Loading...
HomeMy WebLinkAboutWQ0003090_Compliance Evaluation Inspection_20230728ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director NORTH CAROLINA Environmental Quality July 27, 2023 CERTIFIED MAIL No. 7019 1120 0001 5504 9791 RETURN RECEIPT REQUESTED Scott Kidd — Town Manager Town of Liberty P.O. Box 1006 Liberty, NC 27298 SUBJECT: Notice of Violation and Intent to Enforce (NOV-2023-PC-0406) Compliance Evaluation Inspection Liberty WWTF Permit No. WQ0003090 Randolph County izx�a►�r�:frraa On July 20, 2023, Division of Water Resources staff Caitlin Caudle and Kristen Potwora completed a routine compliance inspection. Mr. Tremaine Fike, ORC, was present during the entire inspection. A review of records, treatment facilities, irrigation fields, and monitoring wells was completed. This review reflected non-compliance with the subject permit. The following violations were noted: 1. At the time of inspection, a spray head was damaged in field 8 upstream of the stream crossing between fields 7 and 8B. The broken spray head could not be located at the time of inspection due to the irrigation system being off. Staff were able to track the ponding and runoff visible to the unnamed tributary between fields 7 and 8. Staff tracked the effluent in the unnamed tributary to the North Fork Rocky River. Effluent was visible entering the North Fork Rocky River. Staff collected upstream, downstream, and discharge surface water samples during this inspection. See attached map and photos for reference. This discharge is a violation of Permit Condition 11.1, which states "the Permittee shall maintain and operate the subject non -discharge facilities so there is no discharge to surface waters..." Based on the 5-day report provided by Mr. Fike, 9,000 gallons of effluent entered the North Fork Rocky River. The collected samples were analyzed for fecal coliform. Sample results are listed below. The sample results show Drooer disinfection may not be occurring. Upstream Downstream Discharge v 327 CFU/100mL 12,000 CFU/100mL 12,000 CFU/100mL North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105 NoanicaaouNn oep.m.m or em�nmen� Qualm 336.776.9800 2. At the time of inspection, a spray head was broken upslope of the North Fork Rocky River in field 8B at a different location. Effluent was ponded at the edge of the spray field and Staff tracked effluent runoff to a small depression adjacent to the North Fork Rocky River. See attached map for reference. This is a violation of Permit Condition 111.1 which states "the Permittee shall take measures to prevent effluent ponding in or runoff from the irrigation sites..." 3. As mentioned in the Notice of Deficiency dated May 2, 2022, the freeboard marker must be resurveyed by May 30, 2022. A letter was provided to this Office dated August 1, 2022. To date, the freeboard marker has not been reinstalled based on the survey findings. Per Permit Condition 111.14 a gauge to monitor waste levels in the 15-acre stabilization and storage lagoon shall be provided. As it is currently installed, the freeboard marker does not accurately measure freeboard. The following item of concern was noted: A. The hinge on Monitoring Well 7 was repaired at the time of inspection. Staff observed erosion around the footing of the well cap and noted that the well casing was loose. The erosion around the footing of the well casing can potentially serve as a conduit of pollutants to groundwater. Per Permit Condition V.2, the permittee shall inspect the wastewater treatment facilities to prevent malfunctions, facility deterioration, and operator errors that may result in discharges of wastes to the environment, threats to human health, or public nuisances. As described in 15A NCAC 02C .0108, groundwater monitoring well construction requirements, repair or replace the footing or well casing. Please reply in writing to this notice within 10 days of receiving it. Your written response should detail the corrective actions you have taken and/or plan to take to correct each of the listed violations above. Additionally, you are required to schedule an on -site meeting with staff from the Winston Salem Regional Office to discuss the proposed corrective actions. Please refer to the enclosed inspection report for additional comments and observations. If you have any questions, please contact me or Caitlin Caudle at the letterhead address and phone number, or by email at lon.snider(a_deg.nc.gov or Caitlin.caudle(c_deg.nc.gov. Sincerely, DocuSiTgned by: 145B49E225CMEA... Lon T. Snider, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources Att: 1. Inspection Map Cc: Tremaine Fike, ORC (electronic copy) 2. Inspection Photos Randolph County Environmental Health (electronic 3. Inspection Report