HomeMy WebLinkAboutNC0066028_202309CEI_20230905ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Town of Lansing
Attn: Sandra Rotten
PO BOX 266
Lansing, NC 28643-0266
NORTH CAROLINA
Environmental Quality
September 13, 2023
SUBJECT: Compliance Evaluation Inspection
Lansing WWTP, NCO066028
Ashe County
Dear Ms. Roten:
Tricia Lowery, of the NC Division of Water Resources (DWR), Winston-Salem Regional Office (WSRO),
visited the Lansing WWTP on 9/5/2023, to perform a Compliance Evaluation Inspection (CEI). The
assistance and cooperation of Tim Church (ORC) was greatly appreciated. Details of the inspection
are recorded on the attached Compliance Inspection Report.
You are reminded that, in accordance with NC General Statute 143-215.6A, failure to comply with all
conditions of the permit subjects the City/Town to civil penalties not to exceed $25,000.00 per
violation, per day.
If you have any questions or require further assistance, please contact Tricia Lowery by phone at
336-776-9691, or by email at tricia.lowery@deq.nc.gov. . You may also contact me by phone at 336-
776-9700, or by email at lon.snider@deq.nc.gov.
Sincerely,
EDocu Signed by:
Loti -T. SAwdlu-
145B49E225C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Attachments:
Compliance Inspection Report
DffNorth Carolina Department of Environmental Quality I Division of Water Resources
oan caaouNn
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
M336.776.9800
oep.m.m or em�nmen� ouaim,
DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO066028 I11 121 23/09/05 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:30AM 23/09/05
21/11/01
Lansing WWTP
3322 Teaberry Rd
Exit Time/Date
Permit Expiration Date
Lansing NC 28643
12:30PM 23/09/05
26/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Timothy Church/ORC/336-246-2165/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Tim Church,PO Box 67 Jefferson NC 286400067//336-246-2165/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Patricia Lowery DWR/WSRO WQ/336-776-9691/
by: 9/12/2023
FPDocuSigned
afVi(Aa thwt V
42D62165508C476.-
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by: 9/13/202 3
Lo- T. Sti�olcr
r—
EPA7orm W6-YtNev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411
NPDES yr/mo/day Inspection Type (Cont.)
NCO066028 I11 12I 23/09/05 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 9/5/2023, Division of Water Resources staff Tricia Lowery conducted a routine compliance
inspection at Lansing WWTP (NC0066028). Tim Church was present during the inspection. A review
of records, data, treatment components, structures, fields, etc. was completed. This review reflected
compliance with the subject permit. No violations or items of concern were noted.
A private company has awarded a grant to the Town of Lansing to upgrade the WWTP. On the day
of CEI, the Town was in meetings with company to review plans of upgrade. DEQ should expect
documentation (application) for AtC with engineering plans of upgrade in the near future.
Page#
DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411
Permit: NCO066028 Owner -Facility: Lansing WWTP
Inspection Date: 09/05/2023 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Permit expires 3/31/2026. They are still operating under the effluent limitations for
0.015 MGD flow. Treatment facility will be undergoing an upgrade in near future.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: Tim Church remains the ORC of WWTP. Jacob Cruev is the BORC (replacing Fred
Walters). Mr. Cruet' certification #1011936. Operator license for ORC and BORC are
active.
Reviewed February 2022 & April 2023 DMRs. All data is consistent with data reported
on eDMR. COC's are in good order. No issues found.
Page# 3
DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411
Permit: NCO066028 Owner -Facility: Lansing WWTP
Inspection Date: 09/05/2023 Inspection Type: Compliance Evaluation
Record Keeping
Yes No NA NE
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Settleable solids on average are 68% (MLSS -3300mg/1). DO and pH are monitored
closely. This is a small package plant secured by fence and locked pate. The area is
well maintained. Storage building/shed on site for record keeping and process control
monitoring.
Bar Screens
Type of bar screen
Yes No NA NE
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
■
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: No issues found durinq inspection. Bar screen is adequately maintained.
Debris
removed is landfilled.
Aeration Basins
Yes
No
NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
■
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
■
❑
❑
❑
Page# 4
DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411
Permit: NCO066028 Owner -Facility: Lansing WWTP
Inspection Date: 09/05/2023 Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Comment: Proper "earthy" smell to aeration basin. The DO readings average 2.0mg/I. No
excessive foaming or foam coverage. Healthy aeration basin. No issues found during
inspection.
Great improvement in the past year due to ORC's efforts. WWTP was having issues
which resulted in civil penalites. ORC had to 're -seed' basin more than once due to
microorganism death (excessive organic loading) and adjust blower rate to basin. No
industries in vicinity, however it was believed to be caused by slug discharges from
local brewery.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: No issues found during inspection.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
❑
❑
■
❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: Dewaterinq pump in good working order (ORC demonstrated during inspection). No
excessive odor and mixing is adequate.
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? 0 ❑ ❑ ❑
Are the tablets the proper size and type? ■ ❑ ❑ ❑
Number of tubes in use?
Is the level of chlorine residual acceptable?
1
❑ ❑ ❑
Page# 5
DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411
Permit: NCO066028 Owner -Facility: Lansing WWTP
Inspection Date: 09/05/2023 Inspection Type: Compliance Evaluation
Disinfection -Tablet Yes No NA NE
Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑
Is there chlorine residual prior to de -chlorination? 0 ❑ ❑ ❑
Comment: Chlorine chamber is well maintained and in -good working order. Tablets are stored
properly. Adequate tablets in use. Ratio 1:1
De -chlorination
Yes
No
NA
NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
0
❑
❑
❑
Is storage appropriate for cylinders?
0
❑
❑
❑
# Is de -chlorination substance stored away from chlorine containers?
0
❑
❑
❑
Are the tablets the proper size and type?
■
❑
❑
❑
Comment: Proper storage and use. Ratio 1:1. Facility has 2 tubes for de -chlorination with one
tube in use.
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment: See comment above
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Stevens system. Last calibration 8/15/2023. No issues found.
■ ❑ ❑ ❑
1
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Effluent Pipe
Yes
No
NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: Right of way is properly maintained. Outfall looks good with no issues.
Receiving
waters are clear with no foaming.
Page# 6