September 19, 2023
Michael P. Remige, General Manager
North Carolina Department of Natural and Cultural Resources
P.O. Box 1445
Nags Head, NC 27959
SUBJECT: NOTICE OF DEFICIENCY
Tracking Number: NOD-2023-LM-0007
Permit No. WQ0033589
Jennette's Pier WWTP
Dare County
Dear Mr. Remige:
A review of the July 2023 Non -Discharge Monitoring Report
(NDMR) for the subject facility revealed the
deficiency(s) indicated below:
Limit Exceedance Deficiency(s):
Sample
Limit
Reported
Location Parameter
Date
Value
Value
Type of Deficiency
001 Nitrogen, Ammonia Total (as
7/6/2023
6
68.4
Daily Maximum Exceeded
N) (00610)
001 Nitrogen, Ammonia Total (as
7/11/2023
6
17.1
Daily Maximum Exceeded
N) (00610)
001 Nitrogen, Ammonia Total (as
7/31/2023
4
22.3
Monthly Average Exceeded
N) (00610)
001 Nitrogen, Nitrate Total (as N)
7/31/2023
10
12.62
Monthly Average Exceeded
(00620)
001 Nitrogen, Total (as N) (00600)
7/31/2023
7
42.58
Monthly Average Exceeded
001 Phosphorus, Total (as P)
7/31/2023
3
8.29
Monthly Average Exceeded
(00665)
D E I North Carolina Department of Environmental Quality I Division of Water Resources
Washington Regional Office 1 943 Washington Square Mail I Washington. North Carolina 27889
y-^-•=�^ — 252.946.6481
Monitorina Deficiencv(s):
Sample Monitoring
Location Parameter Date Frequency Type of Deficiency
001 Turbidity, HCH Turbidimiter (00076) 7/1/2023 Continuous Frequency Violation
001 Turbidity, HCH Turbidimiter (00076) 7/2/2023 Continuous Frequency Violation
001 Turbidity, HCH Turbidimiter (00076) 7/8/2023 Continuous Frequency Violation
001 Turbidity, HCH Turbidimiter (00076) 7/9/2023 Continuous Frequency Violation
001 Turbidity, HCH Turbidimiter (00076) 7/15/2023 Continuous Frequency Violation
001 Turbidity, HCH Turbidimiter (00076) 7/16/2023 Continuous Frequency Violation
001 Turbidity, HCH Turbidimiter (00076) 7/22/2023 Continuous Frequency Violation
001 Turbidity, HCH Turbidimiter (00076) 7/23/2023 Continuous Frequency Violation
001 Turbidity, HCH Turbidimiter (00076) 7/29/2023 Continuous Frequency Violation
Please be aware that non-compliance with your permit could result in enforcement action by the Division of
Water Resources for these and any additional violations of State law. The Washington Regional Office
encourages you to take all necessary actions to bring your facility into compliance.
If you have any questions regarding this Notice or need additional information, you may contact Robert Tankard at
(252) 948-3921 or Randy Sipe at (252) 948-3849.
Sincerely,
Plow TR..f,
Robert Tankard, Assistant Regional Supervisor
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
Cc: Dave Robertson (ORC) — Atlantic OBX (electronic copy)
Laserfiche
D_EQ_- North Carullna➢epartment OF Environmental Quality I Division of Water Resources
Washington Regional Office 1943 Washington Square Mal[ I Washington, North Carolina 27889
^� ^��*�•���^�^v�o���� 252.946.6481