HomeMy WebLinkAboutNC0070394_NOVNOI2023PC0130 & CEI Report_20230405 (5)Certified Mail # 7022 0410 0002 1249 8279
Return Receipt Requested
April 5, 2023
Max H Hopper
Willowbrook Run Property Owners Association
PO Box 182
Linville Falls, NC 28647-0182
SUBJECT: NOTICE OF VIOLATION & INTENT TO ASSESS CIVIL PENALTY
Tracking Number: NOV-2023-PC-0130
Permit No. NC0070394
Willowbrook Run POA WWTP
Macon County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Willowbrook Run POA WWTP on
March 23, 2023. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0070394. A summary of the findings and
comments noted during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following violation(s) were noted during the inspection:
Inspection Area Description of Violation
_________________________________________________________________________________________________________________________________________________________________________
Operations & Maintenance There are multiple deferred maintenance issues at the facility that pose safety hazards.
[NC0070394 Part II. Standard Conditions - Section C. 2. Proper Operation &
Maintenance - The Permittee shall at all times properly operate and maintain all
facilities and systems of treatment and control (and related appurtenances) which
are installed or used by the Permittee to achieve compliance with the conditions of
this permit.]
_________________________________________________________________________________________________________________________________________________________________________
DocuSign Envelope ID: F1B3614A-3929-4647-9B71-E7C81F3C9942
_________________________________________________________________________________________________________________________________________________________________________
Secondary Clarifier The line that goes from the clarifier to the chlorine contact chamber needs to be more
thoroughly stabilized to prevent the line from breaking.
[NC0070394 Part II. Standard Conditions - Section C. 2. Proper Operation &
Maintenance - The Permittee shall at all times properly operate and maintain all
facilities and systems of treatment and control (and related appurtenances) which
are installed or used by the Permittee to achieve compliance with the conditions of
this permit.]
_________________________________________________________________________________________________________________________________________________________________________
Disinfection-Tablet The chlorine contact chamber has a leak and treated wastewater is ponding on the ground.
[NC0070394 Part II. Standard Conditions - Section C. 2. Proper Operation &
Maintenance - The Permittee shall at all times properly operate and maintain all
facilities and systems of treatment and control (and related appurtenances) which
are installed or used by the Permittee to achieve compliance with the conditions of
this permit.]
_________________________________________________________________________________________________________________________________________________________________________
Effluent Pipe The effluent pipe could not be located.
[NC0070394 Part II. Standard Conditions - Section C. 2. Proper Operation &
Maintenance - The Permittee shall at all times properly operate and maintain all
facilities and systems of treatment and control (and related appurtenances) which
are installed or used by the Permittee to achieve compliance with the conditions of
this permit.]
_________________________________________________________________________________________________________________________________________________________________________
A Notice of Violation/Intent to Issue Civil Penalty is being issued for the noted violation of North Carolina General
Statute (G.S.) 143-215.1 and the facility’s NPDES WW Permit. Pursuant to G.S. 143-215.6A, a civil penalty of
not more than twenty-five thousand dollars ($25,000.00) may be assessed against any person who violates or
fails to act in accordance with the terms, conditions, or requirements of any permit issued pursuant to G.S.
143-215.1.
If you wish to provide additional information regarding the noted violation, request technical assistance, or discuss
overall compliance please respond in writing within ten (10) business days after receipt of this Notice. A review of
your response will be considered along with any additional information provided. You will then be notified of any
civil penalties that may be assessed regarding the violations. If no response is received in this Office
within the 10-day period, a civil penalty assessment may be prepared.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law. If the violations are of a continuing nature, not related to operation and/or maintenance problems, and
you anticipate remedial construction activities, then you may wish to consider applying for a Special Order by
Consent.
Reminder: Pursuant to Permit Condition 6 in Section E, the Permittee is required to verbally notify the Regional
Office as soon as possible, not to exceed 24 hours, from first knowledge of any non-compliance at
the facility including limit violations, bypasses of, or failure of a treatment unit. A written report may
be required within 5 days if directed by Division staff. Prior notice should be given for anticipated or
potential problems due to planned maintenance activities, taking units off-line, etc.
DocuSign Envelope ID: F1B3614A-3929-4647-9B71-E7C81F3C9942
If you should have any questions, please do not hesitate to contact Lauren Armeni with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4667.
Sincerely,
Daniel Boss, Assistant Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Laserfiche
Mark Teague (ORC, Environmental Inc.)
DocuSign Envelope ID: F1B3614A-3929-4647-9B71-E7C81F3C9942
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0070394 23/03/23 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Willowbrook Run POA WWTP
17 McClure Mill Rd
Franklin NC 28734
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
11:30AM 23/03/23 18/07/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Mark Fredrick Teague/ORC/828-586-5588/
Other Facility Data
01:00PM 23/03/23 22/11/30
Name, Address of Responsible Official/Title/Phone and Fax Number
Max H Hopper,PO Box 182 Linville Falls NC 286470182//704-534-4500/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Melanie Kemp DWR/ARO WQ/ - - /
Lauren E Armeni DWR/ARO WQ/828-296-4500/
Mara G Chamlee DWR/ARO WQ/828-296-4500/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: F1B3614A-3929-4647-9B71-E7C81F3C9942
4/5/2023
4/5/2023
4/5/2023
4/5/2023
NPDES yr/mo/day
23/03/23
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Lauren Armeni, Mara Chamlee, and Melanie Kemp, with the Asheville Regional Office, conducted a
Compliance Evaluation Inspection of Willowbrook Run POA WWTP on March 23, 2023. This
inspection was conducted to determine whether the facility is being operated and maintained in
compliance with NPDES Permit No. NC0070394. Mr. Mark Teague (ORC, Environmental Inc.) and
Mr. Zach Story (BORC in-training, Environmental Inc.) were present and assisted in the inspection.
The following items were noted during the inspection:
Operations & Maintenance: Overall, the facility is in need of maintenance and repair. There is no
ladder to get up to the aeration basin, clarifier, and digester. Some components are rusting and need
to be painted. There are still missing and unstable rails around the aeration basin and secondary
clarifier. The grates on top of the aeration basin and secondary clarifier are rusted and missing in
some areas. Additionally, the ground adjacent to the secondary clarifier is eroded with pipe exposed.
These issues pose safety hazards and need to be fixed and/or replaced.
Secondary Clarifier: The line going from the secondary clarifier to the chlorine contact chamber is
stabilized with a single bar and does not appear stable. This line should be more thoroughly stabilized
to prevent it from breaking and causing a bypass to land and potentially surface water.
Disinfection - Tablet: At the time of the inspection, a leak in the chlorine contact chamber was
discovered, and treated wastewater was pooled on the ground. Mr. Teague indicated that the leak
would be patched from the inside. This contact chamber is old and has been patched many times.
The integrity of the contact chamber should be evaluated to determine if it should be replaced.
Effluent Pipe: At the time of the inspection, the effluent pipe could not be located due to steep terrain
and inaccessibility. Mr. Teague indicated that a gate should be installed to allow easier access to
locate and maintain the effluent pipe. Per the permit, the right of way to the outfall needs to be
maintained in order to evaluate the receiving waters and condition of the effluent pipe.
The following violations were noted during the inspection:
1.Operations & Maintenance: There are multiple deferred maintenance issues at the facility that
pose safety hazards.
2.Secondary Clarifier: The line that goes from the clarifier to the chlorine contact chamber needs to
be more thoroughly stabilized to prevent the line from breaking.
3.Disinfection - Tablet: The chlorine contact chamber has a leak and treated wastewater is ponding
on the ground.
4.Effluent Pipe: The effluent pipe could not be located.
NC0070394 17 (Cont.)
Page#2
DocuSign Envelope ID: F1B3614A-3929-4647-9B71-E7C81F3C9942
Permit:NC0070394
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Willowbrook Run POA WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
The facility analyzes the following process controls: temperature, DO, pH, and MLSS.
Overall, the facility is rusting and needs to be painted. Additionally, there are still
broken and missing rails around the aeration basin and clarifier. The grates on top of
these components are rusted and missing in some parts. There are several safety
hazards throughout the plant. See summary for details.
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment:
Bar Screens Yes No NA NE
Type of bar screen
Page#3
DocuSign Envelope ID: F1B3614A-3929-4647-9B71-E7C81F3C9942
Permit:NC0070394
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Willowbrook Run POA WWTP
Compliance Evaluation
Bar Screens Yes No NA NE
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Influent flow initially enters a pump station with a grinder pump. This pump station is
maintained by Willowbrook Run POA. Return activated sludge from the clarifier goes
through the bar screen prior to entering the aeration basin.
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
At the time of the inspection, the DO was taken by Mr. Story and read 7.4 mg/L, which
is higher than the desired range but has not affected the treatment. The blowers run
for thirty minutes every hour during the day and fifteen minutes every hour at night. DO
has been higher lately due to the warmer weather. Mr. Teague indicated that the basin
needs a new header line because air is being lost.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Page#4
DocuSign Envelope ID: F1B3614A-3929-4647-9B71-E7C81F3C9942
Permit:NC0070394
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Willowbrook Run POA WWTP
Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
At the time of the inspection, the sludge blanket was 1' out of a 7' deep clarifier. The
line that goes from the clarifier to the chlorine contact chamber is stabilized by a single
bar and should be further stabilized to prevent the line from breaking. See summary for
details.
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?1
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
At the time of the inspection, there was a leak in the chlorine contact chamber and
wastewater pooling on the ground. The chamber is aboveground and old, and has
been patched many times. Mr. Teague indicated that they would patch the leak from
the inside of the chamber since in the past they have been patching the outside. See
summary for details.
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?1
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
Page#5
DocuSign Envelope ID: F1B3614A-3929-4647-9B71-E7C81F3C9942
Permit:NC0070394
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Willowbrook Run POA WWTP
Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
(If units are separated) Does the chart recorder match the flow meter?
Flow is manually measured weekly.Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
At the time of the inspection, the effluent pipe could not be located. Currently, there is
not a very accessible way to get to the area where the effluent pipe is located due to a
steep bank. Mr. Teague indicated that the facility needs a gate installed to access and
maintain the effluent pipe. See summary for details.
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
There is a manual bar screen at the facility but it is not listed in the facility components
list on the current permit; however, the permit is currently under renewal and this issue
will be addressed.
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
The permit requires grab sampling.Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Page#6
DocuSign Envelope ID: F1B3614A-3929-4647-9B71-E7C81F3C9942
Permit:NC0070394
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Willowbrook Run POA WWTP
Compliance Evaluation
Aerobic Digester Yes No NA NE
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Mr. Teague indicated that the digester has the capability of being aerated, but he is
unable to get to the diffuser. He said the new header line would also fix this issue.
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
There is no permanent generator at the facility. Mr. Teague indicated that if the power
were to go out, the well pump supplying water to the homes would also not work, and
therefore no additional flow would go to the WWTP during this time.
Comment: