HomeMy WebLinkAboutNC0066028_202309CEI_20230905ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director Town of Lansing Attn: Sandra Rotten PO BOX 266 Lansing, NC 28643-0266 NORTH CAROLINA Environmental Quality September 13, 2023 SUBJECT: Compliance Evaluation Inspection Lansing WWTP, NCO066028 Ashe County Dear Ms. Roten: Tricia Lowery, of the NC Division of Water Resources (DWR), Winston-Salem Regional Office (WSRO), visited the Lansing WWTP on 9/5/2023, to perform a Compliance Evaluation Inspection (CEI). The assistance and cooperation of Tim Church (ORC) was greatly appreciated. Details of the inspection are recorded on the attached Compliance Inspection Report. You are reminded that, in accordance with NC General Statute 143-215.6A, failure to comply with all conditions of the permit subjects the City/Town to civil penalties not to exceed $25,000.00 per violation, per day. If you have any questions or require further assistance, please contact Tricia Lowery by phone at 336-776-9691, or by email at tricia.lowery@deq.nc.gov. . You may also contact me by phone at 336- 776-9700, or by email at lon.snider@deq.nc.gov. Sincerely, EDocu Signed by: Loti -T. SAwdlu- 145B49E225C94EA... Lon T. Snider, Regional Supervisor Water Quality Regional Operations Section Winston-Salem Regional Office Division of Water Resources, NCDEQ Attachments: Compliance Inspection Report DffNorth Carolina Department of Environmental Quality I Division of Water Resources oan caaouNn Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105 M336.776.9800 oep.m.m or em�nmen� ouaim, DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 u 3 I NCO066028 I11 121 23/09/05 I17 18I � I 19 I s I 201 I 211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 67 I 72 I n, I 71 I 74 79 I I I I I I I80 701 I 71 I LL -1 I I LJ Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES Dermit Number) 10:30AM 23/09/05 21/11/01 Lansing WWTP 3322 Teaberry Rd Exit Time/Date Permit Expiration Date Lansing NC 28643 12:30PM 23/09/05 26/03/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Timothy Church/ORC/336-246-2165/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Tim Church,PO Box 67 Jefferson NC 286400067//336-246-2165/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenar Records/Reports Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Patricia Lowery DWR/WSRO WQ/336-776-9691/ by: 9/12/2023 FPDocuSigned afVi(Aa thwt V 42D62165508C476.- Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date DocuSigned by: 9/13/202 3 Lo- T. Sti�olcr r— EPA7orm W6-YtNev 9-94) Previous editions are obsolete. Page# DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411 NPDES yr/mo/day Inspection Type (Cont.) NCO066028 I11 12I 23/09/05 117 18 i c i Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On 9/5/2023, Division of Water Resources staff Tricia Lowery conducted a routine compliance inspection at Lansing WWTP (NC0066028). Tim Church was present during the inspection. A review of records, data, treatment components, structures, fields, etc. was completed. This review reflected compliance with the subject permit. No violations or items of concern were noted. A private company has awarded a grant to the Town of Lansing to upgrade the WWTP. On the day of CEI, the Town was in meetings with company to review plans of upgrade. DEQ should expect documentation (application) for AtC with engineering plans of upgrade in the near future. Page# DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411 Permit: NCO066028 Owner -Facility: Lansing WWTP Inspection Date: 09/05/2023 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ 0 ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: Permit expires 3/31/2026. They are still operating under the effluent limitations for 0.015 MGD flow. Treatment facility will be undergoing an upgrade in near future. Record Keeping Are records kept and maintained as required by the permit? Is all required information readily available, complete and current? Are all records maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? Has the facility submitted its annual compliance report to users and DWQ? (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? Is the ORC visitation log available and current? Is the ORC certified at grade equal to or higher than the facility classification? Is the backup operator certified at one grade less or greater than the facility classification? Is a copy of the current NPDES permit available on site? Facility has copy of previous year's Annual Report on file for review? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ Comment: Tim Church remains the ORC of WWTP. Jacob Cruev is the BORC (replacing Fred Walters). Mr. Cruet' certification #1011936. Operator license for ORC and BORC are active. Reviewed February 2022 & April 2023 DMRs. All data is consistent with data reported on eDMR. COC's are in good order. No issues found. Page# 3 DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411 Permit: NCO066028 Owner -Facility: Lansing WWTP Inspection Date: 09/05/2023 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Settleable solids on average are 68% (MLSS -3300mg/1). DO and pH are monitored closely. This is a small package plant secured by fence and locked pate. The area is well maintained. Storage building/shed on site for record keeping and process control monitoring. Bar Screens Type of bar screen Yes No NA NE a.Manual b.Mechanical ❑ Are the bars adequately screening debris? ■ ❑ ❑ ❑ Is the screen free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screening in compliance? 0 ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: No issues found durinq inspection. Bar screen is adequately maintained. Debris removed is landfilled. Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? 0 ❑ ❑ ❑ Are the diffusers operational? ■ ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? 0 ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) ■ ❑ ❑ ❑ Page# 4 DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411 Permit: NCO066028 Owner -Facility: Lansing WWTP Inspection Date: 09/05/2023 Inspection Type: Compliance Evaluation Aeration Basins Yes No NA NE Comment: Proper "earthy" smell to aeration basin. The DO readings average 2.0mg/I. No excessive foaming or foam coverage. Healthy aeration basin. No issues found during inspection. Great improvement in the past year due to ORC's efforts. WWTP was having issues which resulted in civil penalites. ORC had to 're -seed' basin more than once due to microorganism death (excessive organic loading) and adjust blower rate to basin. No industries in vicinity, however it was believed to be caused by slug discharges from local brewery. Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) Comment: No issues found during inspection. Aerobic Digester Is the capacity adequate? Is the mixing adequate? Is the site free of excessive foaming in the tank? # Is the odor acceptable? # Is tankage available for properly waste sludge? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ■ ❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Comment: Dewaterinq pump in good working order (ORC demonstrated during inspection). No excessive odor and mixing is adequate. Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? ■ ❑ ❑ ❑ Number of tubes in use? Is the level of chlorine residual acceptable? 1 ❑ ❑ ❑ Page# 5 DocuSign Envelope ID: 691AF089-6745-4C81-BD76-F6D229676411 Permit: NCO066028 Owner -Facility: Lansing WWTP Inspection Date: 09/05/2023 Inspection Type: Compliance Evaluation Disinfection -Tablet Yes No NA NE Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? 0 ❑ ❑ ❑ Comment: Chlorine chamber is well maintained and in -good working order. Tablets are stored properly. Adequate tablets in use. Ratio 1:1 De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑ Is storage appropriate for cylinders? 0 ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Are the tablets the proper size and type? ■ ❑ ❑ ❑ Comment: Proper storage and use. Ratio 1:1. Facility has 2 tubes for de -chlorination with one tube in use. Are tablet de -chlorinators operational? Number of tubes in use? Comment: See comment above Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Comment: Stevens system. Last calibration 8/15/2023. No issues found. ■ ❑ ❑ ❑ 1 Yes No NA NE ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: Right of way is properly maintained. Outfall looks good with no issues. Receiving waters are clear with no foaming. Page# 6