Compliance Inspection Report
Permit: WQ0000165 Effective: 05/01/21 Expiration: 06/30/27 Owner : Sands Villa Utilities Inc
SOC: Effective: Expiration: Facility: Sands Villa WWTP
County: Carteret 1400 E Fort Macon Rd
Region: Wilmington
Atlantic Beach NC 28512
Contact Person: Hope Mazzeo Title: Property Manager Phone: 252-247-0519
Directions to Facility:
System Classifications: WW3.,
Primary ORC: Drew Boyd Piner
Secondary ORC(s):
On -Site Representative(s):
On -site representative
Related Permits:
Certification: 1009727
Donald P Omara
Phone: 252-726-1366
252-247-9167
Inspection Date: 07/26/2023 Entry Time 10:50AM Exit Time: 11:40AM
Primary Inspector: Helen I Perez ° e�e Phone: 910-796-7387
AtZ�
Secondary Inspector(s):
1 D645B4A39694BE...
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Treatment Barscreen
Use Records
Treatment Filters Record Keeping Treatment Activated Sludge
Treatment Influent Pump Station Treatment Disinfection End Use -Infiltration
Treatment Flow Measurement Standby Power
(See attachment summary)
Page 1 of 7
DocuSign Envelope ID: 5AODEFBD-El20-404D-9602-68COE8DE11 FC
Permit: WQ0000165 Owner - Facility: Sands Villa Utilities Inc
Inspection Date: 07/26/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine inspection of the Sands Villa WWTF was conducted on July 26, 2023. The purpose of the
evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
WQ0000165. Don O'Mara was present during the inspection.
This facility is a 43,000 GPD, dual Sequencing Batch Reactor (SBR) system with two high -rate infiltration disposal fields.
The flow averaged 7,647 GPD in May, and peaked at approximately 20,000 GPD on the July 4th weekend. A new SBR
screen/program is now float activated and only operates when the wastewater reaches an optimal level for treatment.
A review of records show that there has been no effluent violations since the last inspection in March 2021. The monitoring
wells have had some TDS and Chloride exceedances, but likely attributable to background concentration of a barrier island
environment. Since the start-up of the new BNR plant in 2008, nitrate exceedances have improved. The last exceedance waE
in MW-6 in July 2022.
The facility is compliant with Non -Discharge Permit WQ0000165. Please review the comment sections of the inspection
report for more details.
Page 2 of 7
DocuSign Envelope ID: 5AODEFBD-El20-404D-9602-68COE8DE11 FC
Permit: WQ0000165 Owner - Facility: Sands Villa Utilities Inc
Inspection Date: 07/26/2023 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Lagoon Spray, LR
❑
Reuse (Quality)
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
❑
Single Family Drip
❑
Infiltration System
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: No comment.
Treatment Influent Pump Station
Yes No NA NE
Is the pump station free of bypass lines or structures?
0
❑ ❑ ❑
Is the general housekeeping acceptable?
❑ ❑ ❑
Are all pumps present?
❑ ❑ ❑
Are all pumps operable?
❑ ❑ ❑
Are floats/controls operable?
❑
❑ ❑
Are audio and visual alarms available?
0
❑ ❑ ❑
Are audio and visual alarms operational?
❑
❑ ❑
# Are SCADA/Telemetry alarms required?
❑ ❑ ❑
Are SCADA/Telemetry available?
❑ ❑ ❑
Are SCADA/Telemetry operational?
❑
❑ ❑
Comment: The pumps have been recently replaced.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ 0❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment:
Treatment Flow Measurement -Water Use Records Yes No NA NE
Page 3 of 7
DocuSign Envelope ID: 5AODEFBD-El20-404D-9602-68COE8DE11 FC
Permit: WQ0000165 Owner - Facility: Sands Villa Utilities Inc
Inspection Date: 07/26/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement -Effluent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment: The effluent flowmeter was calibrated in May by Delta Systems Environmental.
Standby Power
Is automatically activated standby power available?
Is generator tested weekly by interrupting primary power source?
Is generator operable?
Does generator have adequate fuel?
Comment: No comment.
❑❑■❑
❑❑■❑
Yes No NA NE
■❑❑❑
■❑❑❑
■❑❑❑
Yes No NA NE
Treatment Barscreen
Yes No NA NE
Is it free of excessive debris? ❑ ❑ ❑
Is disposal of screenings in compliance? ❑ ❑ ❑
Are the bars spaced properly? ❑ ❑ ❑
Is the unit in good condition? 0 ❑ ❑ ❑
Comment: Influent flows through the manually cleaned bar screen as it enters the EQ tank. The high-level
alarm for the EQ tank was tested and found to be operable.
