HomeMy WebLinkAboutNC0067008_202304CEI_20230421DocuSign Envelope ID: EE9F34DO-BCDC-4B43-ABF3-ED29F15EOC1C
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO067008 I11 121 23/04/18 I17 18LC I 19 Ls_] I 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701 I 71 I LL J I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
11:00AM 23/04/18
17/12/01
Old Cove Creek School
NCSR 1214
Exit Time/Date
Permit Expiration Date
Sugar Grove NC 28679
12:30PM 23/04/18
22/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Paul E. Isenhour/ORC/828-898-6277/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Glenda Evans,PO Box 338 Sugar Grove NC 28679//828-297-2919/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Tricia Lowery DWR/WSRO WQ/336-776-9691/
ocuSigned by: 4/21/202 3
L
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
4/21/2023
r-L- T. 5,Jtr
EPA Form-JW5 (§ev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: EE9F34DO-BCDC-4B43-ABF3-ED29F15EOC1C
NPDES yr/mo/day Inspection Type
NC0067008 I11 12I 23/04/18 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
4/21/2023 — Inspection Summary
On 4/18/2023, Division of Water Resources staff Tricia Lowery conducted a routine compliance
inspection at Old Cove Creek School. Paul Isenhour & Chris Server were present during the
inspection. A review of records, data, and treatment components was completed. This review
reflected compliance with the subject permit.
Observation to note:
1. Grit chamber is approaching full capacity. Needs maintenance soon.
Page#
DocuSign Envelope ID: EE9F34DO-BCDC-4B43-ABF3-ED29F15EOC1C
Permit: NCO067008 Owner -Facility: Old Cove Creek School
Inspection Date: 04/18/2023 Inspection Type: Compliance Evaluation
Permit Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0
❑
❑ ❑
application?
Is the facility as described in the permit? 0
❑
❑ ❑
# Are there any special conditions for the permit? ❑
0
❑ ❑
Is access to the plant site restricted to the general public? 0
❑
❑ ❑
Is the inspector granted access to all areas for inspection? 0
❑
❑ ❑
Comment: Permit expired 9/30/2022. Renewal application sent to DEQ 3/22/2022. Facility is
operating under expired permit until permit is renewed. This is a simple package
treatment plant that only serves the recreation center. No residential use. The flow is
<1000 gallons/day. The plant is securely fenced, restricting access to public.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: DMRs reviewed were satisfactory with accurate information. Operator lops are in
order. COC's were properly documented. ORC is proper grade for system.
Page# 3
DocuSign Envelope ID: EE9F34DO-BCDC-4B43-ABF3-ED29F15EOC1C
Permit: NCO067008 Owner -Facility: Old Cove Creek School
Inspection Date: 04/18/2023 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Overall the facility is in good working order.
Grit Removal
Yes
No
NA
NE
Type of grit removal
a.Manual
b.Mechanical
❑
Is the grit free of excessive organic matter?
0
❑
❑
❑
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment: There is some buildup in the grit chamber, but not excessive. Inspector recommends
the chamber be pumps and cleaned soon.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system
Fixed
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
❑
❑
■
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
❑
■
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
■
❑
❑
❑
Comment: This is a small aeration basin. The foam does cover >25%, however it has a earth
odor and proper color. No indication during
inspection the basin is causing issue with
treatment process.
Forced air system that operates on a timer.
DO readings average -2 mg/I
Disinfection -Tablet
Yes
No
NA
NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
Is the level of chlorine residual acceptable?
1
■ ❑ ❑ ❑
Page# 4
DocuSign Envelope ID: EE9F34DO-BCDC-4B43-ABF3-ED29F15EOC1C
Permit: NC0067008 Owner -Facility:
Inspection Date: 04/18/2023 Inspection Type:
Old Cove Creek School
Compliance Evaluation
Disinfection -Tablet
Yes
No
NA
NE
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment: The contact chamber for disinfection was in good shape. No issues found during
inspection.
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Comment: The feed ratio is 1:1. No issues found during inspection.
Yes No NA NE
Tablet
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Are tablet de -chlorinators operational? M ❑ ❑ ❑
Number of tubes in use? 1
Comment: Proper storage of chlorination/dechlori nation products. Proper type of tablets used in
treatment.
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Comment: The facility has a return sludqe holdinq tank. When needed (once a year), it is
pumped. It is pumped by Triple T Pumping, Inc. Last pumped 12/7/2022.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: No issues found during inspection.
Page# 5