HomeMy WebLinkAboutNC0089478_Minor Permit Mod_20150519 tr
NCDENR
North Carolina Department of Environment and Natural Resources
Pat McCrory Donald R. van der Vaart
Governor Secretary
May 19, 2015
Paul P. Vest,President and CEO
YMCA of Western Carolina
53 Asheland Avenue, Suite 105
Asheville,North Carolina 28801
Subject:NPDES Minor Permit Modification
Permit NCO089478
Camp Watia WWTP
Swain County
Class II
Dear Mr. Vest:
In accordance with your request to provide an intermediate 0.006 MGD limitation page in your
NPDES permit to accommodate your December 12, 2014 Authorization to Construct application for
the first phase of construction for 0.006 MGD treatment capacity, a minor permit modification is being
issued. As we discussed, except for the permitted flow both limitation pages, 0.006 MGD and 0.012
MGD have the identical limits and monitoring requirements. To expand to 0.012 MGD will require
you to obtain an Authorization to Construct permit for the 0.012 MGD expanded flow. Additional
technical corrections were made to narratives and formatting where warranted.
Please insert the attached minor modification pages in your existing permit and discard any
pages that are duplicated by the minor modification pages.
Please note that this permit is not transferable except after notice to the Division. The Division
may require modification or revocation and reissuance of the permit. This permit does not affect the
legal requirements to obtain other permits which may be required by the Division of Water Resources
or any other Federal, State, or Local governmental permits that may be required.
1617 Mail Service Center,Raleigh,North Carolina 27699-1617
Location:512 N.Salisbury St Raleigh,North Carolina 27604
Phone:919$07.63001 Fax:919-807-6494
Internet www.ncdenr.gov
An Equal OpportunityWffirma6ve Acton Employer
7MPaulP. Vest, President and CEO
ay 19, 2015
Page 2 of 2
If you have any questions concerning this permit,please contact Ron Berry at telephone
number(919) 807-6396 or at email ron.berry@ncdenr.gov.
Sincerely,
Ron Berry
Environmental Engineer,Division of Water Resources
Enclosure: Modified NPDES Permit NC0089478
cc: NPDE
S File
Central Files
Asheville Regional Office/Water Quality Programs (attach Fact Sheet Addendum)
ecopy:
William Lapsley,P.E., WGLA Engineering, PLLC
Email: wlapsley@wgla.com
Permit NCO089478
SUPPLEMENT TO PERMIT COVER SHEET
[New permit]
YMCA of Western Carolina
is hereby authorized to:
1. begin operating a 0.006 MGD, 100%-domestic wastewater treatment facility,to be located at the
proposed YMCA Camp Watia, 5030 Watia Creek Road, Bryson City;
2. after submitting plans and specifications signed by a North Carolina-certified engineer in
application for the Division'•s Authorization to Construct(ATC)permit, and after submitting an
Engineer's Certification following the completion of WWTP construction, and
3. begin operating an expanded 0.012 MGD 100%-domestic wastewater treatment facility after
submitting plans and specifications for expansion signed by a North Carolina-certified engineer in
application for the Division's Authorization to Construct(ATC)permit, and after submitting an
Engineer's Certification following the completion of expanded WWTP construction,
4. discharge from said treatment works via proposed Outfall 001, as located on the attached map, into
the Townhouse Branch [Stream Segment 2-58], a waterbody currently classified C within subbasin
04-04-02 of the Little Tennessee River Basin.
Page 2 of 6
PART 1
A. (L) EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
During the period beginning on the effective date of this permit and after receipt of the signed
Engineer's Certificate for completion of construction for 0.006 MGD, and lasting until expiration or
expansion to 0.012 MGD,the Permittee is authorized to discharge from Outfall 001. Such discharges
shall be limited and monitored 1 by the Permittee as specified below:
EFFLUENT LIMITS MONITORING REQUIREMENTS 1
CHARACTERISTICS Monthly Daily Measurement Sample Sample
[Parameter Code] Average Maximum Frequency Type Location 2
Flow 50050 0.006 MGD Weekly Instantaneous I or E
Total Residual Chlorine 3 50060 28 pg/L 2/Weekly Grab E
Dissolved Oxygen 00300 Weekly Grab E
pH 00400 Not<6.0 nor>9.0 Weekly Grab E
standard units
Temperature(°C) 00010 Weekly Grab E
Fecal Coliform 31616 200/ 100 ml 400/100 ml 2/Monthly Grab E
(geometric mean)
BOD,5-day(20°C) C0310 30.0 mg/L 45.0 mg/L 2/Monthly Grab E
Total Suspended Solids C0530 30.0 mg/L 45.0 mg/L 2/Monthly Grab E
Ammonia[NH3 as N] C0610 13 mg/L 35 mg/L 2/Monthly Grab E
Footnotes:
1. eDMR-beginning no later than 270 days from the effective date of this permit,the Permittee shall
report electronically all discharge monitoring data using NCDWR's Electronic Discharge Monitoring
Report(eDMR)internet application(see Section A. (3.).
2. Sampling: E=Effluent;I=Influent. A given effluent sample shall accurately represent the chemical
and physical character of its discharge event.
3. Total Residual Chlorine(TRC)—The Permittee shall monitor and report Total Residual Chlorine
only if chlorine is used to disinfect. TRC effluent concentrations reported below 50pg/L shall be
deemed compliant with this permit, however the Permittee shall submit all levels reported by NC-
certified test methods(including field certified),even if these levels are below 50gg/L.
