HomeMy WebLinkAboutWQ0044593_Application (FTSE)_20230719DWR
Division of Water Resources
State of North Carolina
Department of Environmental Quality
Division of Water Resources
FAST TRACK SEWER SYSTEM EXTENSION APPLICATION
FTA 06-21 & SUPPORTING DOCUMENTATION
Application Number: ° L�� �C13(to be completed by DWR)
All items must be completed or the application will be returned
I. APPLICANT INFORMATION:
1. Applicant's name: Toyota (company, municipality, HOA, utility, etc.)
2. Applicant type: ❑ Individual ® Corporation ❑ General Partnership
❑ Federal ❑ State/County ❑ Municipal
3. Signature authority's name: Kevin Kerwin per 15A NCAC 02T .0106(b)
Title: Manager
4. Applicant's mailing address: 5938 Julian Airport Road
City: Liberty State: NC Zip: 27298-
5. Applicant's contact information:
Phone number: (734) 223-8318 Email Address: kevin.kerwin(ibtoyota.com
II. PROJECT INFORMATION:
❑ Privately -Owned Public Utility
❑ Other
1. Project name: TBMNC BEV Phase II Central Quad
2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project
If a modification, provide the existing permit number: WQ and issued date: ,
For modifications, also attach a detailed narrative description as described in Item G of the checklist.
If new construction, but part of a master plan, provide the existing permit number: WQ00
3. County where project is located: Randolph
4. Approximate Coordinates: (Decimal Degrees): Latitude: 35.8947854' Longitude:-079.6335583'
5. Parcel ID (if applicable): 8718029180 (or Parcel ID to closest downstream sewer)
III. CONSULTANT INFORMATION:
1. Professional Engineer: Matthew W Watt License Number: 037518
Firm: HDR Engineering Inc. of the Carolinas
Mailing address: 440 S. Church St. Suite 1200
City: Charlotte State: NC Zip: 28202-2075
Phone number: (336) 955-8259 Email Address: matthew.wattAhdrinc.com
IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION:
1. Facility Name: T.Z. Osborne Water reclamation Facility Permit Number: NCO047384
Owner Name: City of Greensboro
V. RECEIVING DOWNSTREAM SEWER INFORMATION:
1. Permit Number(s): WQCS00006
2. Downstream (Receiving) Sewer Information: 24" inch ❑X Gravity ❑ Force Main
3. System Wide Collection System Permit Number(s) (if applicable): WQCS00006
Owner Name(s): City of Greensboro
FORM: FTA 06-21 Page 1 of 6
VI. GENERAL REQUIREMENTS
1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached?
❑ Yes ❑ No ® N/A
2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV) been attached?
❑ Yes [:]No ® N/A
3. If the Applicant is a Home/Property Owners' Association, has an HOA/POA Operational Agreement (FORM: HOA) and
supplementary documentation as required by 15A NCAC 02T.0115(c) been attached?
❑ Yes ❑ No ® N/A
4. Origin of wastewater: (check all that apply):
❑ Residential (Individually Owned) ❑ Retail (stores, centers, malls) ❑ Car Wash
❑ Residential (Leased) ❑ Retail with food preparation/service ❑ Hotel and/or Motels
❑ School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool/Clubhouse
❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash
® Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment)
5. Nature of wastewater: % Domestic % Commercial % Industrial (See 15A NCAC 02T .0103(20))
If Industrial, is there a Pretreatment Program in effect? ❑ Yes ❑ No
6. Hasa flow reduction been approved under 15A NCAC 02T .0114(1)? ❑ Yes ® No
➢ If Yes, provide a copy of flow reduction approval letter with this application
7. Summarize wastewater generated by project:
Establishment Type (see 02T.0114(f))
Daily Design Flow a b
No. of Units
Flow
gal/
GPD
gall
GPD
gal/
GPD
gal/
GPD
gal/
GPD
gal/
GPD
Total
0 GPD
a See 15A NCAC 02T .0114(b), (d), (e)(1) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per
dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas;
and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined
in G.S. 42A-4).
b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.0114] shall be
determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data.
8. Wastewater generated by project: 0 GPD (per 15A NCAC 02T .0114)
➢ Do not include future flows or previously permitted allocations
If permitted flow is zero, please indicate why:
❑ Pump Station/Force Main or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line.
Please provide supplementary information indicating the approximate timeframe for permitting upstream sewers with flow.
