Compliance Inspection Report
Permit: WQ0002571 Effective: 08/23/19 Expiration: 09/30/24 Owner: Bobby F Williams
SOC: Effective: Expiration: Facility: Village Oaks Mobile Home Park WWTF
County: Onslow 2980 Burgaw Hwy
Region: Wilmington
Jacksonville NC 28540
Contact Person: Bobby F Williams Title: Phone: 910-346-9912
Directions to Facility:
Southwest of Jacksonville. On the North side of NC Highway 53 approximately 0.4 mile West of SR 1109.
System Classifications: SI,
Primary ORC: Stanley Earl Buck Certification: 987939 Phone: 252-503-5307
Secondary ORC(s):
On -Site Representative(s):
On -site representative Stanley E Buck 252-503-5307
Related Permits:
Inspection Date: 07/11/2023 Entry Time 12:45PM Exit Time: 01:45PM
Primary Inspector: Helen I Perez D�R uSig ed by: Phone: 910-796-7387
Ins eCtOr S lI^J [T04A.
DocuSi�gnned by:
Secondary : p ()1D645B4A39694BE... Naffs Oti 7/20/2023
7F141E73B6F3456...
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: ❑ Compliant Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Record Keeping
Use Records
Treatment Lagoons End Use -Irrigation Treatment Disinfection
Treatment Flow Measurement
(See attachment summary)
Page 1 of 7
DocuSign Envelope ID: 91`1792AB-BEC6-428D-92BC-12A74546FB4F
Permit: WQ0002571 Owner - Facility: Bobby F Williams
Inspection Date: 07/11/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine inspection of the Village Oaks Mobile Home Park WWTF was conducted on July 11, 2023. The purpose of the
evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
WQ0002571. Lee Buck, ORC, was present during the inspection.
This facility is a 786,522 gallon facultative lagoon system with a hydraulically connected 332,486 gallon storage lagoon and
3.6 acre spray irrigation field. It serves the Village Oaks Mobile Home Park and was originally permitted in 1985. The spray
area appears to be in much better condition than the last inspection in January 2020. A review of monitoring reports show
no violations. The west, east and north edges of the spray area slopes down considerably and irrigation needs to continue to
operate so no run-off occurs during spray events.
The facility was found to be non -compliant for the following issues:
1. There was some erosion of the east side of the facultative lagoon causing a low point along the berm. The water level
gauge needs to be surveyed again to this lowest part of the lagoon. Currently, the freeboard appears to be 1 foot from the
lowest point.
2. Documentation of maintenance for the irrigation equipment and field were not available.
3. Flow calibration records of the irrigation equipment, since the last inspection, were not available.
4. The BORC listed for the facility has an invalid certification.
A Notice of Violation will be issued. Please see the comment sections of the inspection report for more details.
Page 2 of 7
DocuSign Envelope ID: 91`1792AB-BEC6-428D-92BC-12A74546FB4F
Permit: WQ0002571 Owner - Facility: Bobby F Williams
Inspection Date: 07/11/2023 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Infiltration System
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Single Family Drip
❑
Recycle/Reuse
❑
Lagoon Spray, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: No comment.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ 0 ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment:
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? 0 ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ ❑
Comment: Influent flow is estimated using meter readings for the mobile home park.
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment:
Treatment Disinfection Yes No NA NE
Is the system working? 0 ❑ ❑ ❑
Page 3 of 7
DocuSign Envelope ID: 91`1792AB-BEC6-428D-92BC-12A74546FB4F
Permit: WQ0002571 Owner - Facility: Bobby F Williams
Inspection Date: 07/11/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (>=30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1 000-- )
If yes, then when was the RMP last updated?
Comment: Effluent flows from the facultative lagoon, through the tablet chlorinator, to the storage lagoon.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
0
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑
❑ ❑
NDAR?
❑
❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑
❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑ ❑ ❑
# Are PAN records required?
❑
❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑
❑ ❑
Page 4 of 7
DocuSign Envelope ID: 91`1792AB-BEC6-428D-92BC-12A74546FB4F
Permit: WQ0002571 Owner - Facility: Bobby F Williams
Inspection Date: 07/11/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Do lab sheets support data reported on NDMR? ❑ ❑ ❑
Do lab sheets support data reported on GW-59s? ❑ ❑ ❑
Are Operational and Maintenance records present? ❑ 0 ❑ ❑
Were Operational and Maintenance records complete? ❑ ❑ 0 ❑
Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑
Is a copy of the SOC readily available? ❑ ❑ 0 ❑
No treatment units bypassed since last inspection? 0 ❑ ❑ ❑
Comment: There is no maintenance documentation of the irrigation equipment or disposal field available.
