SUBJECT: Compliance Inspection Report
Robersonville WWTP
NPDES WW Permit No. NCO026042
Martin County
Dear Permittel
The North Carolina Division of Water Resources conducted an inspection of the Robersonville WWTP on
6/27/2023. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0026042. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
If you should have any questions, please do not hesitate to contact Robbie Bullock with the Water
Quality Regional Operations Section in the Washington Regional Office at 252-948-3843 or via email at
robert.e.bullock@deq.nc.gov.
ATTACHMENTS
Cc: Laserfiche
Sincerely,
ROW TR..:,
Robert Tankard, Assistant Regional Supervisor
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
mlora„D �� North Carocna Department afElrvlrammental Qaallty I DWAon ofwaterP sources
Washington VNg mlOFt3ce 1943Washinglon3gvarc Mall I Washington, North Carolina 27M
252.9464481
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO026042 I11 121 23/06/27 I17 18LC I 19 Ls_] I 201 �
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n,J I I I 71 I 74 79 I I I I I I I80
701� I 711 L
LJ L
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:OOAM 23/06/27
17/05/01
Robersonville WWTP
1149 Rogerson Rd
Exit Time/Date
Permit Expiration Date
Robersonville NC 27871
12:OOPM 23/06/27
21/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Elizabeth Jenkins,PO Box 487 Robersonville NC 278710487//252-508-0311/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Robert E Bullock DWR/WARO WQ/252-948-3843/ 6/28/2023
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Plow Tom. DWR/WARD WQ 252-948-3921 6/28/2023
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO026042 I11 12I 23/06/27 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Robbie Bullock (DWR WaRO) met with Randy Brown (Envirolink) and Richard Sink (Town of
Robersonville) during the inspection. The review period for this inspection was January 2022 through
April 2023. The facility was issued One Notice of Deficiency, One Notice of Violation and Two Civil
Penalty Assessments over the review period.
The operator states the Influent sampler stopped working over the weekend. A grab sample is taken
until the sampler is replaced. The facility is ordering a new influent sampler.
On the day of the inspection the grit auger was not operational due to a bad motor. The facility is
working on repairing the motor.
On the day of inspection #1 Oxidation Ditch was operational. #2 Oxidation Ditch was not in service
due to low flow. Vegetation growth needs to be removed from the overflow trough on the #2 Oxidation
Ditch
On the day of inspection the #6 Clarifier was offline and not operational. As mentioned in the
February 8, 2022 inspection the gear box for the Clarifier arm needs to be rebuilt. The Town has
received a grant to replace the gear box.
Effluent sampler is on constant time and constant volume with a sample taken every 30 minutes. On
the day of inspection the sampler temperature was 15 degrees C. The facility stated they will add ice
to the sampler to keep the sample cool until the sampler is repaired.
Page#
Permit: NCO026042
Inspection Date: 06/27/2023
Owner -Facility: Robersonville WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ■ ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ■ ❑ ❑ ❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
■
❑
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: The current permit was set to expire on November 30, 2021. A renewal application
has
been submitted and the existing permit will remain active until a new permit is issued.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
❑
❑
❑
■
Is all required information readily available, complete and current?
❑
❑
❑
■
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
■
Are analytical results consistent with data reported on DMRs?
❑
❑
❑
■
Is the chain -of -custody complete?
❑
❑
❑
■
Dates, times and location of sampling
❑
Name of individual performing the sampling
❑
Results of analysis and calibration
❑
Dates of analysis
❑
Name of person performing analyses
❑
Transported COCs
❑
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
■
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
■
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Page# 3
Permit: NCO026042 Owner -Facility: Robersonville WWTP
Inspection Date: 06/27/2023 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑ ■
Comment: William Lamm is the ORC with Anthony Branch as the Backup ORC.
Bar Screens
Yes
No
NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
■
❑
❑
❑
Is disposal of screening in compliance?
■
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: Screenings is disposed of in the landfill
Pump Station - Influent
Yes
No
NA
NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
■
❑
❑
❑
Are all pumps operable?
■
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
❑
❑
❑
Is audible and visual alarm available and operational?
❑
❑
❑
Comment:
Influent Sampling
Yes
No
NA
NE
# Is composite sampling flow proportional?
❑
0
❑
❑
Is sample collected above side streams?
■
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Is sampling performed according to the permit?
■
❑
❑
❑
Page# 4
Permit: NCO026042
Inspection Date: 06/27/2023
Owner -Facility: Robersonville WWTP
Inspection Type: Compliance Evaluation
Influent Sampling Yes No NA NE
Comment: The operator states the Influent sampler stopped working over the weekend. A grab
sample is taken until the sampler is replaced. The facility is ordering a new influent
sampler.
Grit Removal
Type of grit removal
Yes No NA NE
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
❑
❑
0
❑
Is the grit free of excessive odor?
❑
❑
■
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment: On the day of the inspection the auger was not operational
due to a bad motor. The
facility is working on repairing the motor.