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable? 0 ❑ ❑ ❑
Is the aeration basin thoroughly mixed? 0 ❑ ❑ ❑
Is the aeration equipment easily accessed? ❑ ❑ ❑
Is Dissolved Oxygen adequate? ❑ ❑ ❑
Are Settleometer results acceptable? ❑ ❑ ❑
Is activated sludge an acceptable color? 0 ❑ ❑ ❑
Comment: From the EQ tank, influent flows through a splitter box to dual train SBRs. Process control
testing consists of a settleometer test and a visual color nitrate test once a week, or more if
needed. Micro-C is added as an additional carbon source. Solids are removed from the sludge
holding tank by Barnes Environmental.
Treatment Filters
Is the filter media present?
/ ]r- ]..�.1N
■❑❑❑
Page 4 of 7
DocuSign Envelope ID: 5AODEFBD-El20-404D-9602-68COE8DE11 FC
Permit: WQ0000165 Owner - Facility: Sands Villa Utilities Inc
Inspection Date: 07/26/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Is the filter media the correct size and type? 0 ❑ ❑ ❑
Is the air scour operational? ❑ ❑ 0 ❑
Is the scouring acceptable? ❑ ❑ 0 ❑
Is the clear well free of excessive solids? 0 ❑ ❑ ❑
Is the mud well free of excessive solids and filter media? ❑ ❑ 0 ❑
Does backwashing frequency appear adequate? ❑ ❑ 0 ❑
Comment: From the SBRs, wastewater flows to the post EQ, then to dual Pyradeck upflow filters which are
manually cleaned as needed.
Treatment Disinfection
Yes No NA NE
Is the system working?
0
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑ ❑ ❑
Is there adequate detention time (>=30 minutes)?
❑
❑ ❑
Is the system properly maintained?
❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ ❑
Is the chlorinator accessible?
❑
❑ ❑
If tablets, are tablets present?
❑
❑ ❑
Are the tablets the proper size and type?
❑
❑ ❑
Is contact chamber free of sludge, solids, and growth?
❑
❑ ❑
If UV, are extra UV bulbs available?
❑ ❑ ❑
If UV, is the UV intensity adequate?
❑
❑ ❑
# Is it a dual feed system?
❑
❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1 000--_
If yes, then when was the RMP last updated?
Comment: Disinfection consists of dual Trojan UV units.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑
❑ ❑
NDAR?
❑
❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Page 5 of 7
DocuSign Envelope ID: 5AODEFBD-El20-404D-9602-68COE8DE11 FC
Permit: WQ0000165 Owner - Facility: Sands Villa Utilities Inc
Inspection Date: 07/26/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Are there any 2L GW quality violations?
❑
0 ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
0
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
0 ❑ ❑
Are annual soil reports available?
❑
❑ 0 ❑
# Are PAN records required?
❑
❑ 0 ❑
# Did last soil report indicate a need for lime?
❑
❑ 0 ❑
If so, has it been applied?
❑
❑ 0 ❑
Are operational logs present?
0
❑ ❑ ❑
Are lab sheets available for review?
❑
❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
0
❑ ❑ ❑
Were Operational and Maintenance records complete?
0
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
0
❑ ❑ ❑
Is a copy of the SOC readily available?
❑
❑ 0 ❑
No treatment units bypassed since last inspection?
0
❑ ❑ ❑
Comment: Operation and maintenance records were available for review and were found to be complete.
A review of records show some Chloride and TDS exceedances in MWs #3,
#4 and #6.
Monitoring well #6 has had a history of Nitrate exceedances, but since the start of the new
BNR plant in 2008, there's been much improvement. The last Nitrate exceedance was in July
2022.
End Use -Infiltration
Yes No NA NE
# Is the application High Rate or Low Rate?
High Rate
Are buffers maintained?
0
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
Is municipal water available in the area?
❑
❑ ❑
Are GW monitoring wells required?
0
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
0
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Is a usable green area maintained?
❑
❑ 0 ❑
Is the disposal site acceptable?
0
❑ ❑ ❑
Is the distribution equipment acceptable?
0
❑ ❑ ❑
Is the disposal site free of ponding?
0
❑ ❑ ❑
Is the disposal site free of breakout?
0
❑ ❑ ❑
Are the disposal sites free of solids, algae, etc.?
0
❑ ❑ ❑
Page 6 of 7
DocuSign Envelope ID: 5AODEFBD-El20-404D-9602-68COE8DE11 FC
Permit: WQ0000165 Owner - Facility: Sands Villa Utilities Inc
Inspection Date: 07/26/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Do the records show that the fields are properly maintained? 0 ❑ ❑ ❑
Are the disposal sites free of vegetation? ❑ 0 ❑ ❑
Do any surface water features appear to be adversely impacted by GW discharge? ❑ ❑ 0 ❑
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.? 0 ❑ ❑ ❑
Comment: The 2 infiltration fields have some vegetation and has been allowed in the past. The effluent
dosing tank high-level alarm was tested and found to be operable.