HomeMy WebLinkAboutNC0060283_NOV2023PC0176 & CEI Report_20230501
May 01, 2023
Joel K Brown
Ridgeview N C M H C LLC
31200 Northwestern Hwy
Farmington Hls, MI 48334
SUBJECT: NOTICE OF VIOLATION
Tracking Number: NOV-2023-PC-0176
Permit No. NC0060283
Ridgeview Acres Mobile Home Park
Buncombe County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Ridgeview Acres Mobile Home
Park on February 16, 2023. This inspection was conducted to verify that the facility is operating in compliance
with the conditions and limitations specified in NPDES WW Permit No. NC0060283. A summary of the findings
and comments noted during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following violation(s) were noted during the inspection:
Inspection Area Description of Violation _________________________________________________________________________________________________________________________________________________________________________ Operations & Maintenance The location and number of the sand filters and septic tanks is unknown.
_________________________________________________________________________________________________________________________________________________________________________
In addition, the issues below must also be addressed:
Compliance Issue(s): This facility has been routinely failing whole effluent toxicity testing. The
cause of these failures needs to be discovered and abated.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law.
DocuSign Envelope ID: 7B59795F-F296-4FA9-93CB-4A162A007A01
To prevent further action, please respond in writing to this office within 30 days upon your receipt of this Notice
of Violation regarding your plans or measures to be taken to address the indicated violations and other identified
issues, if applicable.
If you should have any questions, please do not hesitate to contact me with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4500.
Sincerely,
Daniel Boss, Assistant Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Ec: Laserfiche
DocuSign Envelope ID: 7B59795F-F296-4FA9-93CB-4A162A007A01
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0060283 23/02/16 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Ridgeview Acres Mobile Home Park
5 Impala Trl
Asheville NC 28806
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
01:30PM 23/02/16 21/10/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Mark Brandon Jones/ORC/828-273-0760/
Other Facility Data
02:15PM 23/02/16 25/10/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Trevor Clyde McMinn,2020 Howard Gap Rd Hendersonville NC
287929238//828-696-8971/8286968971
Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Self-Monitoring Program
Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Mara G Chamlee DWR/ARO WQ/828-296-4500/
Daniel J Boss DWR/ARO WQ/828-296-4658/
Timothy H Heim DWR/ARO WQ/828-296-4665/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 7B59795F-F296-4FA9-93CB-4A162A007A01
5/1/2023
5/1/2023
NPDES yr/mo/day
23/02/16
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 2/16/2023, I (Daniel Boss), Tim Heim, and Mara Chamlee conducted a Compliance Evaluation
Inspection of the Ridgeview Acres Mobile Home Park WWTP. We met with the ORC, Mark Jones, for
the inspection.
Mr. Jones didn't know the number of septic tanks in the system nor the number of sand filters in the
system.
This facility didn't discharge any effluent from October 2022 through December 2022. Mr. Jones
believes this may have been caused by a diversion of groudwater during that period. The presence
of iron bacteria on the aeration cascade supports the idea that much of the effluent flow is actually
groundwater infiltrating the wastewater treatment system.
NC0060283 17 (Cont.)
Page#2
DocuSign Envelope ID: 7B59795F-F296-4FA9-93CB-4A162A007A01
Permit:NC0060283
Inspection Date:02/16/2023
Owner - Facility:
Inspection Type:
Ridgeview Acres Mobile Home Park
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
There is no barrier around the plant components.Comment:
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
The number, location, and pumping schedule for the septic tanks is unknown.Comment:
Sand Filters (Low rate)Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re-circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re-circulated at a valid ratio? (Approximately 3 to 1)
The location and number of sand filters is unknown.Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?1
Page#3
DocuSign Envelope ID: 7B59795F-F296-4FA9-93CB-4A162A007A01
Permit:NC0060283
Inspection Date:02/16/2023
Owner - Facility:
Inspection Type:
Ridgeview Acres Mobile Home Park
Compliance Evaluation
Disinfection-Tablet Yes No NA NE
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?2
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Page#4
DocuSign Envelope ID: 7B59795F-F296-4FA9-93CB-4A162A007A01
Permit:NC0060283
Inspection Date:02/16/2023
Owner - Facility:
Inspection Type:
Ridgeview Acres Mobile Home Park
Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type,
and sampling location)?
Comment:
Page#5