Loading...
HomeMy WebLinkAboutWQCSD0406_BIMS Report_20230620Permit: WQCSD0406 SOC: County: Iredell Region: Mooresville Compliance Inspection Report Effective: 11/16/10 Expiration: Owner : Aqua North Carolina Inc Effective: Expiration: Facility: Alexander Island Collection System Contact Person: Shannon V Becker Directions to Facility: System Classifications: Primary ORC: Secondary ORC(s): On -Site Representative(s): Title: President Certification: Related Permits: NC0075205 Aqua North Carolina Inc - Alexander Island WWTP Phone: 919-653-5570 Phone: Inspection Date: 06/14/2023 Entry Time 11:OOAM Exit Time: 12:45PM Primary Inspector: Tony Parker Phone: 704-663-1699 Secondary Inspector(s): Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type: Deemed permitted collection system management and operation Facility Status: Compliant ❑ Not Compliant Question Areas: Miscellaneous Questions General Grease Control Spills/Response Plan Inspections Manholes Pump Stations (See attachment summary) Page 1 of 6 Permit: WQCSD0406 Owner - Facility: Aqua North Carolina Inc Inspection Date: 06/14/2023 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary: Page 2 of 6 Permit: WQCSD0406 Owner - Facility: Aqua North Carolina Inc Inspection Date: 06/14/2023 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine General Yes No NA NE # Is this system a satellite system? ❑ ❑ ❑ # If Yes, what is system name or permit number? Is there a overall sewer system map? ❑ ❑ ❑ Does the map include: Pipe sizes ❑ ❑ ❑ Pipe materials (PVC, DIP, etc) ❑ ❑ ❑ Pipe location ❑ ❑ ❑ # Flow direction ❑ ❑ ❑ # Approximate pipe age ❑ ❑ ❑ # Pump station ID, location and capacity ❑ ❑ ❑ # Force main air release valve location & type ❑ ❑ ❑ # Location of satellite connections ❑ ❑ ❑ Are system maintenance records maintained? ❑ ❑ ❑ ❑ Comment: The utility uses digital and paper maps Grease Control Yes No NA NE Is grease/sewer education program documented with req'd customer distribution? ❑ ❑ ❑ # Are other types of education tools used like websites, booths, special meetings, etc? ❑ ❑ ❑ If Yes, what are they? (This can reduce mailing to annual.) The utility posts FOG info on their website and does mailouts 2/year. For public systems, is there a Grease Control Program via an ordinance/agreement? ❑ ❑ ❑ If Yes, does it require grease control devices at applicable locations? ❑ ❑ ❑ Is the Grease Control Program enforced via periodic inspections/records review? ❑ ❑ ❑ Is action taken against violators? ❑ ❑ 0 ❑ Comment: This is a private deemed system and they have a sewer use policy ( not an ordinance ) approved by the NCUC. Spills and Response Action Plan Yes No NA NE # Is system free of known points of bypass? 0 ❑ ❑ ❑ # Have there been any sewer spills in the past 3 years? ❑ ❑ ❑ If Yes, were they reported to the Division if meeting the reportable criteria? ❑ ❑ ❑ If applicable, is there documentation of press releases and public notices issued? ❑ ❑ ❑ Are all spills or sewer related issues/complaints documented? ❑ ❑ ❑ # Are there repeated overflows/problems (2 or more in 12 months) at same location? ❑ ❑ ❑ # If Yes, is there a corrective action plan? ❑ ❑ ❑ Is a Spill Response Action Plan available? ❑ ❑ ❑ Page 3 of 6 Permit: WQCSD0406 Owner - Facility: Aqua North Carolina Inc Inspection Date: 06/14/2023 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Is a Spill Response Action Plan available for all personnel? 0 ❑ ❑ ❑ Does the plan include: # 24-hour contact numbers ❑ ❑ ❑ # Response time ❑ ❑ ❑ # Equipment list and spare parts inventory ❑ ❑ ❑ # Access to cleaning equipment ❑ ❑ ❑ # Access to construction crews, contractors, and/or engineers ❑ ❑ ❑ # Source of emergency funds ❑ ❑ ❑ # Site sanitation and cleanup materials ❑ ❑ ❑ # Post-overflow/spill assessment ❑ ❑ ❑ Comment: A spill response plan was available. Inspections Yes No NA NE Are adequate maintenance records maintained? 