HomeMy WebLinkAboutNC0055212_Compliance Evaluation Inspection_20150611 ASA
NCDENR
North Carolina Department of Environment and Natural Resources
Pat McCrory Donald R. van der Vaart
Governor Secretary
June 11, 2015
RECEIVED/DENR/DWR
Auman's Mobile Home Park, LLC
Attn: Barbara N. Auman, Owner 'JUN J 6 2015
3910-2 North Main Street
High Point, NC 27265-1217 Water Quality
Permitting Sectior
Subject: Compliance Evaluation Inspection
Permittee: Auman's Mobile Home Park, LLC
Facility: Auman's Mobile Home Park Wastewater Treatment Plant
NPDES Permit#: NC0055212
Forsyth County
Dear Ms. Auman:
Ron Boone, of the Winston-Salem Regional Office of the NC Division of Water Resources (DWR or
the Division) conducted a compliance evaluation inspection (CEI) of the Auman's Mobile Home Park
Wastewater Treatment Plant (WWTP) on June 2, 2015. Your assistance and cooperation was greatly
appreciated. An inspection checklist is attached for your records and inspection findings are summarized
below.
General Information
The mobile home park is located at 3910-2 North Main Street, in High Point, Forsyth County, NC. The
WWTP is located on the north side of the mobile home park (MHP) at coordinates 36.018002°N, -
80.051194°W. Although in Forsyth County, the park/plant are actually located at a High Point address. The
permit authorizes you to operate this 0.016 MGD WWTP, which consists of three 3,000 gallon septic tanks
with 1,000 gallon pump tanks, a 6,000 gallon gravity fed septic tank, a 2,000 gallon detention tank, dual
surface sand filters, a 4,000 gallon final tank with alternating pumps, an ultraviolet disinfection system, and a
backup chlorine disinfection system with dechlorination. The permit authorizes you to discharge the treated
effluent from the WWTP via outfall 001 to Rich Fork Creek, which is currently classified as Class C waters and
is located in the Yadkin Pee-Dee River basin.
Site Review
The entire plant was very well maintained and in good condition. Mr. Boone noted no problems or
discrepancies.
Documentation Review
450 West Hanes Mill Road,Suite#300,Winston-Salem,North Carolina 27105
Phone:336-776-98001 Internet:www.ncdenr.gov
An Equal Opportunity 1 Affirmative Action Employer-Made in part by recycled paper
4
All documentation was reviewed and no discrepancies were found. You have done an excellent job
documenting the operation and maintenance of the plant as required by the permit; this includes operations
and visitation logs, discharge monitoring reports, laboratory and field laboratory records, chains of custody,
sludge pumping records, etc.
If you have any questions regarding the inspection or this letter, please call Mr. Boone or me at (336)
776-9800. Thank you for your cooperation in this matter.
Sincerely,
}
W. Corey Basinger
Surface Water Regional Supervisor
Winston-Salem Regional Office
Division of Water Quality
Attachments:
1. BIMS Inspection Report
CC: WSRO-SWP
Central Files
NPDES Unit
•
4
United States Environmental Protection Agency Form Approved.
EPA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 �N I 2 I5 3 I NC0055212 111 12 I 15/06/02 117 18 12. 19 S 201 I
2111_1 I I I I I I I I I I I 1 j I I I I I 1 1 1 I I I I I I 1 1 I I l l l 1 1 1 1 I I 166
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved ----
671 70 LJ I u
I 71 Li 72 I " I 731 I 174 751 1 1 1 1 I 1 180
Section B:Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 10:00AM 15/06/02 14/05/01
Auman's Mobile Home Park WWTP
Exit Time/Date Permit Expiration Date
3910-2 N Main St
11:00AM 15/06/02 19/04/30
High Point NC 272851217
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Barbara N Auman/ORC/919-883-3910/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Barbara N Auman,3910-2 N Main St High Point NC 272651217//336-883-3910/
No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
op Permit • Flow Measurement II Operations&Maintenance el Records/Reports
di Self-Monitoring Program Ni Facility Site Review • Effluent/Receiving Waters • Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone WSRO WQ//336-776-9690/ , -
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NC 0055212 I11 121 15/08/02 117 18
Section D:Summary of Finding/Comments(Mach additional sheets of narrative and cheddists as necessary)
Please refer to the attached inspection summary letter.
F ♦ A ..
Page* 2
•
Permit NC0055212 Owner-Facility: Auman's Mobile Home Park WWTP
Inspection Date: 06/02/2015 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0 0 III 0
application?
Is the facility as described in the permit? • 0 0 0
#Are there any special conditions for the permit? 0 • 0 0
Is access to the plant site restricted to the general public? • 0 0 0
Is the inspector granted access to all areas for inspection? • 0 0 0
Comment: None
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • 0 0 0
Is all required information readily available, complete and current? • 0 0 0
Are all records maintained for 3 years(lab. reg. required 5 years)? • 0 0 0
Are analytical results consistent with data reported on DMRs? U 0 0 0
Is the chain-of-custody complete? • 0 0 0
Dates,times and location of sampling •
Name of individual performing the sampling U
Results of analysis and calibration •
Dates of analysis U
Name of person performing analyses
Transported COCs •
Are DMRs complete:do they include all permit parameters? • 0 0 0
Has the facility submitted its annual compliance report to users and DWQ? 0 ❑ • 0
(If the facility is=or>5 MGD permitted flow)Do they operate 24/7 with a certified operator 0 U 0 0
on each shift?
Is the ORC visitation log available and current? • 0 0 0
Is the ORC certified at grade equal to or higher than the facility classification? • 0 0 0
Is the backup operator certified at one grade less or greater than the facility classification? • 0 0 0
Is a copy of the current NPDES permit available on site? • 0 0 0
Facility has copy of previous year's Annual Report on file for review? 0 0 • 0
Comment: None
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • 0 0 0
Are all other parameters(excluding field parameters)performed by a certified lab? • 0 0 0
Page# 3
•
Permit: NC0055212 Owner-Facility: Auman's Mobile Home Park VVWTP
Inspection Date: 06/02/2015 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
#Is the facility using a contract lab? • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees 0 0 0 •
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? 0 0 0 •
Incubator(BOD)set to 20.0 degrees Celsius+/-1.0 degrees? 0 0 0 U
Comment: None
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? 0 0 II 0
Is sample collected below all treatment units? • 0 0 0
Is proper volume collected? • 0 0 0
Is the tubing clean? 0 0 • 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees 0 0 0 •
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type • 0 0 0
representative)?
Comment: None
Upstream/Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit(frequency, sampling type, and • 0 0 0
sampling location)?
Comment: None
Flow Measurement-Influent Yes No NA NE
#Is flow meter used for reporting? • 0 0 0
Is flow meter calibrated annually? 0 0 0 III
Is the flow meter operational? • 0 0 0
(If units are separated)Does the chart recorder match the flow meter? 0 0 MI 0
Comment: Facility uses city water meter for flow readings.
Septic Tank Yes No NA NE
(If pumps are used)Is an audible and visual alarm operational? 0 II 0 0
Is septic tank pumped on a schedule? • 0 0 0
Are pumps or syphons operating properly? • 0 0 0
Page# 4
a
a
Permit NC0055212 Owner-Facility: Auman's Mobile Home Park VVVVTP
Inspection Date: 06/02/2015 Inspection Type: Compliance Evaluation
Septic Tank Yes No NA NE
Are high and low water alarms operating properly? 0 0 • 0
Comment: None
Sand Filters (Low rate) Yes No NA NE
(If pumps are used)Is an audible and visible alarm Present and operational? 0 0 • 0
Is the distribution box level and watertight? 0 0 0 •
Is sand filter free of ponding? U 0 0 0
Is the sand filter effluent re-circulated at a valid ratio? • 0 0 0
#Is the sand filter surface free of algae or excessive vegetation? • 0 0 0
#Is the sand filter effluent re-circulated at a valid ratio?(Approximately 3 to 1) • 0 0 0
Comment: None
Disinfection - UV Yes No NA NE
Are extra UV bulbs available on site? • 0 0 0
Are UV bulbs clean? • ❑ 0 0
Is UV intensity adequate? • 0 0 0
Is transmittance at or above designed level? U 0 0 0
Is there a backup system on site? • 0 0 0
Is effluent clear and free of solids? • 0 0 0
Comment: None
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? • 0 0 0
Are the receiving water free of foam other than trace amounts and other debris? • 0 0 0
If effluent (diffuser pipes are required) are they operating properly? 0 ❑ • 0
Comment: None
Operations& Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • 0 0 ❑
Does the facility analyze process control parameters,for ex: MLSS, MCRT, Settleable 0 • 0 0
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Page# 5