The irrigation flow meter calibration records could not be located. The operator scheduled a
contractor to calibrate the flow meter for the same day, after inspection. Annual soil analyses
for the last three years were available for review.
End Use -Irrigation
Yes No NA NE
Are buffers adequate?
❑
❑ ❑
Is the cover crop type specified in permit?
❑
❑ ❑
Is the crop cover acceptable?
❑ ❑ ❑
Is the site condition adequate?
❑ ❑ ❑
Is the site free of runoff / ponding?
❑ ❑ ❑
Is the acreage specified in the permit being utilized?
❑
❑ ❑
Is the application equipment present?
❑ ❑ ❑
Is the application equipment operational?
❑ ❑ ❑
Is the disposal field free of limiting slopes?
❑
❑ ❑
Is access restricted and/or signs posted during active site use?
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
How close is the closest water supply well?
❑
❑ ❑
Is municipal water available in the area?
❑
❑ ❑
# Info only: Does the permit call for monitoring wells?
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Are monitoring wells damaged?
❑
❑ ❑
Comment: The irrigation field has improved since the last inspection. The west, east and north edges of
the irrigation field slope down considerably. Care needs to be taken during spray
events to
avoid any run-off in these areas. The pump appears to have been replaced to apply
sufficient
pressure to the spray heads.
TREATMENT -
Treatment Lagoons
Lagoon Type
Primary/Secondary
Yes No NA NE
None
Primary
Page 5 of 7
DocuSign Envelope ID: 91`1792AB-BEC6-428D-92BC-12A74546FB4F
Permit: WQ0002571 Owner - Facility: Bobby F Williams
Inspection Date: 07/11/2023 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Influent structure
❑
❑ ❑
Banks/berms (seepage and erosion)
0
❑ ❑ ❑
Vegetation (excessive vegetation on banks/berms)
❑
0 ❑ ❑
Liner
❑
0 ❑ ❑
Liner Type
Baffles/curtains
❑
0 ❑ ❑
Freeboard Marker
0
❑ ❑ ❑
Required freeboard
2
Feet
Actual freeboard
1
Feet
Are increments clearly marked on gauge at adequate intervals?
❑
0 ❑ ❑
Has the water level gauge been surveyed w/ respect to lowest point on dike? wall?
❑
0 ❑ ❑
No Evidence of overflow
0
❑ ❑ ❑
Acceptable color
❑
❑ ❑
Floating mats
❑
❑ ❑
Excessive solids buildup
❑
0 ❑ ❑
Aerators/mixers
❑
0 ❑ ❑
Effluent structure
❑
❑ ❑
Lagoon cover
❑
0 ❑ ❑
STORAGE -
Treatment Lagoons
Yes No NA NE
Lagoon Type
None
Primary/Secondary
Secondary
Influent structure
❑ ❑ ❑
Banks/berms (seepage and erosion)
❑ ❑ ❑
Vegetation (excessive vegetation on banks/berms)
❑ ❑ ❑
Liner
❑ ❑ ❑
Liner Type
Baffles/curtains
❑ ❑ ❑
Freeboard Marker
0 ❑ ❑ ❑
Page 6 of 7
DocuSign Envelope ID: 91`1792AB-BEC6-428D-92BC-12A74546FB4F
Permit: WQ0002571 Owner - Facility: Bobby F Williams
Inspection Date: 07/11/2023 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Required freeboard
2
Feet
Actual freeboard
1
Feet
Are increments clearly marked on gauge at adequate intervals?
❑
0 ❑ ❑
Has the water level gauge been surveyed w/ respect to lowest point on dike? wall?
❑
0 ❑ ❑
No Evidence of overflow
0
❑ ❑ ❑
Acceptable color
❑
❑ ❑
Floating mats
❑
0 ❑ ❑
Excessive solids buildup
❑
❑ ❑
Aerators/mixers
❑
0 ❑ ❑
Effluent structure
❑
❑ ❑
Lagoon cover
❑
0 ❑ ❑
Page 7 of 7