0 ❑ ❑ ❑ Are pump stations being inspected at the required frequency? ❑ ❑ ❑ Is at least one complete functionality test conducted weekly per pump station? ❑ ❑ ❑ Is there a system or plan in place to observe the entire system annually? ❑ ❑ ❑ Is the annual inspection documented? ❑ ❑ ❑ # Does the system have any high -priority lines/locations? ❑ ❑ ❑ Are inspections of HPL documented at least every 6 months? ❑ ❑ ❑ Are new lines being added to the HPL list when found or created? ❑ ❑ ❑ Comment: The system has no HPL's Manholes Yes No NA NE Please list the Manholes Inspected: Various manholes inspected. The influent manhole for the Alexander Island lift station needs rehab. The frame and cover needs to be replaced and the bottom of the manhole has deterioated due to water fall effect from a high invert with no drop pipe. Therefore, the bottom needs rehab and the high drop may need an inside drop pipe to prevent deterioation of the bottom. Are manholes accessible? ❑ ❑ ❑ # Are manhole covers/vents above grade? ❑ ❑ ❑ Are manholes free of visible signs of overflow? ❑ ❑ ❑ Are manholes free of sinkholes and depressions? ❑ ❑ ❑ Are manhole covers present? ❑ ❑ ❑ # Are manholes properly seated? ❑ ❑ ❑ # Are manholes in good condition? ❑ ❑ ❑ # Are inverts in good condition? ❑ ❑ ❑ Is flow unrestricted in manholes? ❑ ❑ ❑ Are manholes free of excessive amounts of grease? ❑ ❑ ❑ Page 4 of 6 Permit: WQCSD0406 Owner - Facility: Aqua North Carolina Inc Inspection Date: 06/14/2023 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Are manholes free of excessive roots? 0 ❑ ❑ ❑ Are manholes free of excessive sand? 0 ❑ ❑ ❑ Are manhole vents screened? ❑ ❑ 0 ❑ Are vents free of submergence? ❑ ❑ 0 ❑ Are manholes free of bypass structures or pipes? 0 ❑ ❑ ❑ Comment: See above comments on manholes. Pump Stations Yes No NA NE Please list the Pump Stations Inspected: Alexander Island lift station. No issues with this lift station noted. # Number of duplex or larger pump stations in system 1 # Number of vacuum stations in system 0 # Number of simplex pump stations in system 0 # Number of simplex pump stations in system serving more than one building 0 How many pump/vacuum stations have: # A two-way "auto polling" communication system (SCADA) installed? 0 # A simple one-way telemetry/communication system (auto -dialer) installed? 1 For pump stations inspected: Are they secure with restricted access? 0 ❑ ❑ ❑ Were they free of by-pass structures/pipes? 0 ❑ ❑ ❑ Were wet wells free of excessive grease/debris? 0 ❑ ❑ ❑ # Do they all have telemetry installed? 0 ❑ ❑ ❑ Is the telemetry system functional? 0 ❑ ❑ ❑ Is a 24-hour notification sign posted ? 0 ❑ ❑ ❑ Does the sign include: Owner Name? 0 ❑ ❑ ❑ Pump station identifier? 0 ❑ ❑ ❑ # Address? ❑ ❑ 0 ❑ Instructions for notification? 0 ❑ ❑ ❑ 24-hour emergency contact numbers? 0 ❑ ❑ ❑ Are audio and visual alarms present? 0 ❑ ❑ ❑ Are audio and visual alarms operable? 0 ❑ ❑ ❑ # Is there a backup generator or bypass pump connected? 0 ❑ ❑ ❑ If tested during inspection, did it function properly? 0 ❑ ❑ ❑ Is the back-up system tested at least bi-annually under normal operating conditions? 0 ❑ ❑ ❑ # Does it have a dedicated connection for a portable generator? ❑ ❑ 0 ❑ # Is the owner relying on portable units in the event of a power outage? ❑ ❑ 0 ❑ Page 5 of 6 Permit: WQCSD0406 Owner - Facility: Aqua North Carolina Inc Inspection Date: 06/14/2023 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine # If Yes, is there a distribution plan? If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan? This lift station is supported by the dedicated WWTP generator located nearby. The generator was tested under load and the US and generator functioned without issues. In addition the utility has a fleet of portable generators availabe if needed. # Does Permittee have the approved percentage of replacement simplex pumps? Is recordkeeping of pump station inspection and maintenance program adequate? Do pump station logs include at a minimum: Inside and outside cleaning and debris removal? Inspecting and exercising all valves? Inspecting and lubricating pumps and other equipment? Inspecting alarms, telemetry and auxiliary equipment? Comment: No issues with the lift station and records wre available for all activities. ❑❑■❑ ❑❑■❑ ■❑❑❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page 6 of 6