HomeMy WebLinkAboutNC0003671_CEI_Letter_20230614ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Buckeye SE Terminals LP
Attn: Carl Ostach, Owner
6161 Hamilton Bvd
Allentown, PA 18106
NORTH CAROLINA
Environmental Quality
June 14, 2023
SUBJECT: Compliance Evaluation Inspection
Greensboro Terminal II
NPDES Permit #: NC0003671
Guilford County
On May 24th, 2023, Division of Water Resources staff Ron Boone conducted a routine compliance
inspection at Buckeye SE Terminals LP Greensboro Terminal II. Nathan Wood was present during the
inspection. A review of records, data, treatment components, and structures was completed. This
inspection reflected compliance with the subject permit.
Observations:
1. All loading rack drainage enters a trench drain that conveys drainage to a 1,000 gallon oil/water
separator (OWS).
2. OWS effluent is transferred to the onsite wet holding pond under normal conditions. If abnormal
conditions occur, i.e. a fuel spill at the rack or if the amount of fuel spilled overwhelms the OWS,
any contaminated effluent would flow to the wet holding pond and the pond would have to be
cleaned up.
3. Product entrapped in the OWS is transferred back to the fuel tanks to be mixed in.
4. Once the wet holding pond level reaches or nears its maximum level, operators assess the
condition of its contents and determine if the pond should discharge. Wet holding pond contents
are manually released via a normally locked -closed gate valve to Horsepen Creek, Class WS-III,
nutrient sensitive waters in the Cape Fear River Basin.
5. Flow is calculated using the time the valve is open and a pre -calculated factor based on the size of
the valve and discharge pipe.
6. Discharge monitoring reports and laboratory reports for July and December 2022 were reviewed
and no discrepancies were noted.
No other items of concern were noted.
Please be aware that pursuant to North Carolina general statute (NCGS) 143-215.6A, the Division may
assess civil penalties not to exceed $25,000 per day against any person who fails to fully comply with the
requirements of a permit issued pursuant to NC General Statute (NCGS) 143-215.1., as is NC0088552.
DffNorth Carolina Department of Environmental Quality I Division of Water Resources
oan caaouNn
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
M336.776.9800
oep.m.m or em�nmen� Qualm
If you have any questions or concerns, please feel free to contact Mr. Boone at any time by phone at 336-
776-9690, or by email at ron.boone@deq.nc.gov. Thank you for your time and attention to this matter.
Sincerely,
EDo-,B49E22
cuSiiggned b<y:
:5C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Attachments:
Water Compliance Inspection Report
REQ� North Carolina Department ofEnvironmental Quality I Division ofWater Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Winston-Salem, North Carolina 27105
NORTH CAROLINA 336.776.9800
naparMeM of EmironmanW 9uallly
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0003671 111 121 23/05/24 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I ni I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
09:30AM 23/05/24
21/08/01
Greensboro Terminal II
7109 W Market St
Exit Time/Date
Permit Expiration Date
Greensboro NC 27419
10:30AM 23/05/24
25/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Paul Potts,PO Box 22186 Tulsa OK 741212186//918-573-1605/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
ocuSigned by: DWR/WSRO WQ/336-776-9690/
"".& Boom 6/9/2023
Ron Boone �1020FSDD5F2A3460...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Docusigned by: 6/14/202 3
EPA �c�taas�as(v 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0003671 I11 12I 23/05/24 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On May 24th, 2023, Division of Water Resources staff Ron Boone conducted a routine compliance
inspection at Buckeye SE Terminals LP Greensboro Terminal II. Nathan Wood was present during the
inspection. A review of records, data, treatment components, and structures was completed. This
inspection reflected compliance with the subject permit.
Observations:
1. All loading rack drainage enters a trench drain that conveys drainage to a 1,000 gallon oil/water
separator (OWS).
2. OWS effluent is transferred to the onsite wet holding pond under normal conditions. If abnormal
conditions occur, i.e. a fuel spill at the rack or if the amount of fuel spilled overwhelms the OWS, any
contaminated effluent would flow to the wet holding pond and the pond would have to be cleaned up.
3. Product entrapped in the OWS is transferred back to the fuel tanks to be mixed in.
4. Once the wet holding pond level reaches or nears its maximum level, operators assess the
condition of its contents and determine if the pond should discharge. Wet holding pond contents are
manually released via a normally locked -closed gate valve to Horsepen Creek, Class WS-III, nutrient
sensitive waters in the Cape Fear River Basin.
5. Flow is calculated using the time the valve is open and a pre -calculated factor based on the size
of the valve and discharge pipe.
6. Discharge monitoring reports and laboratory reports for July and December 2022 were reviewed
and no discrepancies were noted.
No other items of concern were noted.
Page#
Permit: NC0003671 Owner - Facility: Greensboro Terminal II
Inspection Date: 05/24/2023 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
■
❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
❑
■
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: None
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Is a copy of the current NPDES permit available on site?
■
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
■
❑
Comment: None
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ■ ❑ ❑ ❑
Page# 3
Permit: NC0003671 Owner - Facility: Greensboro Terminal II
Inspection Date: 05/24/2023 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
■
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: None
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
■
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
❑
❑
❑
■
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
❑
❑
❑
representative)?
Comment: None
Lagoons
Yes
No
NA NE
Type of lagoons?
Facultative
# Number of lagoons in operation at time of visit?
1
Are lagoons operated in?
# Is a re -circulation line present?
❑
0
❑
❑
Is lagoon free of excessive floating materials?
0
❑
❑
❑
# Are baffles between ponds or effluent baffles adjustable?
❑
❑
0
❑
Are dike slopes clear of woody vegetation?
0
❑
❑
❑
Are weeds controlled around the edge of the lagoon?
0
❑
❑
❑
Are dikes free of seepage?
0
❑
❑
❑
Are dikes free of erosion?
■
❑
❑
❑
Are dikes free of burrowing animals?
0
❑
❑
❑
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple
❑
❑
0
❑
locations?
# If excessive algae is present, has barley straw been used to help control the growth?
❑
❑
0
❑
Page# 4
Permit: NC0003671
Inspection Date: 05/24/2023
Owner - Facility: Greensboro Terminal II
Inspection Type: Compliance Evaluation
Lagoons
Yes
No
NA
NE
Is the lagoon surface free of weeds?
0
❑
❑
❑
Is the lagoon free of short circuiting?
0
❑
❑
❑
Comment: None
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
❑
❑
0
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: Flow is calculated use time valve is open and a predetermined factor based on
valve/pipe size.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
■
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
■
❑
Comment: None
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Page# 5