Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO048879 111 121 23/06/16 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
1.0 701d I 711„ I 72 I r., I 71 I 74 79 I I I I I I I80
L—I ty L-1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:30AM 23/06/16
19/01/01
North Cary WRF
1900 Old Reedy Creek Rd
Exit Time/Date
Permit Expiration Date
Cary NC 27513
01:OOPM 23/06/16
23/02/28
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Jonathan Andrew Bulla/ORC/919-677-0850/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Donald Bradley Smith,PO Box 8005 Cary NC 275128005//919-469-4095/9194694304
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
OriATuvia DWR/NPDES WW Permitting Unit/704-663-1699/
Kevin Fowler — DWR/RRO WQ/919-791-4200/ 6/22/2023
EBB057A2DE017498...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Vanessa E Manuel DWR/RRO WQ/919-791-4200/ 6/22/2023
EPA Form 3560-3 (Rev 9-94) Previous editions are obsoleteE�B2916EMB321441`...
Docusi9ned by:
&VXSSa f. t'l.aln,l, d
Page#
DocuSign Envelope ID: D33666E2-016E-4ED7-9C33-3664A6FCEB51
NPDES yr/mo/day Inspection Type (Cont.)
NCO048879 I11 12I 23/06/16 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On June 16, 2023, the DWR as conducted a compliance training inspection at the subject facility
attended by: Ori Tuvia, Octovis Henriquez, Douglas Dowden, Min Xiao, Anjali Orlando, Nick coco,
Fenton Brown and Kevin Fowler. The assistance of Jim Bridges and Jonathan Bulla was greatly
appreciated during the inspection. Observations during the inspection are summarized below, as well
as an inspection checklist is attached for your records. • The current permit expired February 28,
2023, the facility has submitted a permit renewal application in a timely manner and operates under
the expired permit. The facility is permitted to discharge at a rate of 12.0 MGO and consists of:
mechanical screening; influent pump station; grit and grease removal system; Nutrient removal
system consisting of anaerobic selectors, oxidation ditches, anoxic zones and reaeration zones;
secondary clarifiers; deep -bed sand filters; UV disinfection; cascade aeration; gravity belt thickeners;
aerated sludge holding tanks. During the inspection one of the three reactor basins, one of two UV
channels, and one of the three circular clarifiers were offline due to low flow. All online treatment units
appeared to be operating satisfactorily. • The facility is a WW-4 Wastewater Treatment Plant and is
staffed 24 hours/day 7 days a week. • Records Review: Discharge Monitoring Report records for
February 2022 and February 2023 were reviewed with lab bench sheets and no transcription errors
were noted. Chain of Custody forms are completed and kept on site. A daily operation log book is
maintained and kept on site. Records are maintained for at least three years.- The laboratory on site
is certified to analyze most permit parameters (lab cert. no. 107). Toxicity and Mercury are sent to
private labs for analysis. A cursory review of the laboratory was conducted and the laboratory
appeared to be properly operated. Field meter calibration records were reviewed.- Biosolids are
thickened and temporarily stored on site in aerated tanks. The sludge is hauled to the South Cary
WRF or Western Wake Regional WRF for aerobic digestion and thermal drying into Class A
residuals.- The facility discharges to Crabtree creek, Class B, Nutrient Sensitive Waters, in the
Neuse River basin. The right of way to the discharged point is maintained. The effluent was clear,
trace amount of foam was observed, which dissipated within 100 feet of the outfall. No visible impacts
were noted immediately downstream of the discharge point. It was noted that the receiving stream is
actually an unnamed tributary to Crabtree Creek (Outfall 001 is about 100 yards away from the main
channel of Crabtree Creek), the receiving stream of the facility will be revised when the permit is up
for renewal.
Page#
DocuSign Envelope ID: D33666E2-016E-4ED7-9C33-3664A6FCEB51
Permit: NCO048879 Owner -Facility: North CaryWRF
Inspection Date: 06/16/2023 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0 ❑ ❑ ❑
application?
