September 18, 2023
Subject: Compliance Evaluation Inspection
Countryside MHP
NPDES WW Permit No. NCO056201
Randolph County
Dear Mr. Fairman:
On August 22, 2023, Division of Water Resources (DWR) Winston-Salem Regional Office (WSRO)
staff Jesse Barnes conducted a routine compliance evaluation inspection at the Countryside NC
MHP WWTP in reference to NPDES permit NC0056201. ORC Paul Smith was present during the
inspection. A review of the subject permit, records, treatment components, receiving waters, and
plant operations and maintenance was completed. This review reflected compliance with the
subject permit.
Items of Concern
1. NPDES permit NCO056201 became effective February 1, 2019 and will expire at midnight
on January 31, 2024. At the time of this inspection, a new permit renewal application had
not yet been received from the permittee.
2. The facility has been upgraded since the last permit issuance, with approval from DWR.
The system components listed on the supplement to permit cover sheet are no longer
accurate. Please ensure the system components are listed and described accurately in the
upcoming permit renewal application.
3. Recent monitoring reports have listed the certified laboratory used as "NC00030", which is
no longer valid. Please list the most up-to-date names and NC lab certification numbers for
all field and non -field labs used to report permit -required parameters.
.19
Mr. Smith stated that the septic tank sludge depths are regularly measured with a sludge
judge and facility owners are notified once sludge depths exceed 3 feet, but at times the
septic tanks have not been pumped frequently enough. Recent permit violations of BOD
and fecal coliform limits may be attributed to excessive sludge depths in the septic tanks,
which could be ameliorated with more frequent pumping. Some surface grease and solids
were observed in the septic tanks during the inspection.
Please be aware that the Division may take enforcement action against any permittee who fails
to comply with any requirement of their permit. Pursuant to NC General Statute (NCGS) 143-
D North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
Moan caaouNn 336.776.9800
oep.m.m or em.v.me.� Qualm
215.6A, a civil penalty of not more than twenty-five thousand dollars ($25,000.00) may be
assessed against any person who violates or fails to act in accordance with the terms, conditions,
or requirements of any permit issued pursuant to G.S. 143-215.1.
If you have any questions or concerns, please do not hesitate to contact Jesse Barnes by phone
at 336-776-9701, or by email at jesse.barnes@deq.nc.gov.
Sincerely,
DocuSigned by:
OD2D3CE3F1 B7456_.
Jennifer F. Graznak, Assistant Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Attachments:
1. Water Compliance Inspection Report, NCO056201
REQ� North Carolina Department ofEnvironmental Quality I Division ofWater Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Raleigh, North Carolina 27105
NORTH CAROLINA 336.776.9800
naparMeM of EmironmanW 9uallly
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO056201 111 121 23/08/22 I17 18 LC] I 19 I s I 201
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I ni I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:20AM 23/08/22
19/02/01
Countryside MHP
3425 Roy Farlow Rd
Exit Time/Date
Permit Expiration Date
Sophia NC 27350
11:20AM 23/08/22
24/01/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Paul Matthew Smith/ORCH
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Eric Fairman,W Bloomfield Acres LLC Royal Oak MI
48067H248-399-7755/2483999975 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Jesse Barnes DWR/WSRO WQ/336-776-9701/
9/15/2023
EY"41797473D3194ED...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
by:
FDocuSigned
.if"DwR/WSRo 336-776-9695 9/18/2023
'--- OD2D3CE3F 197456_.
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO056201 I11 12I 23/08/22 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On August 22, 2023, Division of Water Resources (DWR) Winston-Salem Regional Office (WSRO)
staff Jesse Barnes conducted a routine compliance evaluation inspection at the Countryside NC MHP
WWTP in reference to NPDES permit NC0056201. ORC Paul Smith was present during the
inspection. A review of the subject permit, records, treatment components, receiving waters, and plant
operations and maintenance was completed. This review reflected compliance with the subject permit.
The following items of concern were noted:
1. NPDES permit NC0056201 became effective February 1, 2019 and will expire at midnight on
January 31, 2024. At the time of this inspection, a new permit renewal application had not yet been
received from the permittee.
2. The facility has been upgraded since the last permit issuance, with approval from DWR. The
system components listed on the supplement to permit cover sheet are no longer accurate. Please
ensure the system components are listed and described accurately in the upcoming permit renewal
application.
3. Recent monitoring reports have listed the certified laboratory used as "NC00030", which is no
longer valid. Please list the most up-to-date names and NC lab certification numbers for all field and
non -field labs used to report permit -required parameters.
4. Mr. Smith stated that the septic tank sludge depths are regularly measured with a sludge judge
and facility owners are notified once sludge depths exceed 3 feet, but at times the septic tanks have
not been pumped frequently enough. Recent permit violations of BOD and fecal coliform limits may
be attributed to excessive sludge depths in the septic tanks, which could be ameliorated with more
frequent pumping. Some surface grease and solids were observed in the septic tanks during the
inspection.
Other observations:
There are no special conditions for the subject permit. Access to the plant site is restricted to the
general public by a locked metal chain -link fence. The inspector was granted access to all areas for
inspection.
All required records are stored off site and maintained by AQWA. All requested records were
available to review electronically via tablet and appeared to be complete.
Field parameters of pH, temperature, and dissolved oxygen are performed by Mr. Smith under NC
certified field lab # 5169 — Smith Industries. Bench and calibration data records for field parameters
performed during July 2023 were reviewed and appeared to be complete. Non -field parameters are
performed by Pace Analytical LLC, NC certified lab # 633. Non -field parameter data are stored off site
at AQWA offices and were available for review electronically via tablet during the inspection.
Laboratory data sheets and chains -of -custody for July 2023 were reviewed and appeared to be
complete.