® Flow has already been allocated in Permit Number: W00040884 Issuance Date: 1/5/2023
❑ Rehabilitation or replacement of existing sewers with no new flow expected
❑ Other (Explain):
FORM: FTA 06-21 Page 2 of 6
VII. GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T .0305 & MDC (Gravity Sewers):
1. Summarize gravity sewer to be permitted:
Size (inches)
Length (feet)
Material
8"
45
C-900
➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria
➢ Section III contains information related to minimum slopes for gravity sewer(s)
➢ Oversizing lines to meet minimum slope requirements is not allowed and a violation of the MDC
VIII. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pump Stations/Force Mains):
PROVIDE A SEPARATE COPY OF THIS PAGE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT
1. Pump station number or name: 804
2. Approximate Coordinates (Decimal Degrees): Latitude: 35.8890785' Longitude:-079.6264383'
3. Total number of pumps at the pump station: 2
3. Design flow of the pump station: .31 millions gallons per day (firm capacity)
➢ This should reflect the total GPM for the pump station with the largest pump out of service.
4. Operational point(s) per pump(s): 200 gallons per minute (GPM) at 20 feet total dynamic head (TDH)
5. Summarize the force main to be permitted (for this Pump Station):
Size (inches)
Length (feet)
Material
6
140
C-900
8
1590
C-900
If any portion of the force main is less than 4-inches in diameter, please identify the method of solids reduction per
MDCPSFM Section 2.01 C. Lb. ❑ Grinder Pump ❑ Mechanical Bar Screen ❑ Other (please specify)
6. Power reliability in accordance with 15A NCAC 02T .0305(h)(1):
® Standby power source or ® Standby pump
➢ Must have automatic activation and telemetry - 15A NCAC 02T.0305(h)(1)(B);
➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day
➢ Must be permanent to facility and may not be portable
Or if the pump station has an average daily flow less than 15,000 gallons per day 15A NCACO2T.0305(h)(1)(C):
❑ Portable power source with manual activation, quick -connection receptacle and telemetry -
or
❑ Portable pumping unit with plugged emergency pump connection and telemetry:
➢ Include documentation that the portable source is owned or contracted by the applicant and is compatible with the station.
➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage
capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided
as part of this permit application in the case of a multiple station power outage.
FORM: FTA 06-21 Page 3 of 6
IX. GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T .0305 & MDC (Gravity Sewers):
2. Summarize gravity sewer to be permitted:
Size (inches)
Length (feet)
Material
8"
45
C-900
➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria
➢ Section III contains information related to minimum slopes for gravity sewer(s)
➢ Oversizing lines to meet minimum slope requirements is not allowed and a violation of the MDC
X. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pump Stations/Force Mains):
PROVIDE A SEPARATE COPY OF THIS PAGE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT
2. Pump station number or name: 805
4. Approximate Coordinates (Decimal Degrees): Latitude: 35.89410751 Longitude:-079.62594010
5. Total number of pumps at the pump station: 2
7. Design flow of the pump station: .31 millions gallons per day (firm capacity)
➢ This should reflect the total GPM for the pump station with the largest pump out of service.
8. Operational point(s) per pump(s): 200 gallons per minute (GPM) at 18 feet total dynamic head (TDH)
9. Summarize the force main to be permitted (for this Pump Station):
Size (inches)
Length (feet)
Material
6
2009
C-900
If any portion of the force main is less than 4-inches in diameter, please identify the method of solids reduction per
MDCPSFM Section 2.01 C. Lb. ❑ Grinder Pump ❑ Mechanical Bar Screen ❑ Other (please specify)
10. Power reliability in accordance with 15A NCAC 02T .0305(h)(1):
® Standby power source or ® Standby pump
➢ Must have automatic activation and telemetry - 15A NCAC 02T.0305(h)(1)(B);
➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day
➢ Must be permanent to facility and may not be portable
Or if the pump station has an average daily flow less than 15,000 gallons per day 15A NCACO2T.0305(h)(1)(C):
❑ Portable power source with manual activation, quick -connection receptacle and telemetry -
or
❑ Portable pumping unit with plugged emergency pump connection and telemetry:
➢ Include documentation that the portable source is owned or contracted by the applicant and is compatible with the station.
If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage capacities
and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided as part of this permit
application in the case of a multiple station power outage.