Is the facility as described in the permit? ❑ 0 ❑ ❑
# Are there any special conditions for the permit? M ❑ ❑ ❑
Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑
Comment: The current permit expired February 28, 2023, the facility has submitted a permit
renewal application in a timely manner and operates under the expired permit. The
receiving stream is actually an unnamed tributary to Crabtree Creek (Outfall 001 is
about 100 yards away from the main channel of Crabtree Creek), receiving stream will
be revised when the permit is up for renewal.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Facility analyzes the following parameters for process control: mixed liquor
settleometer, suspended solids, pH, phosphax (PO4-P), nitratax (NOx), temperature;
UV dose and flow; returned activated sludge flow; wasted sludge volume; alkalinity; and
clarifier sludge blanket.
Laboratory
Yes
No
NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
■
❑
❑
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
0
❑
❑
❑
Comment: The laboratory on site is certified to analyze most permit parameters (lab cert. no
107). Toxicity and Mercury are sent to private labs for analysis. A cursory
review of the
laboratory was conducted and the laboratory appeared to be properly operated.
Field
meter calibration records were reviewed
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Page# 3
DocuSign Envelope ID: D33666E2-016E-4ED7-9C33-3664A6FCEB51
Permit: NCO048879 Owner -Facility: North CaryWRF
Inspection Date: 06/16/2023 Inspection Type: Compliance Evaluation
Record Keeping
Yes
No
NA
NE
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
❑
operator on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: Discharge Monitoring Report records for February 2022 and February 2023 were
reviewed with lab bench sheets and no transcription errors were noted. Chain of
Custody forms are completed and kept on site. A daily operation log book is maintained
and kept on site. Records are maintained for at least three years
Flow Measurement - Influent
Yes
No
NA
NE
# Is flow meter used for reporting?
❑
0
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
❑
Comment: Influent and effluent flow meters are calibrated twice per year.
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris? 0 ❑ ❑ ❑
Page# 4
DocuSign Envelope ID: D33666E2-016E-4ED7-9C33-3664A6FCEB51
Permit: NC0048879 Owner -Facility: North CaryWRF
Inspection Date: 06/16/2023 Inspection Type: Compliance Evaluation
Bar Screens
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: Two coarse screens ( 1/ 2 inch) and two fine screens ( 1/ 4 inch). Manual bar screen
serves as backup.
Pump Station - Influent
Yes
No
NA NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
■
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
❑
❑
❑
Comment: Influent pump station # land # 2, each with four pumps.
Grit Removal
Yes
No
NA
NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
0
❑
❑
❑
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment:
Grease Removal
Yes
No
NA
NE
# Is automatic grease removal present?
■
❑
❑
❑
Is grease removal operating properly?
■
❑
❑
❑
Comment:
Influent Sampling
Yes
No
NA NE
# Is composite sampling flow proportional?
0
❑
❑ ❑
Is sample collected above side streams?
0
❑
❑ ❑
Is proper volume collected?
M
❑
❑ ❑
Page# 5
DocuSign Envelope ID: D33666E2-016E-4ED7-9C33-3664A6FCEB51
Permit: NCO048879 Owner -Facility: North CaryWRF
Inspection Date: 06/16/2023 Inspection Type: Compliance Evaluation
Influent Sampling Yes No NA NE
Is the tubing clean? 0 ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ■ ❑ ❑ ❑
degrees Celsius)?
Is sampling performed according to the permit? ■ ❑ ❑ ❑
Comment: Comment: Flow proportional composite sample
Aeration Basins
Yes
No
NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
■
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
0❑
❑
❑
Comment: Three trains of biological nutrient removal basins all trains have had a new diffuser
system installed. Train A and B were on line, Train C was down due to low flow.
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑ ■
❑ ❑ ❑ ■
❑ ❑ ■ ❑
Comment: EQ basins used from the old WWTP, converted from two existing clarifiers, one with
aeration, an EQ pump station.
