HomeMy WebLinkAboutWQ0013027_Compliance Evaluation Inspection_20210831 (2)Comoliance Insoection Resort
Permit: WQ0013027 Effective: 04/10/17 Expiration: 03/31/22 Owner : The Sea Isle Plantation North Homeowners
Association
SOC: Effective: Expiration: Facility: Sea Isle Plantation North WWTP
County: Carteret Sea Isle N Dr
Region: Wilmington
Indian Beach NC 28512
Contact Person: Grady W Fulcher
Title:
Phone: 252-247-4017
Directions to Facility:
Take NC 58 East/North about one mile past Indian Beach. Facility is on the left, prior to Pine Knoll Shores.
System Classifications: WW3.,
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
On -site representative Daniel Edward Fortin 252-393-8720
Related Permits:
Inspection Date: 08/31/2021 Entry Time 09:OOAM Exit Time: 10:30AM
Primary Inspector: Brian S West Phone: 910-796-7341
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Treatment Filters
Use Records
Record Keeping Treatment Activated Sludge Treatment Sludge Storage/Treatment
End Use -Irrigation Treatment Clarifiers Treatment Disinfection
Treatment Flow Measurement Treatment Return pumps Standby Power
(See attachment summary)
Page 1 of 6
Permit: WQ0013027 Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Date: 08/31/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Routine compliance inspection with Fortin Contracting Services staff, their assistance during the visit was appreciated
System continues to experience periodic total nitrogen (TN) effluent limit exceedances. There have been no effluent TN
exceedances in the past 5 months and no monitoring well limit exceedances of any measured nitrogen parameter over the
past 2 years.
As a reminder, application for renewal of this permit is required to be submitted no later than 6 months prior to expiration on
3/31 /2022.
Please review individual comments under each section in the report, and address findings as noted.
Page 2 of 6
Permit: WQ0013027
Inspection Date: 08/31/2021
Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Type: Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Infiltration System
❑
Single Family Spray, LR
❑
Lagoon Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Drip, LR
❑
Single Family Drip
❑
Recycle/Reuse
❑
Activated Sludge Spray, HR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment:
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ 0 ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment:
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
0
❑ ❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑ ❑ ❑
Does flowmeter record flow?
❑ ❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment: Meter calibrated annually as required
Standby Power Yes No NA NE
Is automatically activated standby power available? 0 ❑ ❑ ❑
Page 3 of 6
Permit: WQ0013027 Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Date: 08/31/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Is generator tested weekly by interrupting primary power source? 0 ❑ ❑ ❑
Is generator operable? 0 ❑ ❑ ❑
Does generator have adequate fuel? ❑ ❑ ❑
Comment: Alternate portable generator on -site due to operational issues with regular unit. Portable unit
powered up on main shut-off and transferred power to plant as required
Treatment Activated Sludge
Yes No NA NE
Is the aeration mechanism operable?
❑ ❑ ❑
Is the aeration basin thoroughly mixed?
❑ ❑ ❑
Is the aeration equipment easily accessed?
❑ ❑ ❑
Is Dissolved Oxygen adequate?
❑ ❑ ❑
Are Settleometer results acceptable?
❑ ❑ ❑
Is activated sludge an acceptable color?
❑ ❑ ❑
Comment:
Treatment Clarifiers
Yes No NA NE
Are the weirs level?
0
❑ ❑ ❑
Are the weirs free of solids and algae?
❑ ❑ ❑
Is the scum removal system operational?
❑ ❑ ❑
Is the scum removal system accessible?
❑ ❑ ❑
Is the sludge blanket at an acceptable level?
❑ ❑ ❑
Is the effluent from the clarifier free of excessive solids?
❑ ❑ ❑
Comment:
Treatment Return pumps Yes No NA NE
Are they in place? 0 ❑ ❑ ❑
Are they operational? 0 ❑ ❑ ❑
Comment:
Treatment Filters
Yes No NA NE
Is the filter media present?
0
❑ ❑ ❑
Is the filter media the correct size and type?
0
❑ ❑ ❑
Is the air scour operational?
❑
❑ ❑
Is the scouring acceptable?
❑
❑ ❑
Is the clear well free of excessive solids?
❑ ❑ ❑
Is the mud well free of excessive solids and filter media?
❑
❑ ❑
Does backwashing frequency appear adequate?
❑ ❑ ❑
Comment: Filters backwashed manually dail
Treatment Sludge Storage/Treatment Yes No NA NE
Page 4 of 6
Permit: WQ0013027 Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Date: 08/31/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Is the aeration operational? 0 ❑ ❑ ❑
Is the aeration pattern even? 0 ❑ ❑ ❑
If required, are Sanitary "Ts" present in tankage? ❑ ❑ 0 ❑
Comment:
Treatment Disinfection
Yes No NA NE
Is the system working?
0
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
0
❑ ❑ ❑
Is there adequate detention time (-30 minutes)?
❑
❑ ❑
Is the system properly maintained?
0
❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ 0 ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ 0 ❑
Is the chlorinator accessible?
0
❑ ❑ ❑
If tablets, are tablets present?
0
❑ ❑ ❑
Are the tablets the proper size and type?
0
❑ ❑ ❑
Is contact chamber free of sludge, solids, and growth?
0
❑ ❑ ❑
If UV, are extra UV bulbs available?
❑
❑ 0 ❑
If UV, is the UV intensity adequate?
❑
❑ 0 ❑
# Is it a dual feed system?
❑
❑ 0 ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ 0 ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ 0 ❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment:
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑
❑ ❑
Are monitoring reports present: NDMR?
❑
❑ ❑
NDAR?
❑
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑
❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑
❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Page 5 of 6
Permit: WQ0013027 Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Date: 08/31/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Are annual soil reports available?
❑
❑ 0 ❑
# Are PAN records required?
❑
❑ 0 ❑
# Did last soil report indicate a need for lime?
❑
❑ 0 ❑
If so, has it been applied?
❑
❑ ❑ ❑
Are operational logs present?
0
❑ ❑ ❑
Are lab sheets available for review?
❑
❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
0
❑ ❑ ❑
Were Operational and Maintenance records complete?
0
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑
❑ ❑
Is a copy of the SOC readily available?
❑
❑ 0 ❑
No treatment units bypassed since last inspection?
❑
❑ 0 ❑
Comment: Periodic exceedances of TDS in monitoring
wells, not uncommon in barrier islands monitoring_
wells
End Use-Irriqation
Yes No NA NE
Are buffers adequate?
❑ ❑ ❑
Is the cover crop type specified in permit?
❑
❑ ❑
Is the crop cover acceptable?
❑
❑ ❑
Is the site condition adequate?
❑ ❑ ❑
Is the site free of runoff / ponding?
❑ ❑ ❑
Is the acreage specified in the permit being utilized?
❑ ❑ ❑
Is the application equipment present?
❑ ❑ ❑
Is the application equipment operational?
❑
❑ ❑ ❑
Is the disposal field free of limiting slopes?
❑ ❑ ❑
Is access restricted and/or signs posted during active site use?
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
How close is the closest water supply well?
❑
❑ ❑
Is municipal water available in the area?
❑ ❑ ❑
# Info only: Does the permit call for monitoring wells?
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑
❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Are monitoring wells damaged?
❑
❑ ❑
Comment: Need to clear vegetation to improve access to monitoring wells
Page 6 of 6