copy) North Carolina Department of Environmental Quality I Division of Water Resources D ��� Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Raleigh, North Carolina 27105 NCRTH CARCLINA ^ 336.776.9800 0_p Mo Emimnmen quay Att 1: Inspection Map IFP- w r '• f' f} O Irby pi�fft N o o r „• , 7/27/2023 1:9,336 0 0.05 0.1 0.2 mi 0 0.1 0.2 0.4 km NC CGIA, Maxar, Esri Community Maps Contributors, Chatham County, NC, State of North Carolina DOT, Esri, HERE, Garmin, SafeGraph, Attachment 2: Inspection Photos Figure 1. Discharge from Field 8 Figure 3. Discharge channelizing from Field 8 NORTH CAROLINAD � �� oeo+ro�.m m F,mro���w n�si� Figure 2. Discharge channelizing from Field 8 F uJw .SRa ?M Figure 4. Discharge entering UT to Rocky River North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Raleigh, North Carolina 27105 336.776.9800 Figure 5. UT before entering Rocky River Figure 6. Discharge entering Rocky River D North Carolina Department of Environmental Quality I Division of Water Resources ✓ Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Raleigh, North Carolina 27105 NORTH CAROLINA 336.776.9800 onparhnem of EmironmanW 9uallly Compliance Inspection Report Permit: WQ0003090 Effective: 05/01/19 Expiration: 08/31/24 Owner : Town of Liberty SOC: Effective: Expiration: Facility: Town of Liberty WWTF County: Randolph 7187 E Highfill Ave Region: Winston-Salem Liberty NC 272981006 Contact Person: Sandra Dixon Title: Phone: 336-622-4276 Directions to Facility: System Classifications: SI, Primary ORC: Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 07/20/2023 Entry Time 10:OOAM Primary Inspector: Caitlin C 768B834968199D49D_. g,ocuSigned by: Secondary Inspector(s): ""'ruv' (""""� & Certification: Phone: Exit Time: 01:30PM Phone: 336-776-9699 Reason for Inspection: Routine Inspection Type: Compliance Evaluation Permit Inspection Type: Wastewater Irrigation Facility Status: ❑ Compliant Not Compliant Question Areas: Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions Treatment Flow Measurement -Water Treatment Barscreen Record Keeping Use Records Treatment Lagoons End Use -Irrigation Treatment Influent Pump Station Treatment Disinfection Treatment Flow Measurement Storage Standby Power Wells (See attachment summary) Page 1 of 8 Permit: WQ0003090 Owner - Facility: Town of Liberty Inspection Date: 07/20/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine Inspection Summary: On July 20, 2023, Division of Water Resources staff Caitlin Caudle and Kristen Potwora completed a routine compliance inspection. Mr. Tremaine Fike, ORC, was present during the entire inspection. A review of records, treatment facilities, irrigation fields, and monitoring wells was completed. This review reflected non-compliance with the subject permit. The following violations were noted: 1. At the time of inspection, a spray head was damaged in field 8 upstream of the stream crossing between fields 7 and 8B. The broken spray head could not be located at the time of inspection due to the irrigation system being off. Staff were able to track the ponding and runoff visible to the unnamed tributary between fields 7 and 8. Staff tracked the effluent in the unnamed tributary to the North Fork Rocky River. Effluent was visible entering the North Fork Rocky River. Staff collected upstream, downstream, and discharge surface water samples during this inspection. See attached map and photos for reference. This discharge is a violation of Permit Condition 11.1, which states "the Permittee shall maintain and operate the subject non -discharge facilities so there is no discharge to surface waters..." Based on the 5-day report provided by Mr. Fike, 9,000 gallons of effluent entered the North Fork Rocky River. The collected samples were analyzed for fecal coliform. Sample results are listed below. The sample results show proper disinfection may not be occurring. Upstream Downstream Discharge 327 CFU/100mL12,000 CFU/100mL 12,000 CFU/100mL 2. At the time of inspection, a spray head was broken upslope of the North Fork Rocky River in field 8B at a different location. Effluent was ponded at the edge of the spray field and Staff tracked effluent runoff to a small depression adjacent to the North Fork Rocky River. See attached map for reference. This is a violation of Permit Condition 111.1 which states "the Permittee shall take measures to prevent effluent ponding in or runoff from the irrigation sites..." 