We are re-submitting the portions of the stormwater application and documents that
have been revised/created per the comments received on November 15.
Please correct the following:
- General:
°Ao The provided Swale velocity&flow depth information shown in the
Supplement EZ Form should reflect the permanent design conditions, not on
the temporary matting. For example,the provided calculations show the l
unreinforced vegetated Swale#2 as having a 10-year design flow of 3.65 fps,
however the Supplement-EZ Swale Table shows the actual velocity of this Swale
as 5.69 fps (based on the calculations for the temporary C125 matting). Please
revise the Vallowable,Vactual, F Depth, Liner,&SF columns in the table to
reflect the permanent design conditions.
■ The chart has been updated to reflect the velocities and flow depth for
the permanent conditions.The columns for the liner and safety factor
were removed.
- Vegetated Conveyance Design:
o Please provide a source for the allowable velocities of the vegetated
conveyances if using values other than those found in Part C-11 of the Manual.
■ The allowable velocities were modified to match the manual.
o The slope of Swale#1 is shown to be 3.0%in the Swale Table of the
Supplement-EZ Form and 0.7% in the calculations. Please revise as needed.
■ The slope in the Swale table was modified to 0.7%to match the
calcuations. i
o The ditch detail on plan sheet C-6.0 indicates to"see plans"for the bottom
width of the ditches. I didn't see the ditch bottom widths shown in the plans.
Please ensure that this information is specified in the plans.
■ The ditch detail has been modified to indicate all ditches have a 0.5'flat
bottom unless otherwise specified on the plans. Ditch 1 &31 have their
widths noted on the plans.
- Supplement-EZ Form:
o Low-Density Page:
■ Revise as needed in accordance with the earlier comments.
409 Chicago Drive,Suite 112, Fayetteville,NC 28306
office 910-426-6777 fax 4 910-426-5777
On time,every time. wwwADsitesotutions.con-i
• Document was updated to reflect the revised maximum
velocity.
If you have any questions or comments, please contact me at your earliest convenience.