Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 u 3 I NC0037834 111 121 23/06/29 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I ni I 73 � I 74 79 I I I I I I I80
70 I I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:OOAM 23/06/29
17/08/01
Archie Elledge WWTP
2801 Griffith Rd
Exit Time/Date
Permit Expiration Date
Winston Salem NC 271036417
12:30PM 23/06/29
22/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Matthew Richard Lavigne/ORC/336-397-7600/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Jon M Southern,2801 Griffith Rd Winston Salem NC
271036417//336-397-7600/3366594320 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Operations & Maintenar 0 Records/Reports Sludge Handling Dispo:
Facility Site Review 0 Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
GarDv Hudson DWR/Division of Water Qua Iity/336-776-9694/
by:
ocuSigned
aarQsbt& 8/2/2023
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
by:
8/4/2023
FDocuSigned
ti -T. 15 ,,dcr
EPA Form Y96&-flfev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO037834 I11 12I 23/06/29 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
July 19, 2023 — Inspection Summary — NC0037834
On June 29, 2023, Division of Water Resources staff Gary Hudson conducted a routine compliance
inspection at the Archie Elledge WWTP. Bonnie McKee and Matthew Lavigne were present during the
inspection. A review of the October 2022, and April 2023 eDMR was compared to laboratory bench
sheets. No discrepancies were noted. During the inspection, no violations or items of concern were
noted. The following treatment components were inspected:
Permit
The permit became effective on August 1, 2017, and expired on June 30, 2022. A renewal application
was submitted on December 28, 2021.
Odor Control:
The Archie Elledge WWTP has six carbon air scrubbers for odor control. Four are located at the
influent/preliminary treatment, one is located at the primary clarifiers, and one is located at the sludge
thickener. Carbon is replaced yearly. All units were operating properly during the inspection.
Preliminary Treatment:
Preliminary treatment consists of two mechanical bar screens, two grit classifiers, and two cyclone grit
chambers. All six units are rated at a maximum capacity of 50 million gallons pr day (MGD). All units
were operating properly during the inspection.
Primary Treatment:
Primary treatment consists of four large primary clarifiers. All units were operating properly during the
inspection.
Secondary Treatment:
Secondary treatment consists of activated sludge basins, and six secondary clarifiers. All units were
operating properly during the inspection. Magnesium hydroxide is used for pH adjustment when
needed.
Final Effluent:
Sodium hypochlorite is used for disinfection and sodium bisulfate is used for de -chlorination. The
effluent composite sampler is set to collect 140 ml sample every 28 pulses. The refrigerator
temperature was 5 degrees centigrade.
Sludge Digestion:
Sludge digestion consists of six floating cover anaerobic digesters.
Sludge Handling and Disposal:
All sludge is run through a gravity belt thickener before it enters the anaerobic digesters. After
digestion, the sludge is run through a dryer and turned into pellets. All of the dried pellets are sold to
a private contractor to be used as fertilizer.
Page#
Permit: NCO037834 Owner -Facility: Archie Elledge WWTP
Inspection Date: 06/29/2023 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The permit became effective on August 1, 2017, and expired on June 30, 2022.
A
renewal application was submitted on December 28, 2021.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: Ms. McKee, Mr. Lavigne, and the rest of the staff do a very good lob with keeping
records.
A review of the October 2022, and April 2023 eDMR was compared to laboratory bench
sheets. No discrepancies were noted.
Page# 3
Permit: NCO037834
Inspection Date: 06/29/2023
Owner -Facility: Archie Elledge WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The WWTP appeared to be well operated and maintained. No discrepancies were
noted during the inspection.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Yes No NA NE
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Preliminary treatment consists of two mechanical bar screens, two grit classifiers, and
two cyclone grit chambers. All six units are rated at a maximum capacity of 50 million
_gallons pr day (MGD). All units were operating properly during the inspection.
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The Archie Elledge WWTP has six carbon air scrubbers for odor control. Four are
located at the influent/preliminary treatment, one is located at the primary
clarifiers,
and one is located at the sludge thickener. Carbon is replaced yearly. All units were
operating properly during the inspection.
Primary Clarifier
Yes
No
NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Page# 4
Permit: NCO037834
Inspection Date: 06/29/2023
Owner -Facility: Archie Elledge WWTP
Inspection Type: Compliance Evaluation
Primary Clarifier
Yes
No
NA
NE
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the sludge blanket level acceptable?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4
of the sidewall depth) ❑
❑
❑
Comment: Primary treatment consists of four large primary clarifiers. All units were operating
properly during the inspection.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
0
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
■
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
Comment: Secondary treatment consists of activated sludge
basins, and six secondary clarifiers.
All units were operating properly during the inspection.
Magnesium hydroxide is used
for pH adjustment when needed.
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
■
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
■
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
■
❑
❑
❑
Is scum removal adequate?
■
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
■
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
❑
❑
❑
Page# 5
Permit: NC0037834
Inspection Date: 06/29/2023
Secondary Clarifier
Owner -Facility: Archie Elledge WWTP
Inspection Type: Compliance Evaluation
Comment: All six secondary clarifiers appeared to be well maintained.
Anaerobic Digester
Type of operation:
Is the capacity adequate?
# Is gas stored on site?
Is the digester(s) free of tilting covers?
Is the gas burner operational?
Is the digester heated?
Is the temperature maintained constantly?
Is tankage available for properly waste sludge?
Comment: Sludge digestion consists of six floating cover anaerobic digesters.
Yes No NA NE
Yes
No
NA NE
Floating cover
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