HomeMy WebLinkAboutNC0062634_CEI_20230823DocuSign Envelope ID: CD7546ED-B8CF-4F46-B945-980C5010BBE5
STATE o
ROY COOPER
Governor
ELIZABETH S. BISER
Secretary �Q
RICHARD E. ROGERS, JR. NORTH CAROLINA
Director Environmental Quality
August 23, 2023
Kevin Hamlin
Wedgefield Acres Mobile Home Park
558 Pond Rd
Asheville, NC 28806
SUBJECT: Compliance Inspection Report
Wedgefield Acres MHP WWTP
NPDES WW Permit No. NCO062634
Buncombe County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Wedgefield Acres MHP
WWTP on 8/07/2023. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0062634. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Rachel Rose with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
rachel.rose@deq.nc.gov.
Sincerely,
DocuSigned by:
Ev
GL��i�
SACE19D3940C494...
Rachel Rose, Environmental Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Laserfiche
Juanita James, James & James Environmental
o.w�•ma.D; North Carolina Department of Environmental Quality l Division of Water Resources
Asheville Regional Office 1 2090 U.S. Highway 70 1 S—nanoa. North Carolina 28778
828.2964500
DocuSign Envelope ID: CD7546ED-B8CF-4F46-B945-980C5010BBE5
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0062634 I11 121 23/08/07 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:OOAM 23/08/07
21/03/01
Wedgefield Acres MHP WWTP
45 Wedgefield PI
Exit Time/Date
Permit Expiration Date
Asheville NC 28806
11:OOAM 23/08/07
25/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Juanita Reed James/ORC/828-697-0063/
Shannon D James/ORC/828-697-0063/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Kevin Hamlin,558 Pond Rd Asheville NC 28806H828-667-4560/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
0 Sg dby:
Mara G Chamlee4,gV�a, DWR/ARO WQ/828-296-4500/ 8/24/2023
CA4697633A65045A-
Rachel Rose DWR/ARO WQ/828-296-4500/
°D—S,gn.d by: 8/23/2023
Z
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
by:8/23/2023
FwD—Signed
ant 156ss
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: CD7546ED-B8CF-4F46-B945-980C5010BBE5
NPDES yr/mo/day Inspection Type (Cont.)
NCO062634 I11 12I 23/08/07 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Rachel Rose and Mara Chamlee, with the Asheville Regional Office (ARO), met with Ms. Juanita
James, Ms. Hannah Turner, and Ms. Shannon James for a Compliance Evaluation Inspection of the
Wedgefield MHP WWTP on August 7, 2023. This inspection was conducted to determine whether the
facility is being operated and maintained in compliance with NPDES Permit No. NC0062634.
Juanita James, Shannon James, and Hannah Turner were present during the inspection. Juanita is
currently in the process of switching the primary ORC from James Smith to Shannon James. Hannah
Turner is the General Manager.
The following items were noted during the inspection:
Equalization Basin: The equalization basin is an airlift system which does not require pumps, alarms,
or float controls. There is a straight pipe near the top of the basin that goes directly to the aeration
basin that acts as an overflow pipe. There was a considerable amount of grease, solids, and debris
built up on the surface with vegetation growing on top of the solids and debris. Juanita stated that the
facility owner cleans out the buildup three years. It is recommended that this buildup be cleaned out
more frequently. See pictures attached.
Secondary Clarifier: The sludge blanket was measured to be 8ft out of 9ft of water at the time of the
inspection; however, the facility was wasting solids to the digester at the time of the inspection.
Page#
DocuSign Envelope ID: CD7546ED-B8CF-4F46-B945-980C5010BBE5
Permit: NCO062634 Owner -Facility: Wedgefield Acres MHP WWTP
Inspection Date: 08/07/2023 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
■
❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
❑
■
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ■ ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Process controls analyzed include MLSS, settleable solids, and pH.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Page# 3
DocuSign Envelope ID: CD7546ED-B8CF-4F46-B945-980C5010BBE5
Permit: NCO062634 Owner -Facility:
Inspection Date: 08/07/2023 Inspection Type:
Wedgefield Acres MHP WWTP
Compliance Evaluation
Record Keeping
Yes
No
NA
NE
Is a copy of the current NPDES permit available on site?
■
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
■
❑
Comment:
Flow Measurement - Influent
Yes
No
NA
NE
# Is flow meter used for reporting?
❑
❑
■
❑
Is flow meter calibrated annually?
❑
❑
■
❑
Is the flow meter operational?
❑
❑
■
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
■
❑
Comment: Flow is measured from influent well. Usual flow is 9,000-11,000 gallons/day.
Bar Screens
Yes
No
NA
NE
Type of bar screen
a.Manual
■
b.Mechanical
❑
Are the bars adequately screening debris?
