HomeMy WebLinkAboutNC0044253_Notice of Violation_20230814ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Certified Mail # 7018 3090 0001 2322 7171
Return Receipt Requested
Tammy Thomas
North Carolina Lions Foundation Inc
PO Box 39
Sherrills Ford, NC 28673-0039
NORTH CAROLINA
Environmental Quality
August 14, 2023
SUBJECT: NOTICE OF VIOLATION
Tracking Number: NOV-2023-LV-0542
Permit No. NCO044253
Camp Dogwood WWTP
Catawba County
Dear Ms. Thomas:
A review of the June 2023 Discharge Monitoring Report (DMR) for the subject facility revealed the violation(s)
indicated below:
Limit Exceedance Violation(s):
Sample
Location Parameter
Limit Reported
Date Value Value Type of Violation
001 Effluent Solids, Total Suspended - 6/23/2023 45 54 Daily Maximum Exceeded
Concentration (CO530)
Remedial actions, if not already implemented, should be taken to correct any noted problems. The Division of
Water Resources may pursue enforcement actions for this and any additional violations. If the violations are of a
continuing nature, not related to operation and/or maintenance problems, and you anticipate remedial
construction activities, then you may wish to consider applying for a Special Order by Consent (SOC).
M Q-j
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue. Suite 301. 1 Mooresville, North Carolina 28115
704.663.1699
If you have any questions concerning this matter or to apply for an SOC, please contact Wes Bell of the
Mooresville Regional Office at 704-663-1699 or via Wes.Bell@deq.nc.gov.
Sincerely,
DocuSigned by:
fi�uw N P44-t
F161 FB69A2D84A3...
Andrew H. Pitner, P.G.
Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
Cc: WQS Mooresville Regional Office - Enforcement File (Laserfiche)
NPDES Compliance/Enforcement Unit - Enforcement File (Laserfiche)
�D- E Q7' �
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville. North Carolina 26115
704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO046213 111 121 23/08/02 I17 18 LC] I 19 I s I 201
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70LJ 71 I„ I 72 L.71 74 79 I I I I
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
12:47PM 23/08/02
21/11/01
Charlotte Terminal
8035 Mount Holly Rd
Exit Time/Date
Permit Expiration Date
Paw Creek NC 28130
01:12PM 23/08/02
25/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Maribeth D Hughes//704-458-3993 /
Matthew Joseph Brundage/ORC/704-523-4726/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Richard Voytek,8035 Mount Holly Rd Paw Creek NC 28130//812-350-9849/
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell signed by: DWR/MRO WQ/704-663-1699 Ext.2192/ 8/9/2023
Be&
E�Docu`,'c',96DMCC3437—
Signature of Mf�eviewer Agency/Office/Phone and Fax Numbers Date
Andrew Pit e�""�'`�`' H �"bWR/MRO WQ/704-663-1699 Ext.2180/ 8/9/2023
F161 FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO046213 I11 12I 23/08/02 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO046213 Owner -Facility: Charlotte Terminal
Inspection Date: 08/02/2023 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
M
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Outfall 001 consists of stormwater from the secondary containment structures (ASTs
and loading rack area. The stormwater from the loading rack area is treated by an
oil/water separator and combined with the discharge from the secondary containment
structures. The combined discharges flow through a holding pond equipped with a
discharge value that is normally secured in a locked position.
The holding tanks are not currently being used.
The last compliance evaluation inspection at this facility was performed by DWR staff
on 2/26/2020.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Page# 3
Permit: NCO046213 Owner -Facility: Charlotte Terminal
Inspection Date: 08/02/2023 Inspection Type: Compliance Evaluation
Record Keeping Yes No
NA NE
Comment: The records reviewed during the inspection were organized and well maintained.
Discharge Monitoring Reports (eDMRs) were reviewed for the period July 2022 through
June 2023. No limit violations were reported; however, the November 2022, January
2023 and March 2023 eDMRs were all not submitted by the last calendar day of the
month following the completed reporting period as required by the NPDES Permit [Part
1, Section A(4)(1) Reporting Requirementsl. This inspection report will be issued as a
Notice of Violation to address these reporting violations.
The facility staff will review and revise all applicable eDMRs starting in January 2022 to
correct several transcription errors including units of measurement, flow values, ORC
and/Backup ORC visitations (dates/times) and EPA Method 625 and toxicity results.
Facility staff must ensure all eDMRs are accurate and complete prior to submittal.
Laboratory Yes No
NA NE
Are field parameters performed by certified personnel or laboratory? ❑ ❑
0 ❑
Are all other parameters(excluding field parameters) performed by a certified lab? ■ ❑
❑ ❑
# Is the facility using a contract lab? 0 ❑
❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑
0 ❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑
0 ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑
■ ❑
Comment: Pace Analytical Services and ETT Environmental, Inc. (toxicity) have been contracted
to perform permit -required analyses. S&ME staff are contracted to collect effluent
samples.
Facility staff should notify the contracted laboratory to analyze future effluent total
recoverable phenolics samples at a lower detection limit (5 uq/L instead of 40 ug/L).
Analytical methods shall be in accordance with 40 CFR Part 136 and shall be
sufficiently sensitive to determine whether parameters are present in concentrations
greater than applicable standards and criteria.
Effluent Sampling
Yes
No
NA NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
M
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
■
❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
❑
❑
❑
representative)?
Comment: The subject permit requires effluent grab samples.
Facility staff must ensure that the effluent is collected directly into the oil &
grease
sample container (no intermediate sample containers/devices).
Page# 4
Permit: NCO046213
Inspection Date: 08/02/2023
Owner -Facility: Charlotte Terminal
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The NPDES facilities appeared to be properly operated and well maintained. The
entire facility (including NPDES facilities) is inspected on a daily basis by
the on -site
staff. STAT, Inc. would be contracted to remove and dispose of the free
product in the
oil/water separator.
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The flow from Outfall 001 is measured by an in -line flow meter. The flow meter will be
either calibrated annually (as was done under previous ownership) or a new factory
calibrated flow meter will be purchased every year.
The facility staff must ensure all effluent discharges are measured and reported on the
eDMRs.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ■ ❑
Comment: Outfall 001 was not discharging at the time of the inspection; however, no petroleum
sheens were observed in the holding pond.
Page# 5