HomeMy WebLinkAboutNC0024872_Compliance Evaluation Inspection_20230519 (2)United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO024872 111 121 23/05/11 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I ni I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
08:OOAM 23/05/11
21/10/01
Cooleemee WWTP
NC Hwy 801 S
Exit Time/Date
Permit Expiration Date
Cooleemee NC 27014
10:OOAM 23/05/11
26/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Timothy Lamar Smith/ORC/336-284-6680/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Tim Smith,NC Hwy 801 S Cooleemee NC 27014/ORC/336-284-6680/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar 0 Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Gary Hudson DWR/Division of Water Qua Iity/336-776-9694/
DocuSigned by:
a OttIS&A, 5/18/2023
8B 22824F 6 4A6.
Signa ure of anagement Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by: 5/18/202 3
L o' -T. 5,,o r
EPA "4 99&4 @R +A9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO024872 I11 12I 23/05/11 117 18 i c i
(Cont.) 1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
*The WWTP appeared to be well operated and maintained. No discrepancies were noted during the
inspection.
*The permit became effective on October 1, 2021, and will expire on June 30, 2026.
*Mr. Smith does a very good job with regards to keeping records.
*The June 2022 eDMR was checked with the contract lab reports. No discrepancies were noted.
*The mechanical bar screen is located in the main pump station on the other side of the South Yadkin
River.
*The aeration basin appeared to be operating properly. There is a floating mechanical aerator and a
floating mixer in each of the aeration basins.
*The secondary clarifier appeared to be working properly. The effluent leaving the clarifier was very
clear on the day of the inspection.
*The effluent pipe was located. The discharge was very clear at the time of the inspection.
*The effluent flow meter was last calibrated on March 28, 2023.
Page# 2
Permit: NCO024872
Inspection Date: 05/11/2023
Owner -Facility: Cooleemee WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ■ ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The WWTP appeared to be well operated and maintained. No discrepancies were
noted during the inspection.
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
■
❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
❑
■
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: The permit became effective on October 1, 2021, and will expire on June 30,
2026.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
■
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
■
❑
❑
❑
classification?
Page# 3
Permit: NCO024872 Owner -Facility: Cooleemee WWTP
Inspection Date: 05/11/2023 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? 0 ❑ ❑ ❑
Comment: Mr. Smith does a very good mob with regards to keeping records.
The June 2022 eDMR was checked with the contract lab reports. No discrepancies
were noted.
Bar Screens
Type of bar screen
Yes No NA NE
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
■
❑
❑
❑
Is the screen free of excessive debris?
■
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: The mechanical bar screen is located in the main
pump station on the other side of the
South Yadkin River.
Aeration Basins
Yes
No
NA
NE
Mode of operation
Ext. Air
Type of aeration system
Surface
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
❑
❑
■
❑
Is the foam the proper color for the treatment process?
■
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
■
Comment: The aeration basin appeared to be operating properly. There is a floatinq mechanical
aerator and a floating mixer in each of the aeration basins.
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Page# 4
Permit: NCO024872
Inspection Date: 05/11/2023
Owner -Facility: Cooleemee WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier
Yes
No
NA
NE
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
■
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
■
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4
of the sidewall depth) ❑
❑
❑
Comment: The secondary clarifier appeared to be working properly. The effluent leaving the
clarifier was very clear on the day of the inspection.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
❑
❑
Comment: The effluent pipe was located. The discharge was very clear at the time of the
inspection.
The effluent flow meter was last calibrated on March 28, 2023.
Page# 5