3. As mentioned in the Notice of Deficiency dated May 2, 2022, the freeboard marker must be resurveyed by May 30, 2022. A letter was provided to this Office dated August 1, 2022. To date, the freeboard marker has not been reinstalled based on the survey findings. Per Permit Condition 111.14 a gauge to monitor waste levels in the 15-acre stabilization and storage lagoon shall be provided. As it is currently installed, the freeboard marker does not accurately measure freeboard. The following item of concern was noted: A. The hinge on Monitoring Well 7 was repaired at the time of inspection. Staff observed erosion around the footing of the well cap and noted that the well casing was loose. The erosion the footing of the well casing can potentially serve as a conduit of pollutants to groundwater. Per Permit Condition V.2, the permittee shall inspect the wastewater treatment facilities to prevent malfunctions, facility deterioration, and operator errors that may result in discharges of wastes to the environment, threats to human health, or public nuisances. As described in 15A NCAC 02C .0108, groundwater monitoring well construction requirements, repair or replace the footing or well casing. Please reply in writing to this notice within 10 days of receiving it. Your written response should detail the corrective actions you have taken and/or plan to take to correct each of the listed violations above. Additionally, you are required to schedule an on -site meeting with staff from the Winston Salem Regional Office to discuss the proposed corrective actions. Other observations: • Trees were trimmed and pushed back from the edge of the irrigation fields. Mr. Fike stated that the contracted farmer will be reseeding any bare areas. • Maintenance events completed by the contracted farmer were recorded in the operations and maintenance log. • Mr. Fike stated that areas of the spray field will likely be reseeded this fall by the contracted farmer. • The mobile home park close to the spray fields has a single water supply well and the rest of the area is served by public water. Page 2 of 8 Permit: WQ0003090 Owner - Facility: Town of Liberty Inspection Date: 07/20/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine • Mr. Fike stated he is irrigating for a longer period of time once a week instead of a shorter amount of time twice a week. This has allowed him to repair more spray heads. • The contracted farmer has applied chicken litter to the spray fields. Mr. Fike provided a nutrient analysis of the chicken litter. The chicken litter had a PAN rate of 24.7 Ibs/ton and 3200 Ibs/ac were applied, based on staff calculations this is a loading rate of 40 Ibs/ac. Based on submitted monthly monitoring reports and this information, below is table of 12-month nitrogen loading in each field as of May 2023. Values were calculated using the more conservative seasonal acreage of December through March Zone 1 2 3 4 5 6 7 8 PAN Limits 204 204 204 204 204163.2 163.2 188 (Ibs/ac) PAN Loading (Ibs/ac) 95.1 90.9 86.1 102.1 110.4 84.6 75.3 95.1 • The irrigation system has not been calibrated to date. This must be completed by August 31, 2024. • Fecal values exceed 1/100mL. • Flow values exceeded monthly limits in April 2023, this was addressed in a separate NOD. • Soil samples were collected in November 2022. • Metering equipment was calibrated November 2022. • The high water alarm at the lift station calls out to the ORC and BUORC. • The chlorine contact chamber still had floating solids in it. Mr. Fike stated that they are cleaning the surface of the chlorine contact chamber once a month with a vacuum truck. Solids continue to enter the chlorine contact chamber when freeboard is above the concrete riser in the lagoon. • Freeboard was 6" below the concrete riser in the lagoon. Based on the survey report, this would be 0" freeboard. Field 8 irrigation was viewed in progress. Page 3 of 8 Permit: WQ0003090 Owner - Facility: Town of Liberty Inspection Date: 07/20/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Reuse (Quality) ❑ Infiltration System ❑ Activated Sludge Spray, LR ❑ Single Family Spray, LR ❑ Activated Sludge Spray, HR ❑ Activated Sludge Drip, LR ❑ Recycle/Reuse ❑ Single Family Drip ❑ Lagoon Spray, LR Treatment Influent Pump Station Yes No NA NE Is the pump station free of bypass lines or structures? ❑ ❑ ❑ Is the general housekeeping acceptable? ❑ ❑ ❑ Are all pumps present? ❑ ❑ ❑ Are all pumps operable? ❑ ❑ ❑ Are floats/controls operable? ❑ ❑ ❑ Are audio and visual alarms available? ❑ ❑ ❑ Are audio and visual alarms operational? ❑ ❑ ❑ # Are SCADA/Telemetry alarms required? ❑ ❑ ❑ Are SCADA/Telemetry available? ❑ ❑ ❑ Are SCADA/Telemetry operational? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement -Influent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? 0 ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: Treatment Flow Measurement -Water Use Records Yes No NA NE Is water use metered? ❑ ❑ 0 ❑ Are the daily average values properly calculated? