FACILITY INFORMATION
Applicant/Facility Name Yadkin County Board of Education (Mitchell T Long, ORC)
East Bend Elementary School WWTP
Applicant Address/Mailing
Address 121 Washington Street, Yadkinville, NC 27055
Facility Physical Address 205 School Street, East Bend, NC 27018
Permitted Flow (MGD) 0.007 MGD
Type of Waste 100% Domestic, < 1 MGD
Facility Class WW-1 County Yadkin
Permit Status Renewal Regional Office WSRO
STREAM CHARACTERISTICS
Receiving Stream Logan Creek Stream
Classification C
Stream Segment 12-83-2-(0.3) Outfall Lat. 36° 10' 54" N
7Q10 - Summer (cfs) 1.6 Outfall Long. 80° 32' 14" W
7Q10 - Winter (cfs) 2.9 Drainage basin Yadkin-Pee Dee River Basin
30Q2 (cfs) 3.9 Subbasin 03-07-02
Average Flow (cfs) 11.6 HUC 030401011201
IWC (%) 0.67% (summer) /
0.37% (winter) 303(d) List No
BASIC INFO FOR EXPEDITED PERMIT RENEWAL
Does permit need Daily Max NH3 limits? No
Does permit need TRC limits/footnote? No – Already present in permit.
Does permit have toxicity testing? No – not a complex wastestream
Does permit have any Special Conditions? Nutrient Reopener for High Rock Lake
Does permit have instream monitoring? No
New expiration date: Nov 30, 2028
FACILITY SUMMARY
The Yadkin County Board of Education operates a 100% domestic wastewater treatment plant for an
estimated 250 residents, that sends wastewater to the East Bend Elementary School WWTP nearby. The
East Bend Elementary School WWTP is a minor facility (flow < 1 MGD) with a design capacity and
permitted wastewater discharge of 0.007 MGD. The original NPDES permit for this facility was issued in
March 1982. This facility utilizes the following treatment components:
⬧ Grease trap
⬧ Septic tank
⬧ Dosing tank with filters
⬧ Recirculating surface sand filter with dual recirculation pumps
⬧ Ultraviolet unit for disinfection
⬧ Chlorine disinfection & dechlorination equipment [backup system]
⬧ Dual effluent pumps
Fact Sheet for Permit Renewal
Sept 2023 - NPDES Permit NC0029611 - Page 2
RENEWAL SUMMARY
This renewal contains the following changes:
• Updated eDMR language for electronic data submission in Part I. A. (3).
COMPLIANCE HISTORY
East Bend Elementary School WWTP has not had an enforcement since 2007. The facility has been issued
one NOD for a pH limit violation in 2019, and two NOVs for fecal coliform limit violations in 2022 and
2023, since the permit was originally issued in May 2019. Most recent inspection (May 2023) showed the
facility to be in compliance.