Loading...
HomeMy WebLinkAboutNC0064378_Fact Sheet_20230313FACT SHEET FOR EXPEDITED PERMIT RENEWALS This form must be completed by Permit Writers for all expedited permits which do not require full Fact Sheets. Expedited permits are generally simple 100% domestics (e.g., schools, mobile home parks, etc.) that can be administratively renewed with minor changes but can include facilities with more complex issues (Special Conditions, 303(d) listed water, toxicity testing, instream monitoring, compliance concerns). Basic Information for Expedited Permit Renewals Permit Writer/Date Charles H. Weaver — 3/13/2023 Permit Number NCO064378 Facility Name Willowbrook WWTP Basin Name/Sub-basin number Neuse / 03-04-02 Receiving Stream UT to Beddin field Creek Stream Classification in Permit C-NSW Does permit need Daily Max NH3 limits? Limits at 0.03 MGD flow phase will convert to toxicity -based limits in January 2028, as per 2016 NH3 guidance. Limits at 0.06 MGD are already at BAT. Does permit need TRC limits/language? No — already resent Does permit have toxicity testing? Removed at this renewal due to reduction in NH3 limits at 0.03 MGD]. Does permit have Special Conditions? Neuse special conditions Does permit have instream monitoring? Dissolved oxygen and temperature Is the stream impaired (on 303(d) list)? For whatparameter? Stream segment has been on 303 (d) list since 2014 for Benthos Any obvious compliance concerns? No enforcements since 2018. Five NOVs during this permit cycle. Any permit mods since lastpermit? No New expiration date 3/31/2028 Changes to Draft Permit? ➢ Added BAT NH3 limits for 0.03 MGD flow phase and deleted toxicity testing, as per 2016 NH3 guidance. ➢ Updated eDMR language ➢ Added Neuse modeling reopener