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement -Effluent Yes No NA NE Page 4 of 8 Permit: WQ0003090 Owner - Facility: Town of Liberty Inspection Date: 07/20/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine Is flowmeter calibrated annually? 0 ❑ ❑ ❑ Is flowmeter operating properly? 0 ❑ ❑ ❑ Does flowmeter monitor continuously? 0 ❑ ❑ ❑ Does flowmeter record flow? 0 ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: Standby Power Yes No NA NE Is automatically activated standby power available? ❑ ❑ ❑ Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑ Is generator operable? ❑ ❑ ❑ Does generator have adequate fuel? ❑ ❑ ❑ Comment: Treatment Barscreen Yes No NA NE Is it free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screenings in compliance? 0 ❑ ❑ ❑ Are the bars spaced properly? 0 ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: Treatment Disinfection Yes No NA NE Is the system working? 0 ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time (>=30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas, does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ Is the chlorinator accessible? ❑ ❑ ❑ If tablets, are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑ If UV, are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ # Is it a dual feed system? ❑ ❑ ❑ Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes, then what is the EPA twelve digit ID Number? (1000- Page 5 of 8 Permit: WQ0003090 Owner - Facility: Town of Liberty Inspection Date: 07/20/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine If yes, then when was the RMP last updated? Comment: See summary. Record Keeping Yes No NA NE Is a copy of current permit available? 0 ❑ ❑ ❑ Are monitoring reports present: NDMR? 0 ❑ ❑ ❑ NDAR? 0 ❑ ❑ ❑ Are flow rates less than of permitted flow? 0 ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are application rates adhered to? ❑ ❑ ❑ Is GW monitoring being conducted, if required (GW-59s submitted)? ❑ ❑ ❑ Are all samples analyzed for all required parameters? ❑ ❑ ❑ Are there any 2L GW quality violations? ❑ ❑ ❑ Is GW-59A certification form completed for facility? ❑ ❑ ❑ Is effluent sampled for same parameters as GW? ❑ ❑ ❑ Do effluent concentrations exceed GW standards? ❑ ❑ ❑ Are annual soil reports available? ❑ ❑ ❑ # Are PAN records required? ❑ ❑ ❑ # Did last soil report indicate a need for lime? ❑ ❑ ❑ If so, has it been applied? ❑ ❑ ❑ Are operational logs present? ❑ ❑ ❑ Are lab sheets available for review? ❑ ❑ ❑ Do lab sheets support data reported on NDMR? ❑ ❑ ❑ Do lab sheets support data reported on GW-59s? ❑ ❑ ❑ Are Operational and Maintenance records present? ❑ ❑ ❑ Were Operational and Maintenance records complete? ❑ ❑ ❑ Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑ Is a copy of the SOC readily available? ❑ ❑ ❑ No treatment units bypassed since last inspection? ❑ ❑ ❑ Comment: See summa End Use-Irriqation Yes No NA NE Are buffers adequate? ❑ ❑ ❑ Is the cover crop type specified in permit? ❑ ❑ ❑ Is the crop cover acceptable? ❑ ❑ ❑ Is the site condition adequate? ❑ ❑ ❑ Is the site free of runoff / ponding? ❑ ❑ ❑ Is the acreage specified in the permit being utilized? 0 ❑ ❑ ❑ Page 6 of 8 Permit: WQ0003090 Owner - Facility: Town of Liberty Inspection Date: 07/20/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine Is the application equipment present? 0 ❑ ❑ ❑ Is the application equipment operational? 0 ❑ ❑ ❑ Is the disposal field free of limiting slopes? 0 ❑ ❑ ❑ Is access restricted and/or signs posted during active site use? 0 ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ How close is the closest water supply well? ❑ ❑ ❑ Is municipal water available in the area? 0 ❑ ❑ ❑ # Info only: Does the permit call for monitoring wells? 0 ❑ ❑ ❑ Are GW monitoring wells located properly w/ respect to RB and CB? 0 ❑ ❑ ❑ Are GW monitoring wells properly constructed, including screened interval? 0 ❑ ❑ ❑ Are monitoring wells damaged? 0 ❑ ❑ ❑ Comment: See summary. 001 Treatment Lagoons Yes No NA NE Lagoon Type None Primary/Secondary Primary Influent structure ❑ ❑ ❑ ❑ Banks/berms (seepage and erosion) ❑ ❑ ❑ ❑ Vegetation (excessive vegetation on banks/berms) ❑ ❑ ❑ ❑ Liner ❑ ❑ ❑ ❑ Liner Type Apron, clay Baffles/curtains ❑ ❑ ❑ ❑ Freeboard Marker ❑ ❑ ❑ ❑ Required freeboard 1.5 Feet Actual freeboard 0 Feet Are increments clearly marked on gauge at adequate intervals? ❑ ❑ ❑ ❑ Has the water level gauge been surveyed w/ respect to lowest point on dike? wall? ❑ ❑ ❑ ❑ No Evidence of overflow ❑ ❑ ❑ ❑ Acceptable color ❑ ❑ ❑ ❑ Floating mats ❑ ❑ ❑ ❑ Page 7 of 8 Permit: WQ0003090 Owner - Facility: Town of Liberty Inspection Date: 07/20/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine Excessive solids buildup ❑ ❑ ❑ ❑ Aerators/mixers ❑ ❑ ❑ ❑ Effluent structure ❑ ❑ ❑ ❑ Lagoon cover ❑ ❑ ❑ ❑ Page 8 of 8