HomeMy WebLinkAboutWQ0006863_Compliance Evaluation Inspection_20230908DocuSign Envelope ID: 009E3475-06B1-4EBF-A56F-3E92CBDC288B ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director NORTH CAROLINA Environmental Quality September 08, 2023 Grady W Fulcher Genesis Condominium Owners Association Inc PO Box 1154 Atlantic Beach, NC 28512-1154 SUBJECT: Compliance Inspection Report Genesis Condominiums WWTP Non -discharge Permit No. WQ0006863 Carteret County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Genesis Condominiums WWTP on 8/24/2023. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0006863. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. If you should have any questions, please do not hesitate to contact Geoff Kegley with the Water Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at geoff.kegley@deq.nc.gov. ATTACHMENTS Cc: DWR files — Laserfische Don O'Mara - ORC Sincerely, EDocuSigned by: �-,,j, 6, E3ABA14AC7DC434... Morella Sanchez -King, Regional Supervisor Water Quality Regional Operations Section Wilmington Regional Office Division of Water Resources, NCDEQ North Carolina Department of Environmental Quality I Division of Water Resources ,./ Wiimington Regional Office 1127 Cardinal Drive Extension I Wilmington. North Carolina 26405 910.796,7215 DocuSign Envelope ID: 009E3475-06B1-4EBF-A56F-3E92CBDC288B Comoliance Insoection Resort Permit: WQ0006863 Effective: 09/16/22 Expiration: 07/31/29 Owner: Genesis Condominium Owners Association Inc SOC: Effective: Expiration: Facility: Genesis Condominiums WWTP County: Carteret 301 Salter Path Rd Region: Wilmington Atlantic Beach NC 28512 Contact Person: Grady W Fulcher Title: Property Manager Phone: 252-247-2800 Directions to Facility: From Kinston, take State Route 58 south approximately 50 miles to the bridge across Bogue Sound. Proceed another 13 miles on State Route 58 to Bogue Banks. The facility is directly across from the entrance to the NC Aquarium at Pine Knoll Shores. System Classifications: WW2, Primary ORC: Donald P Omara Certification: 7904 Phone: 252-247-9167 Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 08/24/2023 Entry Time 02:OOPM Exit Time: 03:OOPM Primary Inspector: Geoff Kegley Phone: DocuSigned by: Secondary Inspector(s): � C017E2515MB417... Reason for Inspection: Routine Inspection Type: Compliance Evaluation Permit Inspection Type: High Rate Infiltration Facility Status: Compliant ❑ Not Compliant Question Areas: Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions Treatment Flow Measurement -Water Treatment Record Keeping Use Records Treatment Influent Pump Station Treatment Disinfection End Use -Infiltration Treatment Flow Measurement Standby Power (See attachment summary) Page 1 of 6 DocuSign Envelope ID: 009E3475-06B1-4EBF-A56F-3E92CBDC288B Permit: WQ0006863 Owner - Facility: Genesis Condominium Owners Association Inc Inspection Date: 08/24/2023 Inspection Type : Compliance Evaluation Reason for Visit: Routine Inspection Summary: A routine compliance inspection of the Genesis WWTF was conducted on August 24, 2023. The purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit WQ0006863. Don O'Mara — ORC was present during the inspection. The Genesis WWTF is permitted for 24,000 GPD and consists of: • 12,000 gallon EQ tank • Two 15,000 gallon sequencing batch reactors (SBR) • 3,400 gallon sludge holding tank • Three 40 GPM ultraviolet (UV) disinfection units • 3,000 gallon dosing chamber • high -rate infiltration disposal via two 44foot diameter rotary distributors The dual Sequencing Batch Reactor system peaked at approximately 9,000 gpd this summer season, less than half of the 24,000 gpd of permitted flow. A review of records, since the last inspection in June 2019, shows no effluent violations and some TDS limit exceedances in Monitoring Wells #1 and #4. The facility is compliant with Non -Discharge Permit WQ0006863. Please review the comment sections of the inspection report for more details. Page 2 of 6 DocuSign Envelope ID: 009E3475-06B1-4EBF-A56F-3E92CBDC288B Permit: WQ0006863 Inspection Date: 08/24/2023 Owner - Facility: Genesis Condominium Owners Association Inc Inspection Type : Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Reuse (Quality) ❑ Lagoon Spray, LR ❑ Single Family Spray, LR ❑ Activated Sludge Spray, LR ❑ Activated Sludge Spray, HR ❑ Activated Sludge Drip, LR ❑ Recycle/Reuse ❑ Single Family Drip ❑ Infiltration System Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑ Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑ Comment: The high-level float alarm in the SBR was not working. Recent storms/lightning likely caused the electrical issue. The ORC had this repaired the following day. Treatment Influent Pump Station Yes No NA NE Is the pump station free of bypass lines or structures? ❑ ❑ ❑ Is the general housekeeping acceptable? ❑ ❑ ❑ Are all pumps present? ❑ ❑ ❑ Are all pumps operable? ❑ ❑ ❑ Are floats/controls operable? ❑ ❑ ❑ Are audio and visual alarms available? ❑ ❑ ❑ Are audio and visual alarms operational? ❑ ❑ ❑ # Are SCADA/Telemetry