August 1, 2001
CERTIFIED MAIL
RETURN RECEIPT REQUESTED
Mr. Ray Hollowell, Jr., Manager
Outer Banks/ Kinnakeet Associates, LLC
Post Office Box 1411
Manteo, North Carolina 27954
William G. Ross Jr, Secretary
Depart rent of Environment and Nahual Resources
Kerr T. Stevens, Director
Division of Water Quality
Subject: NOTICE OF VIOLATION
COMPLIANCE EVALUATION INSPECTION
Non -Discharge Wastewater Rotary Distributor Facilities
Kinnakeet Shores
Non -Discharge Permit No. WQ0002284
Dare County
Dear Mr. Hollowell:
Enclosed please find a copy of the Non -Discharge Compliance Inspection Report from the inspection
conducted on March 16, 2001. The Compliance Inspection was conducted by Ms. Kim Cole of the
Washington Regional Office. A review of the records and the wastewater treatment facility revealed that
the Outer Banks/ Kinnakeet Associates, LLC was in violation of non -discharge permit WQ0002284 for the
following:
l . Part II, item I requires that the facilities shall be properly maintained and operated at all times.
• The paint on the wastewater treatment tanks has peeled off leaving bare tanks that are rusting.
• Diffusers in the equalization basin are rusted. These need to be replaced or repaired.
• The spacing between the bars of the barscreen is too large. This is allowing large solids to pass
through the barscreen that cannot be broken down in the treatment process.
• The air scour in the backwash cycle of the tertiary filters is inadequate. Solids had accumulated in
the filters and the backwash cycle did not provide enough air scouring to remove the solids. The
diffusers should be inspected and rehabilitated as required.
• The diffusers in the digester are rusted. These should be repaired or replaced_
• The effluent flowmeter is inadequate. It is not maintaining calibration. The flowmeter had not
been calibrated at the time of the inspection, but a certification form was submitted to the Division
stating that the flowmeter was calibrated on April 21, 2001. According to 15A NCAC 2B .0505
(b) (1), a certification for calibration shall include percent deviation from actual flow.
• The southwest rotary distributor was not adequately operational at the time of the inspection.
Wastewater was applied to the field, but the rotary distributor did not rotate. This could lead to
ponding and potentially the discharge of wastewater outside of the high rate infiltration disposal
area.
943 Washington Square Mall Washington, NC 27889 252-946-6481 (Telephone) 252-946-9215 (Fax)
t
State of North Carolina
Department of Environment
and Natural Resources •' •
Division of Water Quality
Michael F. Easley, Governor
William G. Ross, Jr., Secretary
Kerr T. Stevens Director NCDENR
Norm I C -io_ KA Q; lm-n ENT of
ENVIaf W04T AND Nbr.h2AL F'iC' MjRCL,j
Non -Discharge Compliance. Inspection
WQ Permit Number WQ0002284
Permittee
-Outer Banks Klnnakeet Assoc
Issuance Date
6/16/2000
Expiration Date
9/30/2001
Soc Issuance Date
Permittee Contact
Ray Hollowell Jr
ORC Certification #
ORC Name
Jim Coleman
24hr'6ontact Name
Jim Coleman
County pare
Npdes Number(s)
Soc ExpirationDate
Phone Permittee Contact (252) 995-3511
Phone ORC (252) 995-6827
Phone 24hr (252) 480-7864
Reason For Inspection (Select One) 10 Routine O Complaint p Follow -Up -O Other...
Type Of Inspection (Select One) 10 Collection System *Spray Irrigation Q'Residual
Inspection Summary
�._W.�..�art II- item 1.Iir� mat_ttilltl���f�ayll_b�..�rs�s�c.m�alnt�l�a�d..aasi.�r�t�.�S.;all.
The permit requires that the effluent shall be monitored at the point prior to discharge t
Inspector's Name Kimberly H. Cole
01 Inspector's Title Environmental Specialist II
Phone Inspector (252) 946-6481 Fax Inspector. (252) 946-9215
Inspection Date 3/16/2001 R���_�
"".A—
CL- G
page
Non Discharge Compliance Spray Irrigation Inspection
Barscreen
Was it maintained?
Was it free of excessive debris?
Were the bars evenly spaced?
Were the bars free of excessive corrosion?
Aeration Basin
Permittee Puter Banks Kinnakeet Assoc
Permit Number Q0002284
Inspection Date 1612001
*Yes ONO ON/
O Yes O No 0 NI
OO Yes O No O N/
O Yes Q No O N/
Was the aeration patter even across surface of unit? Yes O No O N/
Was it easily accessed? 0 Yes O No O W
Clarifiers
Were the weirs level? Yes O No O N/
Was the scum rack operational? Q Yes O No O N/
Was it easily accessed? *Yes O No O N/
Return Pumps
Were they in place? O Yes O No O N/
Were they operational? *Yes 0 No O N/
Filters
Was the filter media present?
Was the air scour operational?
Was the clear well free of excessive solids?
Sludge Storage/ Treatment
Was the aeration operational?
Was the aeration patter even?
If required are Sanitary'Ts" present in tankage?
Disinfection
Storage
If gas, was cylinder storage safe?
Is it a dual feed system?
Was the system working?
If tablets:
Were tablets present?
0 Yes O No O N/
O Yes 00 No O N/
0 YesO No O N/
O Yes O No O N/
Yes O No O W
O Yes O No * N/
O Yes O No * N/
O Yea O No * N/
Yes O No O N/
W Yes O No 0 N/M
❑ Lagoon ❑ AST ❑ UST ❑ Septic Tank ❑ Drying Beds ❑ Concrete Storage Pads
How many months storage?
Was spill control plan on site?
If Applicable:
Is lagoon lined?
Above Ground Tank O Aerated ❑ Mixed Aerated Hp:
Under Ground Tank O Aerated ❑ Mixed Aerated Hp:
O Yes O No
O Yes 0 N
Mixed Hp:
Mixed Hp: