HomeMy WebLinkAboutWQ0009267_Compliance Evaluation Inspection_20230815DocuSign Envelope ID: F86F1592-6ABA-4A4C-89FB-9A014923BF5D
Compliance Inspection Report
Permit: WQ0009267 Effective: 10/07/22 Expiration: 07/31/29 Owner: City of Jacksonville
SOC: Effective: Expiration: Facility: City of Jacksonville WWTF
County: Onslow 716 Firetower Rd
Region: Wilmington
Jacksonville NC 28540
Contact Person: Amy Elizabeth Palaschak Title: Supervising Chemist Phone: 910-938-3620
Directions to Facility:
Take Hwy. 17 North to south Jacksonville area. Turn left on NCSR 1113. This road turns into NCSR 1212. Turn left on NCSR 1211,
and travel approximately 2 miles. The WWTF is on the left.
System Classifications: SI,
Primary ORC: Brandon Douglas Davis Certification: 1002072 Phone: 910-330-6308
Secondary ORC(s):
On -Site Representative(s):
On -site representative Brandon Douglas Davis
Related Permits:
WQCS00268 City of Jacksonville - Jacksonville Collection System
Inspection Date: 08/15/2023 Entry Time 09:30AM
Primary Inspector: Helen I Perez DocuSignetd�by:
Secondary Inspector(s):L n
1 D645B4A39694BE...
by:
Geoff Keglet�DOGUSIgned
Reason for Inspection: Routine o 515MB417 .
Permit Inspection Type: Wastewater Irrigation
Facility Status: 0 Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent
Treatment Flow Measurement -Water
Use Records
Record Keeping
Treatment Flow Measurement
(See attachment summary)
Exit Time: 12:OOPM
910-330-6308
Phone: 910-796-7387
Phone :
Inspection Type: Compliance Evaluation
Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Treatment Barscreen
End Use -Irrigation
Treatment Disinfection
Page 1 of 6
DocuSign Envelope ID: F86F1592-6ABA-4A4C-89FB-9A014923BF5D
Permit: WQ0009267 Owner - Facility: City of Jacksonville
Inspection Date: 08/15/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine inspection of the City of Jacksonville WWTF was conducted on August 15, 2023. The purpose of the evaluation
was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit WQ0009267.
Brandon Davis, ORC, and Amy Palaschak, Supervising Chemist, were present during the inspection. Wally Hansen, Public
Services Director, met with us prior to the inspection for an update on plant/spray operations and plans for an up -coming
permit modification submittal.
The City of Jacksonville's lagoon/spray irrigation site is permitted to treat 9 MGD, and in June of this year, averaged 4.6
MGD. The City's 7,400 acre Land Treatment Site (LTS) consists of the irrigation of 2,300 acres of primarily Loblolly pine
trees. Currently, wastewater is transported to the plant by a 36-inch force main. The City's Western Regional Project
involves a phase that will add a 36-inch force main from Pony Farm Road to the plant, parallel to the existing line, for
treatment of wastewater from the western side of the City. The Hydogen Peroxide odor removal system will be upgraded
during this phase.
There was a discussion of the placement of some of the monitoring wells at the plant site and the LTS during the inspection
There are monitoring wells that do not appear to be located at the review or compliance boundaries. It would be beneficial for
the City to evaluate the well locations and submit any change requests in the future permit modification.
The facility is compliant with Non -Discharge Permit WQ0009267. Please review the comment sections of the inspection
report for more details.
Page 2 of 6
DocuSign Envelope ID: F86F1592-6ABA-4A4C-89FB-9A014923BF5D
Permit: WQ0009267 Owner - Facility: City of Jacksonville
Inspection Date: 08/15/2023 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Infiltration System
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
❑
Single Family Drip
❑
Lagoon Spray, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: No comment.
Treatment Flow Measurement -Influent Yes No NA NE
Is flowmeter calibrated annually? 0 ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑
Comment: The influent flowmeter, used for reporting, was last calibrated in November 2022 by John
Glover.
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ 1:10 ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent Yes No NA NE
Is flowmeter calibrated annually? 0 ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? ❑ ❑ ❑ ❑
Comment: The effluent flowmeter used for irrigation calculations was calibrated in November 2022 by
John Glover.
Page 3 of 6
DocuSign Envelope ID: F86F1592-6ABA-4A4C-89FB-9A014923BF5D
Permit: WQ0009267 Owner - Facility: City of Jacksonville
Inspection Date: 08/15/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Treatment Barscreen
Is it free of excessive debris?
Is disposal of screenings in compliance?
Are the bars spaced properly?
Is the unit in good condition?
Comment: The influent is treated with hydrogen peroxide for odor removal prior to enterinq the
Yes No NA NE
■❑❑❑
■❑❑❑
❑❑❑■
■❑❑❑
headworks. The headworks facility consists of 3 Huber step screens and an aerated grit and
grease removal system. Screenings and grit are collected in dumpsters and hauled to the City
landfill. Oil/grease is removed yearly. From the headworks, wastewater flows to 3 mechanically
aerated, multi -cellular biological treatment lagoon trains. From the treatment lagoons, a splitter
box is used to control the effluent flow to the 3 storage lagoons. The City plans to dredge and
remove solids from train 3 in the near future.
Treatment Disinfection
Yes No NA NE
Is the system working?
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑ ❑ ❑
Is there adequate detention time (-30 minutes)?
❑
❑ ❑
Is the system properly maintained?
❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ ❑
Is the chlorinator accessible?
❑
❑ ❑
If tablets, are tablets present?
❑
❑ ❑
Are the tablets the proper size and type?
❑
❑ ❑
Is contact chamber free of sludge, solids, and growth?
❑
❑ ❑
If UV, are extra UV bulbs available?
❑
❑ ❑
If UV, is the UV intensity adequate?
❑
❑ ❑
# Is it a dual feed system?
❑
❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment: The chlorine scrubbers have been recently replaced with the same system as before.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑ ❑ ❑
NDAR?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
0
❑ ❑ ❑
Page 4 of 6
DocuSign Envelope ID: F86F1592-6ABA-4A4C-89FB-9A014923BF5D
Permit: WQ0009267 Owner - Facility: City of Jacksonville
Inspection Date: 08/15/2023 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Is GW monitoring being conducted, if required (GW-59s submitted)?
0
❑ ❑ ❑
Are all samples analyzed for all required parameters?
0
❑ ❑ ❑
Are there any 2L GW quality violations?
❑
❑ 0 ❑
Is GW-59A certification form completed for facility?
0
❑ ❑ ❑
Is effluent sampled for same parameters as GW?
0
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
0 ❑ ❑
Are annual soil reports available?
0
❑ ❑ ❑
# Are PAN records required?
❑
0 ❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
0
❑ ❑ ❑
Are lab sheets available for review?
❑
❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
0
❑ ❑ ❑
Were Operational and Maintenance records complete?
0
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑
❑ ❑
Is a copy of the SOC readily available?
❑
❑ 0 ❑
No treatment units bypassed since last inspection?
0
❑ ❑ ❑
Comment: Operation and maintenance records are lopped and monitored using a workorder GIS
software. This system tracks the operations of the plant and the spray irrigation in real time.
The City has added more details to the software since the last inspection and continues to
refine the system. The facility lab is State certified (# 128) to analyze BOD, solids, ammonia,
Total Phosphorus, fecal coliform and field parameters. Envirochem Lab is contracted to analyze
the remaining parameters.
End Use-Irriqation
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
Yes No NA NE
■❑❑❑
■❑❑❑
❑ ❑ ❑
❑ ❑ ❑
❑❑❑■
❑❑❑■
❑❑❑■
Page 5 of 6
DocuSign Envelope ID: F86F1592-6ABA-4A4C-89FB-9A014923BF5D
Permit: WQ0009267 Owner - Facility: City of Jacksonville
Inspection Date: 08/15/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
How close is the closest water supply well? ❑ ❑ ❑
Is municipal water available in the area? 0 ❑ ❑ ❑
# Info only: Does the permit call for monitoring wells? 0 ❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB? ❑ 0 ❑ ❑
Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑
Are monitoring wells damaged? ❑ ❑ ❑
Comment: The LTS totals 7,400 acres of land and sprays on 2,300 acres, divided into 9 zones of primarily
loblolly pine trees. Premier Forestry is contracted to manage the trees for optimal health and
function. Zones 3, 4 and 5 were inspected and appeared to be well maintained. Staff mows
around the spray lines twice a year and keeps the drainage ditches clear of debris. The
freeboard of the East Storage Lagoon was 9ft, the West Storage Lagoon was 8.2ft and the
South Storage Lagoon was 10.2ft. The liners for the storage lagoons are inspected/repaired
quarterly. Monitoring Well #3 has had the presence of Touene and p-Isopropyltoluene. The
general area of this well was observed during the inspection and found to be in between spray
fields and not at the review or compliance boundries. Sampling techniques were discussed with
City staff. The Wilmington Regional Office will continue to watch trends.
Page 6 of 6