The system components listed on the permit are no longer accurate, as the old activated sludge
package plant has been demolished and completely removed. The new Orenco AdvanTex AX-Max
Treatment System is now in place and operational. The current system consists of two 10,000 gallon
septic tanks that provide primary treatment, one 10,000 gallon equalization tank, two Orenco
AdvanTex AX-Max treatment units with textile biological media that can be operated in parallel or in
series, and a Sanitron UV disinfection system, along with all pumps, valves, piping, controls, and
other appurtenances to complete the treatment system.
Page#
Permit: NCO056201
Inspection Date: 08/22/2023
Owner -Facility: Countryside MHP
Inspection Type: Compliance Evaluation
The equalization tank and its pumps appeared to be in good condition and operation properly during
the inspection. Float controls and alarms were not tested duringthe inspection.
The facility utilizes two Orenco AdvanTex AX-Max treatment units for biological treatment. After leaving
the septic tanks and EQ tank, wastewater is passed through textile biological media in the AX-Max
units and recirculated through the units multiple times before flowing to the UV disinfection system.
The AX-Max treatment units appeared to be operating properly during the inspection.
The facility disinfects with a Sanitron UV light system consisting of two bulbs operating in a series with
independent quartz sleeves, housings, and manual scrubbers for each bulb. The UV disinfection
system appeared to be operating properly during the inspection. Sufficient backup bulbs were
available on site during the inspection.
Flow is monitored and reported with an in -line analog effluent flow meter. The flow meter is replaced
annually with a newly -calibrated meter. Records of new flow meter calibration and installation were
not available during the inspection, but Mr. Smith stated that records are maintained at AQWA offices
and available upon request.
The facility has an automatic propane generator that is automatically tested every week and can
power the entire treatment system. The primary power source is not interrupted during automatic
tests of the generator.
Effluent samples are grabbed from a spigot located after the UV disinfection system. Effluent and
in -stream sampling appeared to have been conducted in compliance with the subject permit.
Page#
Permit: NCO056201 Owner -Facility: Countryside MHP
Inspection Date: 08/22/2023 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
■
❑
❑
application?
Is the facility as described in the permit?
❑
■
❑
❑
# Are there any special conditions for the permit?
❑
■
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: NPDES permit NCO056201 became effective February 1, 2019 and will expire at
midnight on January 31, 2024. At the time of this inspection, a new permit renewal
application had not vet been received from the permittee.
The facility has been upgraded since the last permit issuance, with approval from
DWR. The system components listed on the supplement to permit cover sheet are no
longer accurate. Please ensure the system components are listed and described
accurately in the upcoming permit renewal application.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
❑
■
Is the chain -of -custody complete?
❑
❑
❑
■
Dates, times and location of sampling
❑
Name of individual performing the sampling
❑
Results of analysis and calibration
❑
Dates of analysis
❑
Name of person performing analyses
❑
Transported COCs
❑
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Is a copy of the current NPDES permit available on site?
■
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
■
❑
Page# 4
Permit: NCO056201
Inspection Date: 08/22/2023
Record Keeping
Comment:
Owner -Facility: Countryside MHP
Inspection Type: Compliance Evaluation
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
Comment: Recent monitoring reports have listed the certified laboratory used as "NC00030",
which is no longer valid. Please list the most up-to-date names and NC lab certification
numbers for all field and non -field labs used to report permit -required parameters.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Septic Tank
Yes
No
NA NE
(If pumps are used) Is an audible and visual alarm operational?
❑
❑
❑
Is septic tank pumped on a schedule?
■
❑
❑
❑
Are pumps or syphons operating properly?
0
❑
❑
❑
Are high and low water alarms operating properly?
❑
❑
❑
Comment: Mr. Smith stated that the septic tank sludqe depths are reqularlv measured with a
sludge judge and facility owners are notified once sludge depths exceed 3 feet, but at
times the septic tanks have not been pumped frequently enough. Recent permit
violations of BOD and fecal coliform limits may be attributed to excessive sludge depths
in the septic tanks, which could be ameliorated with more frequent pumping. Some
surface grease and solids were observed in the septic tanks during the inspection.
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Yes No NA NE
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 5
Permit: NC0056201 Owner -Facility: Countryside MHP
Inspection Date: 08/22/2023 Inspection Type: Compliance Evaluation
Equalization Basins Yes No NA NE
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
❑
❑
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment:
Disinfection - UV
Yes
No
NA
NE
Are extra UV bulbs available on site?
0
❑
❑
❑
Are UV bulbs clean?
❑
❑
❑
Is UV intensity adequate?
■
❑
❑
❑
Is transmittance at or above designed level?
❑
❑
❑
■
Is there a backup system on site?
0
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment:
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment:
Standby Power
Yes
No
NA
NE
Is automatically activated standby power available?
0
❑
❑
❑
Is the generator tested by interrupting primary power source?
❑
■
❑
❑
Is the generator tested under load?
0
❑
❑
❑
Was generator tested & operational during the inspection?
❑
❑
❑
■
Do the generator(s) have adequate capacity to operate the entire wastewater site?
0
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up
❑
❑
❑
power?
Is the generator fuel level monitored?
0
❑
❑
❑
Comment: The facility has an automatic propane generator that is automatically tested every
week and can power the entire treatment system. The primary power source is not
interrupted during automatic tests of the generator.
Page# 6
Permit: NCO056201 Owner -Facility: Countryside MHP
Inspection Date: 08/22/2023 Inspection Type: Compliance Evaluation
Standby Power Yes No NA NE
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
❑
❑
0
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
❑
■
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment:
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, 0 ❑ ❑ ❑
and sampling location)?
Comment:
Page# 7