■
❑
❑
❑
Is the screen free of excessive debris?
■
❑
❑
❑
Is disposal of screening in compliance?
■
❑
❑
❑
Is the unit in good condition?
■
❑
❑
❑
Comment:
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
■
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
■
❑
❑
❑
Is the basin free of excessive grease?
❑
■
❑
❑
Are all pumps present?
❑
❑
■
❑
Are all pumps operable?
❑
❑
■
❑
Are float controls operable?
❑
❑
■
❑
Are audible and visual alarms operable?
❑
❑
■
❑
# Is basin size/volume adequate?
■
❑
❑
❑
Page# 4
DocuSign Envelope ID: CD7546ED-B8CF-4F46-B945-980C5010BBE5
Permit: NCO062634 Owner -Facility: Wedgefield Acres MHP WWTP
Inspection Date: 08/07/2023 Inspection Type: Compliance Evaluation
Equalization Basins Yes No NA NE
Comment: The equalization basin is an airlift system which does not require pumps, alarms, or
float controls. There is a straight pipe near the top of the basin that goes directly to the
aeration basin that acts as an overflow pipe. There was a considerable amount of
grease, solids, and debris built up on the surface with vegetation growing on top of the
solids and debris. See summary for details.
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Yes No NA NE
Ext. Air
Diffused
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑ ■
Comment: Settleability was recorded as 30% or 700 mL/1000 mL at the time of the inspection.
The diffusers are run in an automatic cyle of 30 minutes on, 30 minutes off.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
IiY-To I[•7►/_W0I=
■
❑
❑
❑
❑
❑
■
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
❑
❑
■
❑
•
❑
❑
❑
•
❑
❑
❑
❑
■
❑
❑
Comment: The sludqe blanket was measured to be 8ft out of 9ft of water at the time of the
inspection; however, the facility was wasting solids to the digester at the time of the
inspection. Sludge from the secondary clarifier is pumped when the aerobic digester
and solids retaining baffle are pumped. Facility was last pumped on June 3, 2023 by
Able Septic Tank Service.
Page# 5
DocuSign Envelope ID: CD7546ED-B8CF-4F46-B945-980C5010BBE5
Permit: NCO062634
Inspection Date: 08/07/2023
Owner -Facility: Wedgefield Acres MHP WWTP
Inspection Type: Compliance Evaluation
Aerobic Digester
Yes
No
NA
NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
❑
❑
❑
Is the site free of excessive foaming in the tank?
❑
❑
❑
■
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
M
❑
❑
❑
Comment: Blowers were off at the time of the inspection. The facilitv currentiv wastes about once
every 2 weeks. The digester and baffle are pumped about once every
6 months. Last
pumpted on June 3, 2023 by Able Septic Tank Service.
Disinfection -Tablet
Yes
No
NA
NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
■
❑
❑
❑
Number of tubes in use? 2
Is the level of chlorine residual acceptable? ❑ ❑ ❑
Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑
Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑
Comment: Solids built up in the contact chamber are also pumped when the aerobic digester is
pumped. At the time of the inspection, one of the tablet contact tubes had a missing
cover. It is recommended that all of the tablet tubes be covered.
De -chlorination
Yes No
NA
NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑ ❑
0
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
0 ❑
❑
❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? ■ ❑ ❑ ❑
Number of tubes in use? 2
Comment: It is recommended that all of the tablet tubes be covered.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
❑
❑
■
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Page# 6
DocuSign Envelope ID: CD7546ED-B8CF-4F46-B945-980C5010BBE5
Permit: NCO062634 Owner -Facility: Wedgefield Acres MHP WWTP
Inspection Date: 08/07/2023 Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Is the tubing clean? ❑ ❑ ■ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ ■ ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type ■ ❑ ❑ ❑
representative)?
Comment: The permit requires grab samples.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
■
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
■
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
■
❑
Comment:
Standby Power
Yes
No
NA
NE
Is automatically activated standby power available?
❑
❑
■
❑
Is the generator tested by interrupting primary power source?
❑
❑
■
❑
Is the generator tested under load?
❑
❑
■
❑
Was generator tested & operational during the inspection?
❑
❑
■
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
❑
❑
■
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up
❑
❑
■
❑
power?
Is the generator fuel level monitored?
❑
❑
■
❑
Comment: No backup power on site, but the MHP is on well water. Therefore, if the site were
to
lose power, the facility would not be receiving influent flow.
Page# 7
- �.._
ti
L �.�
..
_ _ - *„_
„}T _y ...
-�F. �..-- � J W,
� � -"
,�`
t".
t �
� � Jr�
� .f` a d % j `f' I'.
ni
a
��. '� t � s
c � �r �;{
r
r�
j_
�
' �Y
• � ' /I
�w* �� .�
�, � e
_ .d� -!,�
r�
<_
�, � - �
','; � .