July 26, 2023
SUBJECT: Compliance Evaluation Inspection
Kinder Morgan/ Charlotte Terminal 2
NPDES Permit No. NC0004839
Mecklenburg County
Dear Mr. Arteaga:
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on July 20, 2023, by Mr. Wes Bell of this Office. Please advise all environmental staff of our findings by forwarding
the enclosed report. Thank you for all your assistance provided during the inspection.
Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at
wes.bellgdeq.nc. gov.
Sincerely,
DocuSigned by:
A wNP,uft
F161 F669A2D84A3...
Andrew H. Pitner, P.G.
Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
Enclosure:
Inspection Report
Cc: NPDES Program Files - Laserfiche
D North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0004839 I11 121 23/07/20 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 701d I 71 I„ I 72 I r., I 71 I 74 79 I I I I I I I80
L—I ty L-1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:05AM 23/07/20
21/09/01
Charlotte Terminal 2
6801 Freedom Dr
Exit Time/Date
Permit Expiration Date
Paw Creek NC 28130
11:22AM 23/07/20
25/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Carlos Augusto Arteaga/ORC/704-399-5696/
Joseph W Byers//704-399-5696 /
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Wayne Harvey,1000 Windward Concourse Ste 450 Alpharetta GA
30005//770-751-4116/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell Docusigned by: DWR/MRO WQ/704-663-1699 Ext.2192/ 7/26/2023
A61696D90=437...
Signature of Man ZT"RltqViewer Agency/Office/Phone and Fax Numbers Date
Andrew Pitn r �.c10 H P"*ftR/MRO WQ/704-663-1699 Ext.2180/ 7/26/2023
F161F969A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0004839 I11 12I 23/07/20 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NC0004839 Owner -Facility: Charlotte Terminal 2
Inspection Date: 07/20/2023 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
M
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Outfall 001 consists of stormwater from the secondary containment structure (bulk
petroleum ASTs) and loading rack area. The stormwater from the loading rack area is
treated by an oil/water separator and carbon filtration system prior to being combined
with the discharge from the secondary containment structure.
The last compliance evaluation inspection at this facility was performed by DWR staff
on 2/13/2020.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Page# 3
Permit: NC0004839
Inspection Date: 07/20/2023
Record Keeping
Owner -Facility: Charlotte Terminal 2
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: The records reviewed durinq the inspection were organized and well maintained
Discharge Monitoring Reports (eDMRs) were reviewed for the period May 2022
through June 2023. No limit and/or monitoring violations were reported.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ❑ ❑ 0 ❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
0
❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: Pace Analytical Services and Meritech, Inc. (toxicity) have been contracted to perform
Permit -required analyses. S&ME staff are contracted to collect effluent samples.
Kinder Morgan staff accompany S&ME staff during the effluent sampling events.
Kinder Morgan staff should notify the contracted laboratory to analyze future effluent
total recoverable phenolics samples at a lower detection limit (5 ug/L instead of 40
ug/L). Analytical methods shall be in accordance with 40 CFR Part 136 and shall be
sufficiently sensitive to determine whether parameters are present in concentrations
greater than applicable standards and criteria.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
■
❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
■
❑
❑
❑
representative)?
Comment: The subject permit requires effluent grab samples.
Facilitv staff must ensure that the effluent is collected directly into the oil & arease
sample container (no intermediate sample containers/devices).
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Page# 4
Permit: NC0004839
Inspection Date: 07/20/2023
Operations & Maintenance
Owner -Facility: Charlotte Terminal 2
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: The NPDES facilities appeared to be properly operated and well maintained. The
entire facility (including NPDES facilities) is inspected on a daily basis by Kinder
Morgan staff. No sheens were observed in the accumulations of water inside the
secondary containment structure. The recovered oil (oil/water separator) is removed
two to three times per year by Covanta Environmental Solutions. The carbon is
replaced annually and the spent carbon is disposed of by a contracted company at a
permitted landfill. The high-water level (oil/water separator) and hydrocarbon detection
system (discharge outfall) are both tested annually.
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The facility separately monitors the flow from the stormwater containment structure and
the treatment system for the loading rack area by in line flow meters/totalizers. Both
flows are added together for the final flow for Outfall 001. A new factory calibrated flow
meter is purchased every year for the loading rack area. The flow meter for the
secondary containment structure is calibrated annually and was last calibrated in
September 2022 (installed in October 2022) by Allied Meter Service, Inc.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
❑
❑
0
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
■
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
❑
Comment: No discharge was observed from Outfall 001 during the inspection.