HomeMy WebLinkAboutNC0029882_Inspection_20230809DocuSign Envelope ID: C281F979-706A-43E8-AFC4-B725498D605D
ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
� rs.5lATE o
5 7a
NORTH CAROLINA
Environmental Quality
SENT VIA ELECTRONIC MAIL ONL Y.• NO HARD COPY WILL BE MAILED.
August 28, 2023
Bertha S Burnette
Email: davideburnette@yahoo.com
SUBJECT: Compliance Inspection Report
Briarwood WWTP
NPDES WW Permit No. NCO029882
Buncombe County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Briarwood WWTP on
8/07/2023. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0029882. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Rachel Rose with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
rachel.rose@deq.nc.gov.
Sincerely,
Ev DocuSigned by:
SACE19D3940C494...
Rachel Rose, Environmental Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Laserfiche
Juanita James (ORC, James & James Environmental)
North Carolina Department of Environmental Quality I Divisionof Water Resources
Asheville Regional Office 12090 U.S. Highway 701 S—nano.. North Carolina 28778
828.2964500
DocuSign Envelope ID: C281F979-706A-43E8-AFC4-B725498D605D
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO029882 I11 121 23/08/07 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:OOAM 23/08/07
20/12/01
Briarwood WWTP
41 Dix Creek Rd
Exit Time/Date
Permit Expiration Date
Leicester NC 28748
10:OOAM 23/08/07
25/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Juanita Reed James/ORC/828-697-0063/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Bertha S Burnette,41 Dix Creek Rd #1 Leicester NC
28748//828-683-3791 /8286833967 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
D Sig tl by:
Mara G Chamlee ��.at^a. l6^,� DWR/ARO WQ/828-296-4500/ 8/28/2023
CA4697633A65o45A..
Rachel Rose DWR/ARO WQ/828-296-4500/
°°`°S� 9�'i: 8/28/2023
'�
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DucuSignetl by: 8/28/2023
Fau.it�, J°jbSS
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: C281F979-706A-43E8-AFC4-B725498D605D
NPDES yr/mo/day Inspection Type (Cont.)
NCO029882 I11 12I 23/08/07 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Rachel Rose and Mara Chamlee, with the Asheville Regional Office (ARO), met with Ms. Juanita
James (ORC, James & James Environmental) and Hannah Turner (General Manager, James & James
Environmental) for a Compliance Evaluation Inspection of the Briarwood WWTP on August 7, 2023.
This inspection was conducted to determine whether the facility is being operated and maintained in
compliance with NPDES Permit No. NC0029882.
This facility currently serves about 15 homes with an average flow of 1,000 gallons/day and appeared
to be in compliance with NPDES Permit No. NC0029882.
Page#
DocuSign Envelope ID: C281F979-706A-43E8-AFC4-B725498D605D
Permit: NCO029882 Owner -Facility: Briarwood WWTP
Inspection Date: 08/07/2023 Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: The process controls analyzed include MLSS, settleable solids, temperature, and pH.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Page# 3
DocuSign Envelope ID: C281F979-706A-43E8-AFC4-B725498D605D
Permit: NCO029882 Owner -Facility:
Inspection Date: 08/07/2023 Inspection Type:
Briarwood WWTP
Compliance Evaluation
Record Keeping
Yes
No
NA
NE
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment:
Bar Screens
Yes
No
NA
NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: The bar screens are manually scraped dail
Aeration Basins
Yes
No
NA
NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
■
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
Comment: The difffusers are set on an automatic timer cycle of 30 minutes on, 30 minutes off.
The settleability was recorded at approximately 65% or 350 mL/1000 mL at the time of
the inspection.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 4
DocuSign Envelope ID: C281F979-706A-43E8-AFC4-B725498D605D
Permit: NCO029882
Inspection Date: 08/07/2023
Owner -Facility: Briarwood WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier
Yes
No
NA
NE
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
M
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4
of the sidewall depth) ❑
0
❑
❑
Comment: The sludge blanket measured to be at 2.5 ft. out of 7ft. of water at the time of the
inspection. The facility pumps the sludge about once per year.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment: The aerobic digester tanks are buried with access holes above the ground.
Disinfection -Tablet
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Yes No NA NE
❑ ❑ ❑ ■
❑ ❑ ❑ ■
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
2
❑ ❑ ❑ ■
■ ❑ ❑ ❑
❑ ❑ ❑ ■
Comment: The ORC indicated that an extra tube is used when it rains to ensure proper
chlorination. Grease builds up in the chlorine chamber and is pumped back to the head
of the WWTP aDDroximately once a month alona with solids in the contact chamber.
De -chlorination
Yes No
NA
NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑ ❑
0
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
0 ❑
❑
❑
Comment:
Page# 5
DocuSign Envelope ID: C281F979-706A-43E8-AFC4-B725498D605D
Permit: NCO029882
Inspection Date: 08/07/2023
De -chlorination
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Owner -Facility: Briarwood WWTP
Inspection Type: Compliance Evaluation
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
1
Yes
No
NA
NE
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
Comment: A bucket and timer is used to measure the effluent. The average flow is about 1,000
gallons per day.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
❑
❑
■
❑
Is sample collected below all treatment units?
M
❑
❑
❑
Is proper volume collected?
❑
❑
0
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
■
❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
■
❑
❑
❑
representative)?
Comment: The permit requires grab samples.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment:
Standby Power
Yes
No
NA NE
Is automatically activated standby power available?
❑
0
❑ ❑
Is the generator tested by interrupting primary power source?
❑
❑
0 ❑
Is the generator tested under load?
❑
❑
■ ❑
Page# 6
DocuSign Envelope ID: C281F979-706A-43E8-AFC4-B725498D605D
Permit: NC0029882 Owner -Facility: Briarwood WWTP
Inspection Date: 08/07/2023 Inspection Type: Compliance Evaluation
Standby Power
Yes
No
NA
NE
Was generator tested & operational during the inspection?
❑
❑
0
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
❑
❑
0
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up
❑
❑
■
❑
power?
Is the generator fuel level monitored?
❑
❑
0
❑
Comment: A backup portable generator is on the property nearby to be used as needed. The
owner has an agreement to use the backup generator for the WWTP as needed.
Page# 7