Freed
Enviro-Tech of North Carolina Inc
113 Duck Woods Dr
Southern Shores, NC 27949
SUBJECT: NOTICE OF VIOLATION & INTENT TO ASSESS CIVIL PENALTY
Tracking Number: NOV-2023-LM-0091
Permit No. WQ0015052
Village at Ocean Hill WWTP
Currituck County
Dear Mr. Freed:
A review of the January 2023 Non -Discharge Monitoring Report (NDMR) and Non -Discharge Analysis Report
(NDAR1) for the subject facility revealed the violation(s) indicated below:
Limit Exceedance Violation(s):
Sample
Limit
Reported
Location Parameter Date
Value
Value
Type of Violation
002 BOD, 5-Day (20 Deg. C) 1/26/2023
15
17
Daily Maximum Exceeded
(00310)
002 Nitrogen, Ammonia Total (as 1/26/2023
6
26.7
Daily Maximum Exceeded
N) (00610)
002 Nitrogen, Ammonia Total (as 1/30/2023
6
9.5
Daily Maximum Exceeded
N) (00610)
002 BOD, 5-Day (20 Deg. C) 1/31/2023
10
12.5
Monthly Average Exceeded
(00310)
002 Nitrogen, Ammonia Total (as 1/31/2023
4
18.1
Monthly Average Exceeded
N) (00610)
ni1v eni.Dn � Narth Ceraunaoeparrme,fem�imnmenteiQuantyIOlrbnofWarerRes..—
Wg hmneg 'mgRbnd Office I943 Wshington Square Mall I Wshi�m ,North Carding22b69
7
252.946.6461
Monitorina Violation(s):
Sample
Location
Parameter Date
Monitoring
Frequency
Type of Violation
002
Turbidity, HCH Turbidimiter (00076) 1/1/2023
Continuous
Frequency Violation
002
Turbidity, HCH Turbidimiter (00076) 1/7/2023
Continuous
Frequency Violation
002
Turbidity, HCH Turbidimiter (00076) 1/8/2023
Continuous
Frequency Violation
002
Turbidity, HCH Turbidimiter (00076) 1/14/2023
Continuous
Frequency Violation
002
Turbidity, HCH Turbidimiter (00076) 1/15/2023
Continuous
Frequency Violation
002
Turbidity, HCH Turbidimiter (00076) 1/21/2023
Continuous
Frequency Violation
002
Turbidity, HCH Turbidimiter (00076) 1/22/2023
Continuous
Frequency Violation
002
Turbidity, HCH Turbidimiter (00076) 1/28/2023
Continuous
Frequency Violation
002
Turbidity, HCH Turbidimiter (00076) 1/29/2023
Continuous
Frequency Violation
Reporting Violation(s):
Sample
Location Parameter
Date Type of Violation
5/2/2023 Field -Site Missing
A Notice of Violation/Intent to Issue Civil Penalty is being issued for the noted violation of North Carolina General
Statute (G.S.) 143-215.1 and the facility's Non -discharge Permit. Pursuant to G.S. 143-215.6A, a civil penalty of
not more than twenty-five thousand dollars ($25,000.00) may be assessed against any person who violates or
fails to act in accordance with the terms, conditions, or requirements of any permit issued pursuant to G.S.
143-215.1.
If you wish to provide additional information regarding the noted violation, request technical assistance, or
discuss overall compliance please respond in writing within ten (10) business days after receipt of this Notice. A
review of your response will be considered along with any information provided on the submitted Monitoring
Report(s). You will then be notified of any civil penalties that may be assessed regarding the violations. If no
response is received in this Office within the 10-day period, a civil penalty assessment may be
prepared.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law. If the violations are of a continuing nature, not related to operation and/or maintenance problems,
and you anticipate remedial construction activities, then you may wish to consider applying for a Special Order by
Consent.
DEQ� NorthCaroiinaOeparrmentofEnvlronmenta3Qualltyl�IVlsbnoFWaterResources
W-hing—Regional Office 194 Washing 5qu Mall l Wa h,�t No hCarolina 27M9
�-.•�^ �^����� 252.946b481
Reminder: Pursuant to Permit Condition 11 in Section IV, the Permittee is required to verbally notify the Regional
Office as soon as possible, not to exceed 24 hours, from first knowledge of any non-compliance at
the facility including limit violations, bypasses of, or failure of a treatment unit. A written report may
be required within 5 days if directed by Division staff. Prior notice should be given for anticipated or
potential problems due to planned maintenance activities, taking units off-line, etc.
If you have any questions concerning this matter or to apply for an SOC, please contact Sarah Toppen of the
Washington Regional Office at 252-946-6481.
Cc: Laserfiche
Sincerely,
Plow TR.4.4
Robert Tankard, Assistant Regional Supervisor
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
..�.R D ��� North Carolina Oepartmerrt ofEmlra.mental Qualky OlNslan Water Resources
weshmgton Req�onal ORire 1943 Washington Square Mal II wa,hitgmn, Nor[h Grdina 21E69
252.94bh481