Nutrient Removal
# Is total nitrogen removal required?
# Is total phosphorous removal required?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 6
DocuSign Envelope ID: D33666E2-016E-4ED7-9C33-3664A6FCEB51
Permit: NC0048879 Owner -Facility: North CaryWRF
Inspection Date: 06/16/2023 Inspection Type: Compliance Evaluation
Nutrient Removal Yes No NA NE
Type Biological
# Is chemical feed required to sustain process? ❑ ■ ❑ ❑
Is nutrient removal process operating properly? ■ ❑ ❑ ❑
Comment: Being converted from two existing clarifiers, one with aeration, an EQ pump station was
under construction at the time of inspection
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: Two ( A and B) of three secondary clarifiers were on line.
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Pumps-RAS-WAS
Yes
No
NA NE
Are pumps in place?
■
❑
❑
❑
Are pumps operational?
■
❑
❑
❑
Are there adequate spare parts and supplies on site?
■
❑
❑
❑
Comment: Each clarifier has a RAS- WAS pump station, with two RAS
pumps and one WAS
pump.
Filtration (High Rate Tertiary)
Yes
No
NA NE
Type of operation:
Up flow
Is the filter media present?
■
❑
❑
❑
Is the filter surface free of clogging?
■
❑
❑
❑
Is the filter free of growth?
■
❑
❑
❑
Is the air scour operational?
■
❑
❑
❑
Is the scouring acceptable?
■
❑
❑
❑
Is the clear well free of excessive solids and filter media?
■
❑
❑
❑
Page#
7
DocuSign Envelope ID: D33666E2-016E-4ED7-9C33-3664A6FCEB51
Permit: NCO048879 Owner -Facility: North CaryWRF
Inspection Date: 06/16/2023 Inspection Type: Compliance Evaluation
Filtration (High Rate Tertiary) Yes No NA NE
Comment: Deep - bed sand filters with 12 cells are backwshed constantly.
Disinfection - UV
Yes
No
NA
NE
Are extra UV bulbs available on site?
0
❑
❑
❑
Are UV bulbs clean?
0
❑
❑
❑
Is UV intensity adequate?
■
❑
❑
❑
Is transmittance at or above designed level?
■
❑
❑
❑
Is there a backup system on site?
❑
❑
0
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment: One of two UV channels were in use. Each channel has capacity of 21 MGD.
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: Influent and effluent flow meters are calibrated twice per year.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
■
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
0
❑
❑
❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
❑
❑
❑
representative)?
Comment: The subject permit requires both grab and composite samples.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
■
❑
Page# 8
DocuSign Envelope ID: D33666E2-016E-4ED7-9C33-3664A6FCEB51
Permit: NC0048879 Owner -Facility: North CaryWRF
Inspection Date: 06/16/2023 Inspection Type: Compliance Evaluation
Effluent Pipe
Comment:
Upstream / Downstream Sampling
Is the facility sampling performed as required by the permit (frequency, sampling type,
and sampling location)?
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment:
Chemical Feed
Is containment adequate?
Is storage adequate?
Are backup pumps available?
Is the site free of excessive leaking?
Comment:
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
Yes No NA NE
■ ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 9
DocuSign Envelope ID: D33666E2-016E-4ED7-9C33-3664A6FCEB51
Permit: NCO048879 Owner -Facility: North CaryWRF
Inspection Date: 06/16/2023 Inspection Type: Compliance Evaluation
Solids Handling Equipment Yes No NA NE
Comment: Two gravity belt thickeners dewater wasted sludge. Not in operation at the time of
inspetion ( facility usually wastes sludge at night). Dewatered sludge is stored in two
sludge holding tanks, and then taken to South Cary WRF or Western Wake Regional
WRF for further treatment.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment: Two 0. 75 million gallon aerated sludge holding tanks. Only one was in use.
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Page# 10