Condition:
• The Permittee shall discharge no floating solids or foam.
Page 3 of 6
A. (2.) EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
During the period beginning on the effective date of this permit and after receipt of the signed
Engineer's Certificate for completion of construction for expansion to 0.012 MGD, and lasting until
expiration,the Permittee is authorized to discharge from Outfall 001. Such discharges shall be limited
and monitored 1 by the Permittee as specified below:
EFFLUENT LIMITS MONITORING REQUIREMENTS 1
CHARACTERISTICS --[-Monthly Daily Measurement Sample Sample
[Parameter Code] Average Maximum Frequency Type Location 2
Flow 50050 0.012 MGD Weekly Instantaneous I or E
Total Residual Chlorine 3 50060 28 gg/L 2/Weekly Grab E
Dissolved Oxygen 00300 Weekly Grab E
pH 00400 Not<6.0 nor>9.0 Weekly Grab E
standard units
Temperature(°C) 00010 Weekly Grab E
Fecal Coliform 31616 200/100 ml 400/100 ml 2/Monthly Grab E
(geometric mean)
BOD,5-day(20°C) C0310 30.0 mg/L 45.0 mg/L 2/Monthly Grab E
Total Suspended Solids C0530 30.0 mg/L 45.0 mg/L 2/Monthly Grab E
Ammonia[NH3 as N] C0610 13 mg/L 35 mg/L 2/Monthly Grab E
Footnotes:
4. eDMR-beginning no later than 270 days from the effective date of this permit,the Permittee shall
report electronically all discharge monitoring data using NCDWR's Electronic Discharge Monitoring
Report(eDMR)internet application(see Section A.(3.).
5. Sampling:E=Effluent;I=Influent. A given effluent sample shall accurately represent the chemical
and physical character of its discharge event.
6. Total Residual Chlorine(TRC)—The Permittee shall monitor and report Total Residual Chlorine
only if chlorine is used to disinfect.TRC effluent concentrations reported below 50µg/L shall be
deemed compliant with this permit,however the Permittee shall submit all levels reported by NC-
certified test methods(including field certified), even if these levels are below 50µg/L.
Condition:
• The Permittee shall discharge no floating solids or foam.
Page 4 of 6
A. (3.) ELECTRONIC REPORTING - DISCHARGE MONITORING REPORTS
Proposed federal regulations require electronic submittal of all discharge monitoring reports(DMRs)
and specify that, if a state does not establish a system to receive such submittals,then Permittees must
submit DMRs electronically to the Environmental Protection Agency(EPA). The Division anticipates
that these regulations will be adopted and will begin implementing in 2013.
NOTE: This special condition supplements or supersedes the following sections within Part II of this
permit(Standard Conditions for NPDES Permits):
• Section B.(11.) Signatory Requirements
• Section D.(2.) Reporting
• Section D.(6.) Records Retention
• Section E.(5.) Monitoring Reports
I. Reporting [Supersedes Part H.Section D.(2.)and Section E. (5.)(a)l
Beginning no later than 270 days from the effective date of this permit,the Permittee shall report
discharge monitoring data electronically using the NC DWR's Electronic Discharge Monitoring
Report(eDMR)internet application.
Monitoring results obtained during the previous month(s) shall be summarized for each month and
submitted electronically using eDMR. The eDMR system allows permitted facilities to enter
monitoring data and submit DMRs electronically using the internet. Until such time that the state's
eDMR application is compliant with EPA's Cross-Media Electronic Reporting Regulation
(CROMERR),Permittees will be required to submit all discharge monitoring data to the state
electronically using eDMR and will be required to complete the eDMR submission by printing,
signing, and submitting one signed original and a copy of the computer printed eDMR to the
following address:
NC DENR/DWR/Information Processing Unit
ATTENTION: Central Files/eDMR
1617 Mail Service Center
Raleigh,North Carolina 27699-1617
If a Permittee is unable to use the eDMR system due to a demonstrated hardship or due to the
facility being physically located in an area where less than 10 percent of the households have
broadband access,then a temporary waiver from the NPDES electronic reporting requirements may
be granted and discharge monitoring data may be submitted on paper DMR forms(MR 1, 1.1, 2, 3)
or alternative forms approved by the Director. Duplicate signed copies shall be submitted to the
mailing address above.
Page 5 of 6
1 cc-
I
ADDENDUM—FACT SHEET NCO089478 Camp Watia WWTP—Mav 19 2015
An Authorization to Construct(A to C) application was received 12/12/14 for yet-to- be built domestic
treatment plant for NCO089478 Camp Watia WWTP. The NPDES permit provided a limitation page for
0.012 MGD but the A to C application was for a phase I initial plant operation/design of 0.006 MGD.To
proceed with the A to C permit, a 0.006 MGD limitation page was required in the NPDES permit. After
discussions with the permittee, it was agreed a minor NPDES permit modification would be issued
adding the intermediate 0.006 MGD limitation page with identical limits and monitoring requirements,
except for the flow limit, as stated for the 0.012 MGD limitation page. Because of the addition of the j
0.006 MGD flow page,to expand to 0.012 MGD will require the permittee to obtain an A to C permit and i
submit a signed Engineer's Certificate for the expansion.Various technical corrections to narratives and
formatting were made wh a required.
NAME: DATE: J <J
i
I
I-
I