HomeMy WebLinkAboutNC0078131_Havelock WTP inspection_20230725ROY COOPER
Ca errtor
ELIZABETH S. BISER
Secretary
RICHARD E. PCIl , JR.
Director
David Hemenway
City of Havelock
PO Box 368
Havelock, NC 28532-0368
� 1.a SfATF q,
� awM ✓�`
NORTH CAROLINA
Environmental Quality
July 25, 2023
SUBJECT: Compliance Inspection Report
Brown Blvd WTP
NPDES WW Permit No. NCO078131
Craven County
Dear Permittel
The North Carolina Division of Water Resources conducted an inspection of the Brown Blvd WTP on
7/13/2023. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0078131. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
If you should have any questions, please do not hesitate to contact Robbie Bullock with the Water
Quality Regional Operations Section in the Washington Regional Office at 252-946-6481 or via email at
robert.e.bullock@deq.nc.gov.
ATTACHMENTS
Cc: Laserfiche
Sincerely,
Robert Tankard, Assistant Regional Supervisor
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
mlora„D �� North Carocna Department afElrvlrammental Qaallty I DWAon ofwaterP sources
Washington VNg mlOFt3ce 1943Washinglon3gvarc Mall I Washington, North Carolina 27M
252.9464481
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO078131 111 121 23/07/13 I17 18 I C I 19 Ls_] 20I �
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n,J I I I 71 I 74 79 I I I I I I I80
701� I 711 L
LJ L
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:OOAM 23/07/13
18/11/01
Brown Blvd WTP
Brown Blvd
Exit Time/Date
Permit Expiration Date
Havelock NC 28532
12:OOPM 23/07/13
23/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
David Robert Hemenway/ORC/252-444-6420/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
David Hemenway,PO Box 368 Havelock NC 285320368/ORC/252-444-6420/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Robert E Bullock DWR/WARO WQ/252-948-3843/ 7/25/2023
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Plow Tom. DWR/WARD WQROS 252-948-3921 7/25/2023
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO078131 I11 12I 23/07/13 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The review period for this inspection was from July 2018 through May 2023. No violations were noted
over the review period.
The current permit was set to expire on June 30, 2023. The facility has submitted a renewal
application and the existing permit will remain effective until a new permit is issued.
The January 2023 DMR was spot checked for accuracy with no discrepancies found.
David Hemenway is the ORC with Gavin Bostian as the Backup ORC.
The facility was judged to be Compliant with NPDES permit NC0078131.
Page#
Permit: NCO078131
Inspection Date: 07/13/2023
Owner -Facility: Brown Blvd WTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ■ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ■ ❑ ❑ ❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
■
❑
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: The current permit was set to expire on June 30, 2023. The facility
has submitted a
renewal application and the existing permit will remain effective until a new permit is
:--..-A
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Page# 3
Permit: NCO078131 Owner -Facility: Brown Blvd WTP
Inspection Date: 07/13/2023 Inspection Type: Compliance Evaluation
Record Keeping
Yes
No
NA
NE
Is the backup operator certified at one grade less or greater than the facility
0
❑
❑
❑
classification?
Is a copy of the current NPDES permit available on site?
M
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: The January 2023 DMR was spot checked for accuracy with no discrepancies found.
David Hemenway is the ORC with Gavin Bostian as the Backup ORC.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: The facility is Field Parameter certified with all other samples sent to
Analytical for analysis.
Primary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the sludge blanket level acceptable?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
VVM LlSMLl/_90I:4
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
nt
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
Comment: Wastewater from the Softeners and Iron Filters is sent to the Clarifier to allow solids to
settle out before the wastewater is sent to the 60,000 gallon settling basin. Solids that
accumulate in the Clarifier are sent to the drying beds for disposal.
Equalization Basins
Is the basin aerated?
Yes No NA NE
❑ ❑ ■ ❑
Page# 4
Permit: NC0078131 Owner -Facility: Brown Blvd WTP
Inspection Date: 07/13/2023 Inspection Type: Compliance Evaluation
Equalization Basins
Yes
No
NA
NE
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
■
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
❑
❑
0
❑
Are audible and visual alarms operable?
❑
❑
0
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment:
Drying Beds
Yes
No
NA
NE
Is there adequate drying bed space?
■
❑
❑
❑
Is the sludge distribution on drying beds appropriate?
0
❑
❑
❑
Are the drying beds free of vegetation?
0
❑
❑
❑
# Is the site free of dry sludge remaining in beds?
0
❑
❑
❑
Is the site free of stockpiled sludge?
■
❑
❑
❑
Is the filtrate from sludge drying beds returned to the front of the plant?
0
❑
❑
❑
# Is the sludge disposed of through county landfill?
0
❑
❑
❑
# Is the sludge land applied?
❑
0
❑
❑
(Vacuum filters) Is polymer mixing adequate?
❑
❑
■
❑
Comment: Sludge is taken to Tuscarora Landfill for disposal.
De -chlorination
Yes
No
NA NE
Type of system ?
Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
0
❑
❑
❑
Is storage appropriate for cylinders?
❑
❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
0
❑
❑
❑
Are the tablets the proper size and type?
❑
❑
■
❑
Comment: Liquid Captor is used for Dechlorination
Are tablet de -chlorinators operational?
❑
❑
❑
Number of tubes in use?
Comment:
Page# 5
Permit: NCO078131
Inspection Date: 07/13/2023
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Owner -Facility: Brown Blvd WTP
Inspection Type: Compliance Evaluation
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: CITI, LLC calibrated the flow meter on October 21, 2022
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: The sampler temperature on the day of inspection was 4 Degrees C
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Yes
No
NA
NE
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
❑
❑
❑
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, 0 ❑ ❑ ❑
and sampling location)?
Comment:
Page# 6