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
❑
0
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
■
❑
❑
❑
Are all pumps present?
❑
❑
■
❑
Are all pumps operable?
❑
❑
0
❑
Are float controls operable?
❑
❑
0
❑
Are audible and visual alarms operable?
❑
❑
0
❑
# Is basin size/volume adequate?
■
❑
❑
❑
Comment: The "Equalization Basin" is a Anaerobic and Anoxic zone, On the day of inspection
Basins 1 and 2 were offline due to low flows
Oxidation Ditches
Yes
No
NA
NE
Are the aerators operational?
0
❑
❑
❑
Are the aerators free of excessive solids build up?
0
❑
❑
❑
# Is the foam the proper color for the treatment process?
■
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Are settleometer results acceptable (> 30 minutes)?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
■
❑
❑
❑
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
■
❑
❑
❑
Page# 5
Permit: NCO026042
Inspection Date: 06/27/2023
Oxidation Ditches
Owner -Facility: Robersonville WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: On the day of inspection #1 Oxidation Ditch was operational. #2 Oxidation Ditch was
down due to low flow. Vegetation growth needs to be removed from the overflow trough
on the #2 Oxidation Ditch
Pumps-RAS-WAS
Yes
No
NA
NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
■
❑
❑
❑
Comment:
Aerobic Digester
Yes
No
NA
NE
Is the capacity adequate?
■
❑
❑
❑
Is the mixing adequate?
❑
0
❑
❑
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
■
❑
❑
❑
# Is tankage available for properly waste sludge?
■
❑
❑
❑
Comment: The facility land applied Sludge from the digesters in June 2023.
On the day of inspction the aerators were off.
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
❑
❑
❑
Is the site free of weir blockage?
❑
❑
❑
■
Is the site free of evidence of short-circuiting?
❑
❑
❑
■
Is scum removal adequate?
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
■
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
0
❑
❑
❑
Page# 6
Permit: NCO026042
Inspection Date: 06/27/2023
Owner -Facility: Robersonville WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Comment: On the day of inspection the #6 Clarifier was offline and not operational. As mentioned
in the February 8, 2022 inspection the pear box for the Clarifier arm needs to be
rebuilt. The Town has received a grant to replace the pear box.
On the day of the inspection there was no Effluent discharging from the Clarifiers due
to the facility wasting sludge.
Filtration (High Rate Tertiary)
Yes
No
NA
NE
Type of operation:
Is the filter media present?
❑
❑
❑
Is the filter surface free of clogging?
❑
❑
❑
Is the filter free of growth?
❑
❑
❑
Is the air scour operational?
❑
❑
❑
Is the scouring acceptable?
❑
❑
❑
Is the clear well free of excessive solids and filter media?
❑
❑
❑
Comment: The facility uses two Disc filters
Chemical Feed
Yes
No
NA
NE
Is containment adequate?
0
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Are backup pumps available?
0
❑
❑
❑
Is the site free of excessive leaking?
0
❑
❑
❑
Comment:
Disinfection -Gas
Yes
No
NA
NE
Are cylinders secured adequately?
■
❑
❑
❑
Are cylinders protected from direct sunlight?
0
❑
❑
❑
Is there adequate reserve supply of disinfectant?
0
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
■
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No.
❑
❑
0
❑
7782-50-5)?
If yes, then is there a Risk Management Plan on site?
❑
❑
0
❑
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Page#
7
Permit: NCO026042 Owner -Facility: Robersonville WWTP
Inspection Date: 06/27/2023 Inspection Type: Compliance Evaluation
Disinfection -Gas Yes No NA NE
Comment:
De -chlorination
Yes
No
NA NE
Type of system ?
Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
■
❑
❑
❑
Is storage appropriate for cylinders?
❑
❑
■
❑
# Is de -chlorination substance stored away from chlorine containers?
■
❑
❑
❑
Are the tablets the proper size and type?
❑
❑
■
❑
Comment: Sodium Sulfite is used for Dechlor
Are tablet de -chlorinators operational? ❑ ❑ ■ ❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
■
❑
❑
❑
Is flow meter calibrated annually?
■
❑
❑
❑
Is the flow meter operational?
■
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
❑
■
Comment: Carolina Technical Services calibrated the Effluent flow meter on March 21,
2023.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
❑
■
❑
❑
Is sample collected below all treatment units?
■
❑
❑
❑
Is proper volume collected?
■
❑
❑
❑
Is the tubing clean?
■
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
■
❑
❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type ■
❑
❑
❑
representative)?
Comment: Effluent sampler is on constant time and constant volume with a sample
taken every 30
minutes. On the day of inspection the sampler temperature was 15 degrees
C. The
facility stated they will add ice to the sampler while sampler is running
until the sampler
is repaired.
Page# 8
Permit: NC0026042 Owner -Facility: Robersonville WWTP
Inspection Date: 06/27/2023 Inspection Type: Compliance Evaluation
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
■
❑
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, 0 ❑ ❑ ❑
and sampling location)?
Comment: