HomeMy WebLinkAboutNC0088731_ Draft Factsheet_20231023NCDEQ / DWR / NPDES
EXPEDITED FACT SHEET - NPDES PERMIT RENEWAL
NPDES Permit NC0088731
Sara Bassett / Compliance & Expedited Permitting Unit / sara.bassett@deq.nc.gov / October 2023
FACILITY INFORMATION
Applicant/Facility Name Certainteed Gypsum NC, Inc., Certainteed Gypsum Wallboard
WWTP
Applicant Address 921 Shore Road, Semora Rd NC, 27343
Facility Physical
Address/Mailing Address Same as applicant address
Permitted Flow (MGD) 0.005 MGD
Type of Waste 100% Domestic, < 1 MGD
Facility Class PCNC County Person
Permit Status Renewal Regional Office Raleigh
STREAM CHARACTERISTICS
Receiving Stream Hyco Lake Stream
Classification WS-V, B
Stream Segment 22-58-(0.5) Outfall Lat. 36.4872N
7Q10 - Summer (cfs) - Outfall Long. 79.0678W
7Q10 - Winter (cfs) - Drainage basin Roanoke
30Q2 (cfs) - Subbasin 03-02-05
Average Flow (cfs) - HUC 03010104
303(d) List No
BASIC INFO FOR EXPEDITED PERMIT RENEWAL
Does permit need Daily Max NH3 limits? Already present
Does permit need TRC limits/footnote? Already present
Does permit have toxicity testing? No
Does permit have any Special Conditions? No
Does permit have instream monitoring? No
New expiration date: November 30, 2028
FACILITY SUMMARY
The CertainTeed Gypsum Wallboard WWTP is a minor municipal facility (flow<1 MGD) that
receives 100% domestic waste. The design capacity for the treatment system is 0.005 MGD and
the permitted flow is 0.005 MGD. The facility consists of the following components:
an extended-aeration package plant that includes
• inlet bar screen
• aerated-flow equalization basin (1667 gallon)
• aeration tank (5,000 gallon)
• clarifier (833 gallon)
• sludge-handling tank (1125 gallon)
• dual (2) blowers, and
a tertiary rapid-sand filter system that includes
• two (2) each 3.5 ft x 3.5 ft sand filter cells
• clear-well tank (560 gallon)
• backwash surge tank (560 gallon)
• tablet chlorinator
• chlorine-contact chamber (208 gallon)
• tablet dechlorinator
• dual (2) blowers
• dual (2) discharge pumps
backup power generator
RENEWAL SUMMARY
This renewal contains the following changes:
• Updated Section A. (2) to reflect current federal requirements for Electronic Reporting of
Discharge Monitoring Reports.
• Added facility grade to box (PCNC)
COMPLIANCE HISTORY
15 enforcements, mostly for limit violations since 2017
COMMENTS ON DRAFT PERMIT