FORM: FTA 06-21 Page 4 of 6
IX. SETBACKS & SEPARATIONS — (02B .0200 & 15A NCAC 02T .0305(f)):
1. Does the project comply with all separations/alternatives found in 15A NCAC 02T .0305(f) & (g)? ® Yes ❑ No
15A NCAC 02T.0305(1) contains minimum separations that shall be provided for sewer systems:
Setback Parameter*
Separation Required
Storm sewers and other utilities not listed below (vertical)
18 inches
2Water mains (vertical - water over sewer preferred, including in benched trenches)
18 inches
2Water mains (horizontal)
10 feet
Reclaimed water lines (vertical - reclaimed over sewer)
18 inches
Reclaimed water lines (horizontal - reclaimed over sewer)
2 feet
**Any private or public water supply source, including any wells, WS-I waters of Class I or
Class II impounded reservoirs used as a source of drinking water, and associated wetlands.
100 feet
**Waters classified WS (except WS-1 or WS-V), B, SA, ORW, HQW, or SB from normal
high water (or tide elevation) and wetlands associated with these waters (see item IX.2)
50 feet
**Any other stream, lake, impoundment, or ground water lowering and surface drainage
ditches, as well as wetlands associated with these waters or classified as WL.
10 feet
Any building foundation (horizontal)
5 feet
Any basement (horizontal)
10 feet
Top slope of embankment or cuts of 2 feet or more vertical height
10 feet
Drainage systems and interceptor drains
5 feet
Any swimming pools
10 feet
Final earth grade (vertical)
36 inches
➢ If noncompliance with 02T.0305(_f) or g), see Section X.1 of this application
*15A NCAC 02T.0305(g) contains alternatives where separations in 02T.0305(fl cannot be achieved. Please check "yes"
above if these alternatives are used and provide narrative information to explain.
**Stream classifications can be identified using the Division's NC Surface Water Classifications webpage
2. Does this project comply with the minimum separation requirements for water mains? ® Yes [—]No ® N/A
➢ If no, please refer to 15A NCAC 18C.0906(f) for documentation requirements and submit a separate document,
signed/sealed by an NC licensed PE, verifying the criteria outlined in that Rule.
3. Does the project comply with separation requirements for wetlands? ® Yes ❑ No ❑ N/A
➢ Please provide supplementary information identifying the areas of non-conformance.
➢ See the Division's draft separation requirements for situations where separation cannot be met.
➢ No variance is required if the alternative design criteria specified is utilized in design and construction.
4. Is the project located in a river basin subject to any State buffer rules? ❑ Yes Basin name: ® No
If yes, does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .0200? ❑ Yes ❑ No
➢ This includes Trout Buffered Streams per 15A NCAC 213.0202
5. Does the project require coverage/authorization under a 404 Nationwide/individual permits ® Yes ❑ No
or 401 Water Quality Certifications?
➢ Please provide the permit number/permitting status in the cover letter if coverage/authorization is required.
6. Does project comply with 15A NCAC 02T.0105(c)(6) (additional permits/certifications)? ❑ Yes ® No
Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications must be being prepared,
have been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion
and sedimentation control plans, stormwater management plans, etc.).
7. Does this project include any sewer collection lines that are deemed "high -priority?" ❑ Yes ® No
Per 15A NCAC 02T.0402, "high -priority sewer" means any aerial sewer, sewer contacting surface waters,
siphon, or sewers positioned parallel to streambanks that are subject to erosion that undermines or deteriorates the sewer.
Siphons and sewers suspended through interference/conflict boxes require a variance approval.
➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location).
High priority lines shall be inspected by the permittee or its representative at least once every six -months and
inspections documented per 15A NCAC 02T.0403(a)(5) or the permittee's individual System -Wide Collection permit.
FORM: FTA 06-21 Page 5 of 6
X. CERTIFICATIONS:
1. Does the submitted system comply with 15A NCAC 02T, the Minimum Design Criteria for the Permitting of Pump Stations
and Force Mains (latest version), and the Gravity Sewer Minimum Design Criteria (latest version) as applicable?
® Yes ❑ No
If no, for projects requiring a single variance, complete and submit the Variance/Alternative Design Request application
(VADC 10-14) and supporting documents for review to the Central Office. Approval of the request will be issued
concurrently with the approval of the permit, and projects requiring a variance approval may be subiect to longer
review times. For projects requiring two or more variances or where the variance is determined by the Division to be a
significant portion of the project, the full technical review is required.