alarms required? ❑ ❑ ❑ Are SCADA/Telemetry available? ❑ ❑ ❑ Are SCADA/Telemetry operational? ❑ ❑ 0 ❑ Comment: The high-level float alarm in the pump station was activated and functioning. The pump station is inspected weekly and documented on a check sheet. Treatment Flow Measurement -Influent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ 0 ❑ Is flowmeter operating properly? ❑ ❑ 0 ❑ Does flowmeter monitor continuously? ❑ ❑ 0 ❑ Does flowmeter record flow? ❑ ❑ 0 ❑ Does flowmeter appear to monitor accurately? ❑ ❑ 0 ❑ Page 3 of 6 DocuSign Envelope ID: 009E3475-06B1-4EBF-A56F-3E92CBDC288B Permit: WO0006863 Owner - Facility: Genesis Condominium Owners Association Inc Inspection Date: 08/24/2023 Inspection Type : Compliance Evaluation Reason for Visit: Routine Treatment Flow Measurement -Water Use Records Is water use metered? Are the daily average values properly calculated? Comment: Treatment Flow Measurement -Effluent Is flowmeter calibrated annually? Is flowmeter operating properly? Does flowmeter monitor continuously? Does flowmeter record flow? Does flowmeter appear to monitor accurately? Comment: The flowmeter was calibrated on 5/24/2023 Delta Svstems Environmental. Yes No NA NE ❑❑■❑ ❑❑■❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ■❑❑❑ Standby Power Yes No NA NE Is automatically activated standby power available? ❑ ❑ ❑ Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑ Is generator operable? ❑ ❑ ❑ Does generator have adequate fuel? ❑ ❑ ❑ Comment: The facility generator provides stand-by power for both the wastewater plant and the influent pump station. The generator is tested weekly. Treatment Disinfection Yes No NA NE Is the system working? 0 ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time (-30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas, does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ 0 ❑ Is the chlorinator accessible? ❑ ❑ ❑ If tablets, are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑ If UV, are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ # Is it a dual feed system? ❑ ❑ ❑ Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes, then what is the EPA twelve digit ID Number? (1000- If yes, then when was the RMP last updated? Page 4 of 6 DocuSign Envelope ID: 009E3475-06B1-4EBF-A56F-3E92CBDC288B Permit: WQ0006863 Owner - Facility: Genesis Condominium Owners Association Inc Inspection Date: 08/24/2023 Inspection Type : Compliance Evaluation Reason for Visit: Routine Comment: Record Keeping Yes No NA NE Is a copy of current permit available? 0 ❑ ❑ ❑ Are monitoring reports present: NDMR? ❑ ❑ ❑ NDAR? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are application rates adhered to? ❑ ❑ ❑ Is GW monitoring being conducted, if required (GW-59s submitted)? ❑ ❑ ❑ Are all samples analyzed for all required parameters? ❑ ❑ ❑ Are there any 2L GW quality violations? ❑ ❑ ❑ Is GW-59A certification form completed for facility? ❑ ❑ ❑ Is effluent sampled for same parameters as GW? ❑ ❑ ❑ Do effluent concentrations exceed GW standards? ❑ ❑ ❑ Are annual soil reports available? ❑ ❑ ❑ # Are PAN records required? ❑ ❑ ❑ # Did last soil report indicate a need for lime? ❑ ❑ ❑ If so, has it been applied? ❑ ❑ ❑ Are operational logs present? ❑ ❑ ❑ Are lab sheets available for review? ❑ ❑ ❑ Do lab sheets support data reported on NDMR? ❑ ❑ ❑ Do lab sheets support data reported on GW-59s? ❑ ❑ ❑ Are Operational and Maintenance records present? ❑ ❑ ❑ Were Operational and Maintenance records complete? ❑ ❑ ❑ Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑ Is a copy of the SOC readily available? ❑ ❑ ❑ No treatment units bypassed since last inspection? ❑ ❑ 0 ❑ Comment: Operational and maintenance log book was organized and complete End Use -Infiltration Yes No NA NE # Is the application High Rate or Low Rate? High Rate Are buffers maintained? 0 ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ Is municipal water available in the area? 0 ❑ ❑ ❑ Are GW monitoring wells required? 0 ❑ ❑ ❑ Are GW monitoring wells located properly w/ respect to RB and CB? ❑ ❑ ❑ Page 5 of 6 DocuSign Envelope ID: 009E3475-06B1-4EBF-A56F-3E92CBDC288B Permit: WO0006863 Owner - Facility: Genesis Condominium Owners Association Inc Inspection Date: 08/24/2023 Inspection Type : Compliance Evaluation Reason for Visit: Routine Are GW monitoring wells properly constructed, including screened interval? Is a usable green area maintained? Is the disposal site acceptable? Is the distribution equipment acceptable? Is the disposal site free of ponding? Is the disposal site free of breakout? Are the disposal sites free of solids, algae, etc.? Do the records show that the fields are properly maintained? Are the disposal sites free of vegetation? Do any surface water features appear to be adversely impacted by GW discharge? No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.? Comment: The infiltration rotary fields are well maintained, securely locked with signs vegetative growth is removed. ❑❑❑■ ❑❑■❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑❑■❑ ❑❑■❑ and the Page 6 of 6