2. Professional Engineer's Certification:
I, Matthew Watt, attest that this application for TBMNC BEV Phase II Central Quad
(Professional Engineer's name from Application Item III.1.) (Project Name from Application Item II.1)
has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans,
specifications, engineering calculations, and all other supporting documentation to the best of my knowledge. I further
attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations,
Minimum Design Criteria for Gravity Sewers latest version), and the Minimum Design Criteria for the Fast -Track Permitting
of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this
submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and
have judged it to be consistent with the proposed design.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.613, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation. Misrepresentation of the application
information, including failure to disclose any design non-compliance with the applicable Rules and design criteria, may subject
the North Carolina -licensed Professional Engineer to referral to the licensing board. (21 NCAC 56.0701)
.......................................... ..
North Carolina Professional Engineer's seal, signature, and date:
:q
03751$ —
..................... ....'P.i.rl.l.l t�........................
Applicant's Certification per 15A NCAC 02T .0106(b):
I, Kevin Kerwin, attest that this application for TBMNC BEV Phase II Central Quad
(Signature Authority Name from Application Item 1.3.) (Project Name from Application Item II.1)
attest that this application has been reviewed by me and is accurate and complete to the best of my knowledge.
I understand that if all required parts of this application are not completed and that if all required supporting documentation
and attachments are not included, this application package is subject to being returned as incomplete. I understand that any
discharge of wastewater from this non -discharge system to surface waters or the land will result in an immediate enforcement
action that may include civil penalties, injunctive relief, and/or criminal prosecution. I will make no claim against the Division
of Water Resources should a condition of this permit be violated. I also understand that if all required parts of this application
package are not completed and that if all required supporting information and attachments are not included, this application
package will be returned to me as incomplete.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation.
-7
Signature: Date: -7 ;�, 3
FORM: FTA 06-21 Page 6 of 6
.r
.t
a
v
,
(5) BUSINESS CORPORATION ANNUAL REPORT
1/6/2022
NAME OF BUSINESS CORPORATION: TOYOTA BATTERY MANUFACTURING, INC.
SECRETARY OF STATE ID NUMBER: 2322759 STATE OF FORMATION: DE
REPORT FOR THE FISCAL YEAR END: 12/31 /2021
SECTION A: REGISTERED AGENT'S INFORMATION
1. NAME OF REGISTERED AGENT: CT Corporation System
2. SIGNATURE OF THE NEW REGISTERED AGENT:
h fling Uffice Use Unly
E - Filed Annual Report
2322759
CA202232100643
11 /17/2022 12:00
❑X Changes
SIGNATURE CONSTITUTES CONSENT TO THE APPOINTMENT
3. REGISTERED AGENT OFFICE STREET ADDRESS & COUNTY 4. REGISTERED AGENT OFFICE MAILING ADDRESS
160 Mine Lake Ct Ste 200 160 Mine Lake Ct Ste 200
Raleigh, NC 27615 Wake County
Raleigh, NC 27615
SECTION B: PRINCIPAL OFFICE INFORMATION
1. DESCRIPTION OF NATURE OF BUSINESS: Battery R&D and Manufacturing Plant
2. PRINCIPAL OFFICE PHONE NUMBER: (469) 786-3361 3. PRINCIPAL OFFICE EMAIL: Privacy Redaction
4. PRINCIPAL OFFICE STREET ADDRESS 5. PRINCIPAL OFFICE MAILING ADDRESS
6565 Headquarters Dr
Plano, TX 75024
6565 Headquarters Dr
Plano, TX 75024
6. Select one of the following if applicable. (Optional see instructions)
❑ The company is a veteran -owned small business
❑ The company is a service -disabled veteran -owned small business
SECTION C: OFFICERS (Enter additional officers in Section E.)
NAME: Qhini,-hi Vnc, li
TITLE: Qoninr Wir•c Pracirlanf
ADDRESS:
6565 Headquarters Drive
Plano, TX 75024
NAME:
Sean Suggs
NAME:
Thibaut De Barros Conti
TITLE:
President
TITLE:
Secretary
ADDRESS:
6565 Headquarters Drive
Plano, TX 75024
ADDRESS:
6565 Headquarters Drive
Plano, TX 75024
SECTION D: CERTIFICATION OF ANNUAL REPORT. Section D must be completed in its entirety by a person/business
entit .
%inichi Yasui 11/17/2022
SIGNATURE DATE
Form must be signed by an officer listed under Section C of this form.
Shinichi Yasui Senior Vice President
Print or Type Name of Officer Print or Type Title of Officer
This Annual Report has been filed electronically.
MAIL TO: Secretary of State, Business Registration Division, Post Office Box 29525, Raleigh, NC 27626-0525
J,I BUSINESS CORPORATION ANNUAL REPORT
1/6/2022
NAME OF BUSINESS CORPORATION: TOYOTA BATTERY MANUFACTURING, INC.
SECRETARY OF STATE ID NUMBER: 2322759 STATE OF FORMATION: DE
REPORT FOR THE FISCAL YEAR END: 12/31 /2021
SECTION A: REGISTERED AGENT'S INFORMATION
1. NAME OF REGISTERED AGENT: CT Corporation System
2. SIGNATURE OF THE NEW REGISTERED AGENT:
E - Filed Annual Report
2322759
CA202232100643
11 /17/2022 12:00
❑X Changes
SIGNATURE CONSTITUTES CONSENT TO THE APPOINTMENT
3. REGISTERED AGENT OFFICE STREET ADDRESS & COUNTY 4. REGISTERED AGENT OFFICE MAILING ADDRESS
160 Mine Lake Ct Ste 200 160 Mine Lake Ct Ste 200
Raleigh, NC 27615 Wake County Raleigh, NC 27615
SECTION B: PRINCIPAL OFFICE INFORMATION
1. DESCRIPTION OF NATURE OF BUSINESS: Battery R&D and Manufacturing Plant
2. PRINCIPAL OFFICE PHONE NUMBER: (469) 786-8361 3. PRINCIPAL OFFICE EMAIL: Privacy Redaction
4. PRINCIPAL OFFICE STREET ADDRESS
6565 Headquarters Dr
Plano, TX 75024
5. PRINCIPAL OFFICE MAILING ADDRESS
6565 Headquarters Dr
Plano, TX 75024
6. Select one of the following if applicable. (Optional see instructions)
❑ The company is a veteran -owned small business
❑ The company is a service -disabled veteran -owned small business
SECTION C: OFFICERS (Enter additional officers in Section E.)
NAME: Shinichi Yasui
TITLE: Caninr Vira Praciriant
ADDRESS:
6565 Headquarters Drive
Plano, TX 75024
NAME: Sean Suggs
TITLE: Pracirinnf
ADDRESS:
6565 Headquarters Drive
Plano, TX 75024
NAME: Thibaut De Barros Conti
TITLE: Secretary
ADDRESS:
6565 Headquarters Drive
Plano, TX 75024
SECTION D: CERTIFICATION OF ANNUAL REPORT. Section D must be completed in its entirety by a person/business
entit .
%inichi Yasui 11/17/2022
SIGNATURE
Form must be signed by an officer listed under Section C of this form.
Shinichi Yasui
Senior Vice President
DATE
Print or Type Name of Officer Print or Type Title of Officer
This Annual Report has been filed electronically.
MAIL TO: Secretary of State, Business Registration Division, Post Office Box 29525, Raleigh, NC 27626-0525
F)l
hdrinc.com
July 17, 2023
N.C. Department of Environmental Quality
Division of Water Resources
Winston-Salem Regional Office
450 West Hanes Mill Road
Suite 300
Winston-Salem, NC 27105
Re: Guilford/Randolph Megasite
TBMNC BEV Phase II Central Quad
15A NCAC 02T .0300 — Sewer Extension Application
HDR Project Number 10328292
NC Department of
Environmentzll (duality
Received
R._ 19 2102
Winston-Salem
Regional Office
On behalf of Toyota, enclosed please find the following permit application and supporting
documents for the TBMNC BEV Phase II Central Quad Project for your review and approval:
1. One original and one copy of the Fast Track Sewer System Extension Application
2. $480 Application Fee
3. Two (2) Copies of USGS Site Map
4. Two (2) Copies of Aerial Map
5. Certificate of Authority from Toyota
We are requesting to permit the 804 and 805 lift stations along with the associate piping to
convey the sewer to an offsite manhole owned by the City of Greensboro.
Should you have any questions or need additional information, please do not hesitate to contact
me.
Sincerely,
HDR Engineering, Inc., of the Carolinas
Matthew Watt, PE
Water/Wastewater Engineer
440 S Church Street, Suite 1200, Charlotte, NC 28202-2075
704.338.6700